Quick Reference Guide 
DF5 Frequency Inverter

02/02 AWB8230-1447GB

4

Fault messages

When an overcurrent, overvoltage or undervoltage occurs, the 
output of the DF5 frequency inverter is disabled to protect the DF5 
from damage. The connected motor then coasts to a stop. The 
inverter remains in this condition until the fault message is 
acknowledged with the OFF key or the RST input.

 

Display

Cause

Description

E 01 

Overcurrent in the output stage in 
static operation

If the output current reaches an excessive level, the output voltage is switched off. This happens 
when
• the frequency inverter’s output is short-circuited,
• the motor is blocked,
• an excessive load is suddenly applied to the output.

E 02 

Overcurrent in the output stage 
during deceleration

E 03 

Overcurrent in the output stage 
during acceleration

E 04 

Overcurrent in the output stage at 
standstill

E 05 

Overload

The internal electronic motor protection has switched off the output voltage because the motor was 
overloaded.

E 07 

Overvoltage

The output voltage has been switched off because the motor was operating regeneratively.

E 08 

EEPROM fault

If the program memory does not operate reliably due to radio frequency interference or excessive 
temperature, the output voltage is switched off.
If the supply voltage is switched off while the RST input is active, an EEPROM fault occurs when the 
supply voltage is reapplied.

E 09 

Undervoltage

If the DC voltage is too low, the output voltage is switched off (fault-free function of electronics no 
longer possible; any problems, such as overheating of motor and insufficient torque).

E 11 

Processor malfunction

The processor does not operate correctly. The output voltage is switched off.

E 12 

External fault message

The output voltage is switched off due to an external fault message which is present on a digital 
input configured as an EXT input. 

E 13 

Restart inhibit activated

The mains voltage was switched on or an intermittent interruption in the supply voltage has occurred 
while unattended start protection (input USP) was active.

E 14 

Earth fault

Earth faults between the U, V or W terminals and earth are being reliably detected. A protective 
circuit prevents destruction of the frequency inverter, but does not protect the operating personnel.

E 15 

Mains overvoltage

If the supply voltage is higher than permitted, the output voltage is switched off 100 seconds after 
the voltage supply has been switched on.

E 21 

Overtemperature

If the temperature sensor installed in the power section records an operating temperature above the 
permissible limit value, the output voltage is switched off.

E 22

Processor malfunction

The processor does not operate correctly. The output voltage is switched off.

E 35 

PTC fault signal 

If the resistance of the external PTC thermistor connected to the PTC input (digital input configured 
as a PTC thermistor input) is too high, the output voltage is switched off. 

Содержание DF5 series

Страница 1: ...l brand and product names are trademarks or registered trademarks of the owner concerned All rights reserved including those of the translation No part of this manual may be reproduced in any form pri...

Страница 2: ...quency inverter has power d Hz or A LED Indication in b Output frequency Hz or output current A e Potentiometer and LED Frequency setpoint setting LED is lit when the potentiometer is activated f ENTE...

Страница 3: ...efault to the keypad Figure 2 Specify setpoint definition through keypad RUN PRG POWER Hz A MIN MAX PRG ENTER POWER Hz POWER PRG POWER PRG PRG DF5 3 x DF5 3 x PRG PRG PRG ENTER POWER PRG MIN MAX PRG P...

Страница 4: ...eys and the PRG key at the same time and keep them pressed X While holding the arrow and PRG keys briefly press the OFF key X Keep the other three keys pressed for three further seconds until the foll...

Страница 5: ...the supply voltage is reapplied E 09 Undervoltage If the DC voltage is too low the output voltage is switched off fault free function of electronics no longer possible any problems such as overheatin...

Страница 6: ...B8230 1412GB section Automatic restart after a fault page 97 The default settings have been selected and the frequency inverter is in the initialization phase PNU b84 and b85 a AWB8230 1412GB section...

Страница 7: ...Starting frequency 00 Apply PNU A11 to motor 01 Apply 0 Hz to motor 01 A16 Analog input filter time constant 0 to 8 8 A20 Frequency setpoint definition PNU A01 must be 02 0 5 to 360 Hz 0 0 A21 1st fi...

Страница 8: ...A68 Jump width of the 3rd frequency jump 0 1 to 10 Hz 0 5 A71 PID control 00 Inactive 01 Active 00 A72 P component of the PID control 0 2 to 50 1 0 A73 I component of the PID control 0 0 to 150 s 1 0...

Страница 9: ...ugh SFT input all functions inhibited 01 Through SFT input function F01 possible 02 Without SFT input all functions inhibited 03 Without SFT input function F01 possible 01 b32 Magnetizing current 0 to...

Страница 10: ...contact 01 Break contact 00 C12 Digital input 2 Values a PNU C11 00 C13 Digital input 3 Values a PNU C11 00 C14 Digital input 4 Values a PNU C11 00 C15 Digital input 5 Values a PNU C11 00 C21 Signal...

Страница 11: ...ack display d05 Status of digital inputs 1 to 6 d06 Status of digital outputs 11 and 12 d07 Scaled output frequency d08 Display of last alarm d09 Display of second and third from last alarm PNU Meanin...

Отзывы: