background image

02/02 AWB8230-1447GB

Restoring the Default Settings

3

Restoring the Default Settings

Initialization

Two different types of initialization are available:

• Clearing the fault history register
• Restoring the default parameter settings 

To delete the fault history register or to restore the default 
settings, proceed as follows:

X

Make sure that PNU b85 holds the value.

X

Under PNU b84 (initialization), enter 00 or 01.

X

Press the ENTER key to save the value.

X

On the keypad, press both arrow keys and the PRG key at the 
same time and keep them pressed.

X

While holding the arrow and PRG keys, briefly press the 
OFF key.

X

Keep the other three keys pressed for three further seconds until 
the following flashing display appears: 

d 00

X

Now release all keys again.

Initialization is now complete. 

Country version

Here, you define the country-specific parameter set which will be 
loaded during initialization (

a

 PNU b84). 

PNU

Name

Adjustable in 
RUN mode

Value

Function

WE

b84

Initialization

00

Clearing the fault history register

00

01

Restoring the default parameter settings

PNU

Name

Adjustable in 
RUN mode

Value

Function

WE

b85

Country 
version

00

Japan

01

01

Europe

02

USA

03

Reserved

Содержание DF5 series

Страница 1: ...l brand and product names are trademarks or registered trademarks of the owner concerned All rights reserved including those of the translation No part of this manual may be reproduced in any form pri...

Страница 2: ...quency inverter has power d Hz or A LED Indication in b Output frequency Hz or output current A e Potentiometer and LED Frequency setpoint setting LED is lit when the potentiometer is activated f ENTE...

Страница 3: ...efault to the keypad Figure 2 Specify setpoint definition through keypad RUN PRG POWER Hz A MIN MAX PRG ENTER POWER Hz POWER PRG POWER PRG PRG DF5 3 x DF5 3 x PRG PRG PRG ENTER POWER PRG MIN MAX PRG P...

Страница 4: ...eys and the PRG key at the same time and keep them pressed X While holding the arrow and PRG keys briefly press the OFF key X Keep the other three keys pressed for three further seconds until the foll...

Страница 5: ...the supply voltage is reapplied E 09 Undervoltage If the DC voltage is too low the output voltage is switched off fault free function of electronics no longer possible any problems such as overheatin...

Страница 6: ...B8230 1412GB section Automatic restart after a fault page 97 The default settings have been selected and the frequency inverter is in the initialization phase PNU b84 and b85 a AWB8230 1412GB section...

Страница 7: ...Starting frequency 00 Apply PNU A11 to motor 01 Apply 0 Hz to motor 01 A16 Analog input filter time constant 0 to 8 8 A20 Frequency setpoint definition PNU A01 must be 02 0 5 to 360 Hz 0 0 A21 1st fi...

Страница 8: ...A68 Jump width of the 3rd frequency jump 0 1 to 10 Hz 0 5 A71 PID control 00 Inactive 01 Active 00 A72 P component of the PID control 0 2 to 50 1 0 A73 I component of the PID control 0 0 to 150 s 1 0...

Страница 9: ...ugh SFT input all functions inhibited 01 Through SFT input function F01 possible 02 Without SFT input all functions inhibited 03 Without SFT input function F01 possible 01 b32 Magnetizing current 0 to...

Страница 10: ...contact 01 Break contact 00 C12 Digital input 2 Values a PNU C11 00 C13 Digital input 3 Values a PNU C11 00 C14 Digital input 4 Values a PNU C11 00 C15 Digital input 5 Values a PNU C11 00 C21 Signal...

Страница 11: ...ack display d05 Status of digital inputs 1 to 6 d06 Status of digital outputs 11 and 12 d07 Scaled output frequency d08 Display of last alarm d09 Display of second and third from last alarm PNU Meanin...

Отзывы: