02/02 AWB8230-1447GB

Standard form for user defined 
parameter settings

9

PNU

Meaning

Value range

Def.

Setpoint

C01

Function of digital input 1

• 00: FWD, clockwise operation
• 01: REV, anticlockwise operation
• 02: FF1, first fixed frequency input
• 03: FF2, second fixed frequency input
• 04: FF3, third fixed frequency input
• 05: FF4, fourth fixed frequency input
• 06: JOG, jog mode
• 09: 2CH, second time ramp
• 11: FRS, controller inhibit
• 12: EXT, external fault
• 13: USP, unattended start protection
• 15: SFT, parameter protection
• 16: AT, input OI is used
• 18: RST, reset
• 19: PTC, PTC thermistor input 

(digital input 5 only)

00

C02

Function of digital input 2

Values 

a

 PNU C01

01

C03

Function of digital input 3

Values 

a

 PNU C01

02

C04

Function of digital input 4

Values 

a

 PNU C01

03

C05

Function of digital input 5

Values 

a

 PNU C01

18

C11

Digital input 1

• 00: Make contact
• 01: Break contact

00

C12

Digital input 2

Values 

a

 PNU C11

00

C13

Digital input 3

Values 

a

 PNU C11

00

C14

Digital input 4

Values 

a

 PNU C11

00

C15

Digital input 5

Values 

a

 PNU C11

00

C21

Signal on digital output 11

• 00: RUN signal
• 01: FA1, frequency reached
• 02: FA2, frequency exceeded
• 03: OL, Overload
• 04: OD, PID deviation exceeded
• 05: AL, fault

01

C22

Signal on digital output 12

Values 

a

 PNU C21

00

C23

Indication through FM output

• 00: Frequency, analog
• 01: Motor current, analog
• 02: Output frequency pulse signal

00

C31

Digital output 11

• 00: Make contact
• 01: Break contact

01

C32

Digital output 12

• 00: Make contact
• 01: Break contact

01

C33

Relay output K11-K12 (signalling relay)

• 00: Make contact
• 01: Break contact

01

C41

Threshold for overload alarm at digital 
outputs 11 and 12

0 to 2 

x

 

I

e

 [A]

I

e

 

C42

Frequency from which FA2 is switched on 
during acceleration 

0 to 360 Hz

0.0

C43

Frequency from which FA2 is switched off 
during deceleration

0 to 360 Hz

0.0

C44

PID control deviation (from the maximum 
set point value)

0 to 100 %

3.0

Содержание DF5 series

Страница 1: ...l brand and product names are trademarks or registered trademarks of the owner concerned All rights reserved including those of the translation No part of this manual may be reproduced in any form pri...

Страница 2: ...quency inverter has power d Hz or A LED Indication in b Output frequency Hz or output current A e Potentiometer and LED Frequency setpoint setting LED is lit when the potentiometer is activated f ENTE...

Страница 3: ...efault to the keypad Figure 2 Specify setpoint definition through keypad RUN PRG POWER Hz A MIN MAX PRG ENTER POWER Hz POWER PRG POWER PRG PRG DF5 3 x DF5 3 x PRG PRG PRG ENTER POWER PRG MIN MAX PRG P...

Страница 4: ...eys and the PRG key at the same time and keep them pressed X While holding the arrow and PRG keys briefly press the OFF key X Keep the other three keys pressed for three further seconds until the foll...

Страница 5: ...the supply voltage is reapplied E 09 Undervoltage If the DC voltage is too low the output voltage is switched off fault free function of electronics no longer possible any problems such as overheatin...

Страница 6: ...B8230 1412GB section Automatic restart after a fault page 97 The default settings have been selected and the frequency inverter is in the initialization phase PNU b84 and b85 a AWB8230 1412GB section...

Страница 7: ...Starting frequency 00 Apply PNU A11 to motor 01 Apply 0 Hz to motor 01 A16 Analog input filter time constant 0 to 8 8 A20 Frequency setpoint definition PNU A01 must be 02 0 5 to 360 Hz 0 0 A21 1st fi...

Страница 8: ...A68 Jump width of the 3rd frequency jump 0 1 to 10 Hz 0 5 A71 PID control 00 Inactive 01 Active 00 A72 P component of the PID control 0 2 to 50 1 0 A73 I component of the PID control 0 0 to 150 s 1 0...

Страница 9: ...ugh SFT input all functions inhibited 01 Through SFT input function F01 possible 02 Without SFT input all functions inhibited 03 Without SFT input function F01 possible 01 b32 Magnetizing current 0 to...

Страница 10: ...contact 01 Break contact 00 C12 Digital input 2 Values a PNU C11 00 C13 Digital input 3 Values a PNU C11 00 C14 Digital input 4 Values a PNU C11 00 C15 Digital input 5 Values a PNU C11 00 C21 Signal...

Страница 11: ...ack display d05 Status of digital inputs 1 to 6 d06 Status of digital outputs 11 and 12 d07 Scaled output frequency d08 Display of last alarm d09 Display of second and third from last alarm PNU Meanin...

Отзывы: