AIR14-501.2

START-UP PROCEDURE

Typical Sequence of Operation

 

Supply Fan

The supply fan shall run at all times when unit is in occupied 

mode. When in unoccupied mode, the supply fan shall run only 

on a call for heating or cooling. The supply fan speed can be 

adjusted using the standard equipped manual 3-speed switch. 

If equipped with Modine Control System, the supply fan is 

programmed to run for 2 minutes (adjustable) after the heating 

or cooling cycle ends.

Freeze Stat (Optional)

On units equipped, an adjustable auto-resetting freeze stat is 

factory set to trip at 35˚F. If the coil temperature reaches the 

limit and the freeze stat trips, it shall automatically reset when 

the coil temperature rises 5˚F above the setpoint. The freeze 

stat shall be wired so that upon tripping, power is removed from 

the supply fan, the outside air damper closes, and either the 

HW valve opens (model digit 3=V) or the face & bypass damper 

goes to full bypass (model digit 3=F).

Outside Air and Return Air Dampers (Optional)

The outside air and return air dampers control the mixture of 

return air and outside air drawn through the unit. Both dampers 

are linked together and are controlled by an actuator requiring a 

2-6VDC proportional signal. At 2V, the dampers are positioned 

for full return air and no outside air. At 6V, the dampers are 

positioned for full outside air and no return air. The outside air 

damper shall open to a minimum position to provide ventilation 

requirements when the room is occupied. When in heating 

mode, if the space temperature is more than 4˚F from the 

heating setpoint, the outside air damper shall fully close. The 

outside air damper shall also be fully closed during unoccupied 

mode. If the unit is equipped with a CO

2

 sensor, the outside air 

damper shall modulate open proportionally to compensate for 

the CO

2

 levels in the room.

The dampers can act as economizers for free-cooling. If 

cooling is required and the outside air temperature is below 

the economizer outside air lockout temperature (60˚F 

recommended) and above 35˚F (adjustable), the outside air 

damper shall modulate open. On units with a Carel controller, 

the outside air damper shall fully open when the room 

temperature is above the setpoint by more than 1˚F (adjustable). 

Within 1˚F, the proportional band adjusts the outside air damper. 

When the unit is in free-cooling, water valves shall be fully 

closed, and if equipped, the face & bypass damper should move 

to full bypass position. The outside air lockout temperature on 

Carel units is factory set to 60˚F and is adjustable.

Chilled Water with Valve Control

Units with a chilled water coil and non-Carel controls desiring 

valve control shall use a non-spring return modulating valve 

operated by either a proportional (2-10VDC) or a tri-state 

(24VAC) signal. Units with a chilled water coil and Carel controls 

desiring valve control shall use a modulating valve requiring a 

tri-state signal. When the room temperature is above the cooling 

setpoint, the valve shall open proportionally according to the 

adjustable proportional band. The adjustable proportional band 

on the Carel controller is set to a default 1˚F (example: valve is 

50% open when room temperature is 0.5˚F from setpoint). The 

Carel controller will not allow the chilled water valve to open 

when the outside air temperature is below 55˚F.

Hot Water or Steam with Valve Control

Units with a hot water or steam coil and non-Carel controls 

desiring valve control shall use a spring-return, normally open 

modulating valve operated by a proportional signal (2-10VDC) 

or a tri-state (24VAC) signal. Units with Carel controls desiring 

valve control shall use a modulating control valve with a 

proportional signal. When the room temperature is below the 

heating setpoint, the valve shall open proportionally according 

to the adjustable proportional band. The adjustable proportional 

band on the Carel controller is set to a default 1˚F (example: 

valve is 50% open when room temperature is 0.5˚F from 

setpoint). If for any reason the supply air temperature drops 

below 55˚F (adjustable), the valve shall modulate open to 

maintain 55˚F.

Direct Expansion (DX) Cooling Control

When the room temperature is above the cooling setpoint, the 

compressor will be energized. The compressor will de-energize 

when the room temperature falls below the cooling setpoint. 

If the factory installed low limit stat detects indoor evaporator 

coil temperatures below its set point, the compressor will be 

disabled.

Chilled Water with Face & Bypass Control

Units equipped with a chilled water coil and face & bypass 

control shall modulate the face & bypass damper via a spring 

return actuator, controlled by a proportional signal (2-5.5V). 

The face & bypass damper regulates the amount of return 

air and outside air passing through the chilled water coil. On 

a call for cooling, the damper shall open to the face of the 

coil proportionally based on how many degrees the room 

temperature is from the setpoint. The adjustable proportional 

band on the Carel controller is set to a default 1˚F (example: 

damper is 50% open when room temperature is 0.5˚F from 

setpoint). When the damper is in full bypass position (2V), all 

return and outside air bypasses the chilled water coil. When the 

damper is in full face position (5.5V), all return and outside air 

passes through the chilled water coil.

Hot Water with Face & Bypass Control

Units equipped with a hot water or steam coil and face & bypass 

control shall modulate the face & bypass damper via a spring 

return actuator, controlled by a proportional signal (2-5.5V). 

The face & bypass damper regulates the amount of return air 

and outside air passing through the heating coil. On a call for 

heating, the damper shall open proportionally based on how 

many degrees the room temperature is from the setpoint. The 

adjustable proportional band on the Carel controller is set 

to a default 1˚F (example: damper is 50% open when room 

temperature is 0.5˚F from setpoint). When the damper is in full 

bypass position (2V), all return and outside air bypasses the 

heating coil. When the damper is in full face position (5.5V), 

all return and outside air passes through the heating coil. If 

for any reason the supply air temperature drops below 55˚F 

(adjustable), the heating valve shall open (if equipped) and the 

face and bypass damper shall modulate to maintain 55˚F.

Hot Water and Chilled Water (2-Pipe) with Valve 

Control

Units desiring valve control to provide heating and cooling 

on a single water coil (2-pipe system) and not using Carel 

controls shall use a spring-return, normally open modulating 

valve operated by a proportional signal (2-10VDC) or a tri-

state (24VAC) signal. Units with Carel controls shall use a 

modulating control valve with a proportional signal. On a call 

for heating or cooling (depending on the season), the valve 

Содержание Varsity ZCF 1000

Страница 1: ...nded for a qualified installation and service agency A qualified installation and service agency must perform all installation and service of these appliances 2 ZCV and ZCF units with DX evaporator coils contain the refrigerant R 410A Review the R 410A Material Safety Data Sheet MSDS for hazards and first aid measures 3 Refrigerant charging should only be carried out by an EPA certified air condit...

Страница 2: ...n 3 Handling 3 Preparation 3 Drainage 3 Electrical 3 Installation 3 Piping Installation 4 Piping Insulation 5 Wiring 5 Terminal Strip Connections 5 Start Up Procedure 6 Pre Start Checks 6 Unit Start Up Procedure 6 Typical Sequence of Operation 7 8 Start Up Sheet Example 9 10 Dimensions 11 12 Technical Data 13 Component Layout 14 Maintenance 15 Troubleshooting 16 17 Replacement Parts Model Nomencla...

Страница 3: ...ould be sealed with waterproof sealant Drainage Units with cooling coils have a condensate drain pan connection and 3 4 ID condensate line The condensate drain pan connection is field changeable and can be mounted on either the left or right side of the unit To change the connection location remove the condensate line from the elbow Remove the elbow from the drain pan and remove the plug from the ...

Страница 4: ...1 Condensing unit is typically factory charged for a 15 foot lineset For additional lineset lengths please refer to manufacturer s charging chart See the installation and maintenance manual provided with the condensing unit for installation evacuation and system charge information 1 Chilled water and hot water coils are supplied from the factory with unions Field installed piping can be mounted to...

Страница 5: ...xtra cable must be left outside the panel to allow the panel to open fully Failure to follow these instructions may cause damage to the wiring and or the unit Terminal Strip Connections The terminal strip connections are designed to clamp down on the wires To properly connect the wires to the terminal strip 1 Push a small flat head screwdriver into the square hole on the terminal Press firmly unti...

Страница 6: ...p information 1 DX Cooling models only Ensure that the condensing unit start up procedure has been carried out as detailed in the condensing unit installation and maintenance manual 2 DX Cooling models only The compressor should be isolated by removing the connection at the Y1 terminal on the indoor unit Main power can now be applied to the indoor and outdoor units A system electrical check can no...

Страница 7: ...ide air temperature is below 55 F Hot Water or Steam with Valve Control Units with a hot water or steam coil and non Carel controls desiring valve control shall use a spring return normally open modulating valve operated by a proportional signal 2 10VDC or a tri state 24VAC signal Units with Carel controls desiring valve control shall use a modulating control valve with a proportional signal When ...

Страница 8: ... a call for heating The valve shall always open when the outside air temperature drops below 40 F This is to prevent the coil from freezing or nuisance tripping of the freeze stat The 2 position hot water valve shall be closed when the 2 position chilled water valve is open if equipped The valve is controlled by a 24VAC digital output The 2 position valve used on a 2 pipe changeover system shall o...

Страница 9: ...9 AIR14 501 2 START UP SHEET EXAMPLE Figure 9 1 Start Up Sheet EXAMPLE Page 1 ...

Страница 10: ...10 AIR14 501 2 START UP SHEET EXAMPLE Figure 10 1 Start Up Sheet EXAMPLE Page 2 ...

Страница 11: ...11 AIR14 501 2 DIMENSIONS Figure 11 1 Front Discharge Unit Table 11 1 Unit Dimensions Model Size Dimensions inches W1 W2 750 62 36 1000 74 48 1250 86 60 1500 98 72 ...

Страница 12: ...12 AIR14 501 2 DIMENSIONS Figure 12 1 Down Discharge Unit Table 12 1 Unit Dimensions Model Size Dimensions inches W1 W2 750 62 36 1000 74 48 1250 86 60 1500 98 72 ...

Страница 13: ...6 0 88 3 Row gal 0 72 0 91 1 1 1 28 4 Row gal 0 92 1 17 1 42 1 66 CONNECTIONS Water Coils Inches Unions with 3 4 female solder joint Evaporator Coil Inches 3 4 OD Suction 1 2 OD Liquid Steam Coil Inches 1 NPT Condensate Line Inches 3 4 ID condensate line UNIT WEIGHT approximate Shipping Weight lbs 375 420 470 520 Operating Weight lbs 320 365 410 450 FILTER 1 Woven Fiberglass 70 75 Arrestance Quant...

Страница 14: ...1 2 COMPONENT LAYOUT Figure 14 1 Exploded View PIPING TOP ACCESS PANELS BASE ASSEMBLY DAMPER ASSEMBLY CONTROL PANEL FILTER COIL ASSEMBLY BLOWER ASSEMBLY END PANELS BOTTOM ACCESS PANELS DISCHARGE AIR PANEL ASSEMBLY ...

Страница 15: ...cessary Remove the filter support bracket and slide the filter s out of the track Replace with new filter s and reinstall the filter support bracket see Figure 14 1 Never run the unit without filters Every SIX 6 MONTHS Before the heating and cooling season 1 Check for correct fan operation no excessive noise or vibrations With the Disconnect Switch in the OFF position 2 Inspect all electrical circ...

Страница 16: ...ections 5 Inspect connections beginning with compressor output from the microprocessor 6 Tripped circuit breakers 6 Reset the tripped circuit breaker s 7 Low temperature unit lockout 7 Consult microprocessor setpoints 8 DX Split Units Only Compressor faulty 8 Replace compressor 9 Condensate pan pump float switch tripped 9 Check condensate pan pump and piping for blockage C No Indoor Fan 1 Motor tr...

Страница 17: ...er installation of wall sleeve and louver 1 Ensure splitter plate is in contact with the back of the louver blade and the unit to ensure no re circulation of exhaust air takes place 2 Dirty condenser coils 2 Clean condenser coil 3 System overcharged 3 Remove excess refrigerant 4 Noncondensables in system 4 Evacuate refrigerant circuit and recharge 5 Condenser fan speed is too slow cooling mode 5 N...

Страница 18: ...m Outside Air R Bottom Return Air No Outside Air S Top Return Air No Outside Air 9 Discharge Air DA E Front Discharge with Duct Collar F Front Disch with Dbl Defl Grille G Down Disch with Dbl Defl Grille 10 Cooling Option CO 0 None 2 2 Row Chilled Water Hot Water 2 Pipe 3 3 Row Chilled Water Hot Water 2 Pipe 4 4 Row Chilled Water Hot Water 2 Pipe 5 Direct Expansion DX Cooling Only 11 Heating Optio...

Страница 19: ...19 AIR14 501 2 SERIAL PLATE Figure 19 1 Serial Plate EXAMPLE ...

Страница 20: ...UIPMENT MANUFACTURED BY BUYER BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER FOR GAS FIRED PRODUCTS INSTALLED IN HIGH HUMIDITY APPLICATIONS AND UTILIZING STAINLESS STEEL HEAT EXCHANGERS BUYER S REMEDY FOR BREACH AS LIMITED HEREIN SHALL BE LIMITED TO TEN YEARS FROM DATE OF SHIPMENT FROM SELLER These warranties are issued only to the origin...

Отзывы: