background image

4-522.4

19

service &  trouBlesHooting

 

 

remedy

   Problem B.  Burner motor operates but no oil delivered at nozzle.
  1.  Oil level below intake line inside supply tank.  

1.  Fill tank with oil and bleed air from the line.

  2.  Clogged strainer. 

  2.  Remove and clean strainer.

  3.  Clogged nozzle. 

  3.  Remove and clean or replace nozzle.

    4.  Air leak in the intake line. 

  4.  Tighten all fittings in the intake line. Tighten unused intake port plug in the fuel unit. If there are valves in  

  

 

 

the line, be sure the valve stems are packed solid and tightened securely.

  5.  Restricted intake lines (high vacuum).  

5.  Replace any kinked tubing and check all valves in the intake line.

  6.  A two pipe system that becomes air bound.  

6.  Insert by-pass plug if not in place. Prime pump.

  7.  A single pipe system that becomes air bound.  

7.  See start-up procedure.

  8.  Slipping or broken coupling. 

  8.  Tighten or replace coupling.

  9.  Frozen fuel unit shaft. 

  9.  Return unit to factory.

  10.  Excessive vacuum. 

10.  Use next larger tubing size. Too high of a lift. Also see B5.

  11.  Dirty oil filter cartridge. 

11.  Replace cartridge.

   Problem c.  Burner motor operates, delivers oil, but no flame.
  1.  No spark. 

  1.  Check the ignitor and high tension insulators.

  2.  Poor atomization of oil. 

  2.  Adjust oil pressure to 130 +/- 2psi for POR100 and 145, 100 +/- 2psi for POR 185, check for oil line  

  

 

 

restriction and nozzle defects.

  3.  Improper electrode setting. 

  3.  Remove firing assembly and adjust.

  4.  Excessive combustion air. 

  4.  See start-up procedure.

   Problem d.  Burner starts but flame blows away from nozzle.
  1.  Excessive combustion air. 

  1.  See start-up procedure.

  2.  Excessive draft. 

  2.  Adjust draft regulator.

  3.  Poor atomization of oil. 

  3.  Change nozzle with same capacity.

  4.  Uneven flame. 

  4.  Change nozzle with same capacity.

 

 

remedy

   Problem a. no oil flow at nozzle.
  1.  Oil level below intake line in supply tank.  

1.  Fill tank with oil. (Bleed air from oil lines.)

  2.  Clogged strainer or filter. 

  2.  Remove and clean strainer. Replace filter element.

  3.  Clogged nozzle. 

  3.  Replace nozzle.

  4.  Air leak in intake line. 

  4.  Tighten all fittings in intake line. Tighten unused intake port plug. Check filter cover and gasket.

  5.  Restricted intake line (high vacuum reading).  

5.  Replace any kinked tubing and check any valves in intake line. Check for correct line sizes.

  6.  A two-pipe system that becomes air bound.  

6.  Check for and insert by-pass plug. Make sure return line is below oil level in tank.

  7.  A single-pipe system that becomes air bound.  

7.  Loosen gauge port plug or easy flow valve and bleed oil for 15 seconds after foam is gone in bleed  

  

 

 

hose. Check intake line fittings for tightness. Check all pump plugs for tightness.

  8.  Slipping or broken coupling. 

  8.  Tighten or replace coupling.

  9.  Rotation of motor and fuel unit is not the same  

9.  Install fuel unit with correct rotation. 

  

as indicated by arrow on pad at top of unit.

  10.  Frozen fuel unit shaft. 

10.  Return unit to approved service station or factory for repair. Check for water and dirt in tank.

   Problem B. oil leak.
  1.  Loose plugs or fittings. 

  1.  Dope with good quality oil-resistant thread sealer. Retighten.

  2.  Leak at pressure adj. screw or nozzle plug.  

2.  Washer may be damaged. Replace washer or O-ring.

  3.  Blown seal (single-pipe system). 

  3.  Check if by-pass plug has been left in unit. Replace fuel unit.

  4.  Blown seal (two-pipe system). 

  4.  Check for kinked tubing or other obstructions in return line. Replace fuel unit.

  5.  Seal leaking. 

  5.  Replace fuel unit.

  6.  Cover loose. 

  6.  Tighten cover screws or replace damaged gasket.

   Problem c. noisy operation.
  1.  Bad coupling alignment. 

  1.  Loosen fuel unit mounting screws slightly and shift unit in different positions until noise is eliminated.  

  

 

 

Retighten mounting screws.

  2.  Air in inlet line. 

  2.  Check all connections. Use only good flare fittings.

  3.  Tank hum on two-pipe system and inside tank.  

3.  Install hum eliminator in return line.

   Problem d.  Pulsating pressure.
  1.  Partially clogged strainer or filter. 

  1.  Remove and clean strainer. Replace filter element.

  2.  Air leak in intake line. 

  2.  Tighten all fittings.

  3.  Air leaking around cover. 

  3.  Be sure strainer cover screws are tightened securely. Check for damaged cover gasket.

  4.  High vacuum. Should not exceed 17 inches  

4.  Closed shut-off valve, clogged filter, kinked tubing, too small on line. 

  

Hg (mercury).

   Problem e. low oil pressure.
  1.  Defective gauge. 

  1.  Check gauge against master gauge, or other gauge.

   Problem f. improper nozzle cut-off.
  1.  Filter leaks. 

  1.  Check face of cover and gasket for damage.

  2.  Strainer cover loose. 

  2.  Tighten screws on cover.

  3.  Air pocket cut-off valve and nozzle. 

  3.  Run burner, stopping and starting unit, until smoke and after-fire disappears.

  4.  Air leak in intake line. 

  4.  Tighten intake fittings. Tighten unused intake port and return plug.

  5.  Partially clogged nozzle strainer. 

  5.  Clean strainer or change nozzle.

  6.  Leak at nozzle adaptor. 

  6.  Change nozzle and adaptor.

oil Burner assembly (continued)

Burner fuel unit

Содержание POR

Страница 1: ...ry or death and could cause exposure to substances which have been determined by various state agencies to cause cancer birth defects or other reproductive harm read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment FOR YOUR SAFETY WHat to do if you smell gas 1 open windows 2 do not try to light any appliance 3 do not touch any electri...

Страница 2: ...of not less than one square inch per 1 000 BTU Hr input rating of all units in the enclosure with a minimum of 100 square inches for each opening whichever is greater IMPORTANT 1 To prevent premature heat exchanger failure do not locate ANY oil fired appliances in areas where corrosive vapors i e chlorinated halogenated or acid are present in the atmosphere 2 To check most of the Possible Remedies...

Страница 3: ...ade No 1 or 2 with a flash point not less than 100 F is approved for these unit heaters as specified by ASTM D396 73 Standard Specification for Fuel Oils or the Canadian Government Specification Board 3 GP 28 American Society for Testing and Materials si metric conversion factors unit location CAUTION 1 Do not locate units in tightly sealed rooms or small compartments commonly referred to as confi...

Страница 4: ...r suspension methods note A pipe hanger adapter kit shown in figure 4 1 is available as an accessory from Modine or can be self fabricated Kit consists of two drilled 3 4 I P S pipe caps and two 1 2 13 x 1 3 4 capscrews to facilitate threaded pipe suspension Two kits are required for mounting each unit figure 4 1 suspension methods venting 1 To dispose of flue gasses all oil fired heaters must be ...

Страница 5: ...r in at least 1 2 inch thin wall or flexible metal conduit thermostat Wiring The proper wiring for a single thermostat for each unit heater is shown in Figure 6 1 The multiple unit wiring diagram shown in Figure 6 2 illustrates typical wiring and connections used with a centralized oil distribution system for multiple unit installations This diagram is provided as a reference only and is not inten...

Страница 6: ...NG PRIMARY CONTROL This diagram is provided for reference only System operation and compliance with local codes is the responsibility of the installer Note All wiring shown as dashed lines is field wiring FIELD WIRING JUNCTION BOX ON HEATER 115V 60HZ 1Ø GROUND IN J BOX FUSED DISCONNECT SWITCH BY OTHERS PRESSURE SWITCH ACCESSORY BURNER MOTOR LOW VOLTAGE T STAT BY OTHERS UNIT 1 T T BURNER HOUSING PR...

Страница 7: ...ipe systems See Figure 8 1 If more than one unit is piped to the same tank separate suction oil lines must be installed for each unit A single common line however can be piped in series for fuel oil return one Pipe system The fuel units supplied contain an internal by pass and are shipped from the factory with the by pass plug in place for one pipe installations only supply line connected to fuel ...

Страница 8: ...ceed 3 PSIG For multiple unit systems as shown in Figures 9 1 and 9 2 install a generous capacity oil filter in the inlet line to booster pump suction line Refer to Figure 6 2 for a typical wiring diagram for multiple unit installations oil tanks To provide for a safe and continuous fuel supply the tanks and piping to the unit heaters must be installed in accordance with state and local codes and ...

Страница 9: ...4 522 4 9 installation figure 9 1 typical loop system for multiple units figure 9 2 typical Pressurized supply system for multiple units ...

Страница 10: ...fuel filter oil safety valve osv The Oil safety valve can be installed in any position Preferred position is cover up The IN port is connected to the supply line the OUT port to the burner line Do not install backwards The Oil safety valve is opened by a slight vacuum appearing at the outlet of the Oil safety valve generated by the burner fuel unit Failure to observe the above caution may result i...

Страница 11: ...When the fan and limit switch detects the proper temperature it will turn on the circulating air fan The time it takes before the circulating air fan turns on after the burner is started is a function of the temperature setting on the fan and limit switch When the thermostat is satisfied the primary control will shut off the burner The circulating air fan will shut off when the fan and limit switc...

Страница 12: ... temperatures 2 Open shut off valves at tank and in oil supply line to the burner 3 Turn on power to the unit If burner does not start immediately push reset buttons on burner motor and primary control 4 For units installed on a single pipe system vent air from fuel unit and oil supply lines immediately after the burner motor starts Vent air by opening bleeder valve on fuel unit until oil appears ...

Страница 13: ...ction procedures 2 Tighten fan guard and motor bracket Check fan for proper clearance free rotation and firm connection to motor shaft Clean fan blade with detergent or compressed air 3 Fan motor is permanently lubricated for normal operation Under severe conditions lubricate with non detergent SAE 20 motor oil 4 Routine cleaning of the unit casing and louvers is recommended to remove dirt grease ...

Страница 14: ... for an accumulation of dirt or soot Clean if necessary with a soft cloth 7 Lubricate burner motor with a few drops of non detergent oil at both motor oil holes twice each year on units that are not permanently lubricated with sealed bearings Burner adjustments It is recommended that a combustion check be made on the burner each year or whenever replacing a nozzle This will help assure efficient c...

Страница 15: ...content Zero the CO2 analyzer and insert probe into flue pipe and draw sample of the flue gas into analyzer The concentration of CO2 should be 11 5 to 12 5 CO2 levels above 12 5 are not recommended as sooting could occur as conditions and fuel vary at zero smoke G Conclude testing by reading stack temperature and subtract room temperature to get the net stack temperature Using this figure and the ...

Страница 16: ... running and should not drop to less than 80 PSI and hold there after the burner is shut off If the pressure drops to zero the fuel unit should be replaced fire Pot service The ceramic fiber fire pot will seldom if ever require replacement unless it is accidentally damaged during a heat exchanger cleaning operation To replace take off the front access panel and remove all fire pot pieces Carefully...

Страница 17: ...put input output cfm delivery temp max mtg Heat model Btu Hr gPH Btu Hr 70 f fPm rise f Ht ft throw ft Por 100 119 000 85 100 000 1890 460 49 12 39 Por 145 175 000 1 25 145 000 2400 580 56 13 5 50 Por 185 231 000 1 65 185 000 3200 740 54 12 51 Deflector blades pitch 45 toward the floor Heated air Mounting heights measured from floor to bottom of unit The maximum mounting height is that height abov...

Страница 18: ...el pump service diagnosis Problem d Burner operates but fan does not operate 1 Fan motor failure 1 a Check for loose electrical connections Check wiring with diagram on rear of heater b Repair or replace burned out or defective motor c Voltage too high or too low Check voltage with voltmeter 2 Loose fan 2 Tighten fan set screw 3 Defective fan switch in fan limit control 3 Replace entire control 4 ...

Страница 19: ...Make sure return line is below oil level in tank 7 A single pipe system that becomes air bound 7 Loosen gauge port plug or easy flow valve and bleed oil for 15 seconds after foam is gone in bleed hose Check intake line fittings for tightness Check all pump plugs for tightness 8 Slipping or broken coupling 8 Tighten or replace coupling 9 Rotation of motor and fuel unit is not the same 9 Install fue...

Страница 20: ...D HEREIN SHALL BE LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER Heat exchanger condensers for all seller s products except non separated combustion gas fired unit Heaters and infrared Heaters all Burners except infrared Heaters and sheet metal for all seller s products BUYER S REMEDY FOR BREACH OF WARRANTY EXCLUSIVE OF ALL OTHER REMEDIES PROVIDED BY LAW IS LIMITED TO REPAIR OR REPLACEMENT ...

Отзывы: