MOBILTEX® DATA LTD.
TITLE:
Installation and Operating Instructions
Calgary, Alberta
DOCUMENT NO.:
SPI1-MAN-001
SHEET:
32 of 57
REV:
1.14
Figure 29 corTalk® Portable Interrupter Scheduler Menu Page 3
SCHEDULER MENU
[1]S1 [4]S4 [7]S7
[2]S2 [5]S5 [0]MAN
[3]S3 [6]S6
SCH1 PG3
[0]MORE
[1]SERIES [4]OFF OFS
[2]CHAIN [5]FAST
[3]ON OFS [6]RANGE
*Schedule page 3 options only available on SDL1
equipped devices.
STATION SERIES
1234567
0-9999999 RANGE
Station series. Typically, this number would identify
rectifier station on the pipeline. This field can be set to
any number from 0 to 9999999. Entry is optional,
however it is stored in the resultant data file.
POSITION CHAINAGE(m)
5000
Position Chainage. Typically, this would be the number
of meters from a reference mark on the pipeline. This
field can be set to any number from 0 to 999999. Entry
is optional, however it is stored in the resultant data file.
OFF>ON OFFSET(ms)
100
0-60000 RANGE
The number of milliseconds that the datalogger will wait
before taking a reading after the rectifier has transitioned
from an off to an on state. This parameter can be set in
1ms increments in a range from 0 to cycle on-time (ms).
ON>OFF OFFSET(ms)
100
0-60000 RANGE
The number of milliseconds that the datalogger will wait
before taking a reading after the rectifier has transitioned
from an on to an off state. This parameter can be set in
1ms increments in a range from 0 to cycle off-time (ms).
FAST ACQ INTERVAL(m)
30
0-999 RANGE
The SDL1 will perform fast acquisition cycles
(waveform capture) on a periodic basis determined by the
value in the fast acquisition interval. A fast acquisition
cycle lasts 1 minute, during which samples are taken
every 50ms. By default, this field is set to 30 minutes.
Range is from 0 to 999 minutes.
ANALOG RANGE SELECT
0 0=±6 Vpk 3=±150Vpk
1=±20Vpk
2=±60Vpk
The analog meter range parameter sets the maximum
voltage recordable by the datalogger. This parameter can
be set to 0 for +/-6Vpeak, 1 for +/-20Vpeak, 2 for +/-
60Vpeak, and 3 for +/-75Vpeak.