3
Installer Menu
3.1
Menu activation
To access the Generator Installer menu, activate the Maintenance menu, click the central icon of the
Zeus200 generator and enter the password 3105, confirming with OK.
In this menu it is possible to display the operating parameters of the heating and cooling system,
activate the water pump to verify the cooling system during the first start-up and to activate the fuel
pump to purge the supply circuit. The procedure for the water and fuel pump activation are specified
in the "First start-up" chapter.
The first line of the menu also shows the data (HS) of the heat sink temperature. With the Zeus 150
generator running at full speed, an HS temperature above the outlet temperature (OUT) is an
indication of the presence of air bubbles in the cooling liquid system, for which it needs further
verification. The lower the HS temperature the better the system works.
From the Maintenance menu it is possible to activate the Control Unit Installer screen, typing and
confirming the password 3105. From this screen it is possible to check the data related to the voltage
of the sources and the temperature of the control unit. There is a button for the forced activation of
the generator, useful in case you want to turn on the generator, by-passing the detection of battery
charge/discharge, or the not-completed cooling phase.