18
5.6 CALL ON/OFF
By default, the Mobeye ThermoGuard sends alarm notifications via text message and
calls the preset contact persons. By turning off the CALL, the unit will only send an SMS
text message as alarm notification. It is not possible to switch off both the SMS and the
call.
SMS command enable / disable call:
CALL:ON
or
CALL:OFF
example:
1111 CALL:ON
5.7 TEMPERATURE DELAY TIME
The temperature delay time defines the duration a temperature limit is violated before an
alarm is initiated. If the temperature returns to the non-alarm status within the delay time,
no alarm is sent. The time can be set between 0 and 999 minutes.
As default, the temperature delay time is set to 0 minutes.
SMS command temperature delay time:
DELAYTEMP:
example: 1111 DELAYTEMP:15
5.8 ALARM DELAY TIME
The input delay time defines the time that the input is triggered before an alarm is
initiated. If the input returns to the non-alarm status within the delay time, no alarm is
sent. The time can be set between 0 and 999 seconds. As default, the input delay time is
set to 1 second.
SMS command alarm delay input 1:
DELAY1:
SMS command alarm delay input 2:
DELAY2:
example:
1111 DELAY1:999
5.9 INPUT TYPE
The input type defines the character of the inputs IN1 and IN2. This can be Normally
Open (NO) or Normally Closed (NC). If an input is set to NO, the alarm will be triggered
as soon as the terminals of the input are closed. If the input is set to NC, the alarm is