14
BE-801372.01-Digital_clocks_manual-221114
©MOBATIME
Item
Function
Range
(default values are printed in
bold
)
o1
time zone of synchronization
0–64, A (automatically)
o2
type of synchronization source
1–11, A (automatically)
A
auto detection (DCF, serial code
MOBATIME, MOBALine, IRIG‑B or NTP)
1
autonomous operation without
synchronization
values 2–8 only for LGC
2
synchronization DCF
3
MOBATIME serial code
4
MOBALine
5
24 V DC impulses, minute intervals
6
24 V DC impulses, half minute intervals
7
24 V DC impulses, second intervals
8
DCF‑FSK, IRIG‑B Standard, IRIG‑B 123,
IRIG‑B DIEM, AFNOR A, AFNOR C
9
active DCF code
10
only for GPS
GPS
11
only with RS 485 option
RS 485
o3
only for LGC
impulse line processing mode
1–4
1
polarized impulses, synchronization
and time adjustment
2
polarized impulses, time
synchronization only
3
non-polarized impulses, synchronization
and time adjustment
4
non-polarized impulses, time
synchronization only
o4
only for LGC
time zone for MOBALine
1–20, 0 (off)
o5
only for NTP, PoE, WiFi and WiFi5
time zone server MOBATIME
1–15, 0 (off)
2.3.3
Submenu for time synchronization – SYNC
Содержание DSC. 250.4
Страница 1: ...BE 801372 01 Digital_clocks_manual 221114 MOBATIME Instruction manual Digital clocks ...
Страница 31: ...MENU 31 BE 801372 01 Digital_clocks_manual 221114 MOBATIME ...
Страница 141: ......
Страница 142: ......
Страница 143: ......