Electromagnetic Flow Meter

Using the factory setup 

MagFlux

®

 returns to default mA settings corre-

sponding to the chosen 

MagFlux

®

 flow sensors Q

min

 and Q

max

.

The mA output is an active output, and the maximum load is 800 Ohm.
The upper limit for the mA output is 20,5 mA 
  3,75 mA indicates the mA output is not in use 
  3,5 mA indicates flow under 4 mA level 
  20,5 mA indicates flow higher than 20 mA level.

 

The 20 mA maximum output is rounded up to the nearest round figure. 

Example: The maximum flow of 17.676 m

3

/h for a DN25 is rounded 

up to 20.000 m

3

/h.

Flow Forward

The mA signal provides 4 mA at zero flow and 20 mA at Q

max

 in the for-

ward direction. 

Averaging

Units

mA Output

Only f

or ter

minal use

Must not be surrended

A

B

C

D

E

Date

Modification

Scale:

MJK AUTOMATION A/S
Byageren 7
DK-2800 Nñrum
Fax: +45 45 56 06 46
Tel.: +45 45 56 06 56

Date:

Constructor:

Part no.:

Software  version

Skala for tegning

KJ/LSP

Menu system for MagFlux Converter
Converter setup, 

Minimum Flow, Averaging

Units, mA  Output

Minimum Flow

Averaging

        0010 sec

   Back

Select

>

Flow Forward
Flow Reverse
Forward & rev. (12mA=0)
Forward & rev. (4 mA=0)
Not in use
   Back

Select

OK

mA  Output

20 mA =            1.000 m

3

/h

   Back

Select

>

Minimum Flow
                           0.177 m

3

/h

   Back

Select

>

Flow

m

3

/sec

l/sec
l/min
l/h
m

3

/h

ft

3

/h

MGD
GPM
   Back

Select

OK

Flow Forward

mA  Output

20 mA =            1.000 m

3

/h

   Back

Select

>

(4mA = 0 Flow)

Flow Reverse

mA  Output

4 mA   =

  1.000 m

3

/h

20 mA =      -1.000 m

3

/h

   Back

Select

>

(12mA = 0 Flow, +4mA = - 20mA)

Forward & rev. (12mA=0)

mA  Output

4 mA   =

      0,00 m

3

/h

20 mA =

    1.000 m

3

/h

   Back

Select

>

(4mA = 0 Flow)

Forward & rev.

(4 mA=0)

2006 - 09 - 29

841010

Converter Setup

Minimum Flow
Averaging
Units
mA Output
R Totalizer Forward
R Totalizer Reverse
R Totalizer Sum
NR Totalizer Forward
NR Totalizer Reverse
NR Totalizer Sum
Batch Counter 1
Batch Counter 2
High Flow
Low Flow
Flow Direction
Empty Pipe
Status
Service Menu

   Back

Select

OK

Converter Setup

tbd

Not in use

0

4

8

12

16

20

-100% -80

-60

-40

-20

0

20

40

60

80

100%

Flow

mA

0

4

8

12

16

20

-100% -800

-600

-400

-200

0

200

400

600

800

100%

Flow

mA

0

4

8

12

16

20

-100% -800

-600

-400

-200

0

200

400

600

800

100%

Flow

mA

0

4

8

12

16

20

-100% -800

-600

-400

-200

0

200

400

600

800

100%

Flow

mA

Содержание MagFlux

Страница 1: ...1 GB MagFlux Manual 0812 Electromagnetic Flow Meter FW 841012 842009 Electromagnetic Flow Meter Installation and User Manual...

Страница 2: ...ativen Dokument en bereinstimmt EN61000 6 3 4 2001 EN61000 6 1 2 1999 Gem ss den Bestimmungen der Richtlinie 89 336 EEC 92 31 EEC Declaration de conformite Nous MJK Automation A S DK 2850 N rum d clar...

Страница 3: ...alization and Grounding 23 Type 7100 7200 7600 in Conductive Pipes 23 Type 7100 7200 7600 in Non conductive Pipes 23 Type 7300 7400 in Conductive Pipes 24 Type 7300 7400 in Non conductive Pipes 24 4 F...

Страница 4: ...Sensor Name 59 Converter Setup 61 Minimum Flow 62 Averaging 62 Units 63 mA Output 63 Flow Forward 64 Flow Reverse 65 Forward Rev 12mA 0 65 Forward rev 4mA 0 66 Not in use 66 Totalizers 67 Settings an...

Страница 5: ...5 Appendix A Pop up and Error Messages 107 Appendix B MJK Field Link Software 111 Important Notes 111 A Connect a PC to the Flow Meter 111 B Save Log Data 113 C Upgrade Display Firmware 113 D Upgrade...

Страница 6: ...6 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...

Страница 7: ...first to learn about the MagFlux electromagnetic flow meter and all its features You can always contact your local representative or the MJK hot lines for advice and guidance Europe Tel 45 45 56 06 5...

Страница 8: ...ction example pipe systems sizing chart etc 4 Flow Converter Describes the physical specifications and installation rules for the flow converter such as power supply in and outputs sensor converter di...

Страница 9: ...Appendix G Digital Input Output Connections Illustrates how the digital in and outputs can be interconnected Gatefold 1 Main Menu Overview Is a continuous presentation of the main menu structure The s...

Страница 10: ...between two electrodes arranged perpendicular to the direction of flow and the magnetic field The voltage is proportional to the velocity V of the fluid E B x D x V x k Volt where E is the voltage th...

Страница 11: ...emical polarization between the electrodes and the fluid The MagFlux electromagnetic flow meters are excited by a 2 5 Hz square wave and thereby eliminate the drawbacks of both DC and AC systems A mic...

Страница 12: ...12 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...

Страница 13: ...ry and other equipment are effectively put out of service that is to remove the main fuses and lock main and security switches in off position before commencing configu ration fault finding servicing...

Страница 14: ...name plate see example below This calibration code Cal code is unique and provides the MagFlux converter with information about flow sensor number nominal diameter of the flow sensor and calibration d...

Страница 15: ...hemicals Mounting location To obtain a stable and accurate flow measurement it is very important that the flow sensor is mounted correctly in the pipe system There must be no flow fluctuations Avoid l...

Страница 16: ...ow direction is A Pressure loss The pressure loss can easily be determined if the nominal pipe diameter is greater than the MagFlux flow sensor See the diagram below 0 003 Pressure loss graph The diag...

Страница 17: ...nsioning chart on the following page Min and max flow DN Qmin Qmax DN Qmin Qmax DN Qmin Qmax 0 2 m s 10 m s 0 2 m s 10 m s 0 2 m s 10 m s l h l h l h l h m3 h m3 h 3 5 09 254 20 226 11304 65 2 39 119...

Страница 18: ...18 DN 400 16 DN 350 14 DN 300 12 DN 250 10 DN 200 8 DN 150 6 DN 125 5 DN 100 4 DN 80 3 DN 65 2 1 2 DN 50 2 DN 40 1 1 2 DN 32 1 1 4 DN 25 1 DN 20 3 4 DN 15 1 2 DN 10 3 8 DN 8 5 16 DN 6 1 4 DN 3 1 8 0...

Страница 19: ...to ensure a laminar flow without turbulence upstream of the flow sensor For that reason the flow sensor must be mounted in a straight pipe at a distance from interfering elements of minimum 3 x DN up...

Страница 20: ...e the reducer must then have a length of minimum 152 6 mm in order to keep the inner angle below 7 5 3 Flange connections must be assembled concentrically on both the up stream and the downstream side...

Страница 21: ...the flow sensor is always filled with liquid In case the liquid is carrying particles for example when measuring sludge sewage etc the flow sensor must be mounted vertically 6 When mounting horizontal...

Страница 22: ...e flow sensor can be rotated max 45 seen from the connection end If the flow sensor is rotated more than 45 one of the electrodes may not be in full contact with the liquid Cabinet Mounted on the Flow...

Страница 23: ...The flow sensor must be connected to an effective ground connection and the wire dimension must be at least 1 5 mm2 Type 7100 7200 7600 in Non conductive Pipes Ground connection NB The flow sensor mus...

Страница 24: ...st be connected to an effective ground connection and the wire dimension must be at least 1 5 mm2 Type 7300 7400 in Non conductive Pipes Ground connection NB The flow sensor must be connected to an ef...

Страница 25: ...ins supply mA RE2 RE1 DI1 Display A B DI COM C NO NO PE N L FUSE www mjk com Fuse rating 100 mAT 115 V AC 63 mAT 230 V AC 521254 Connection for top mounted operator panel Live Neutral Protective earth...

Страница 26: ...E Protective ground DC neutral DC live The internal fuse ratings are Internal Fuse Ratings Voltage Rating Order no Dimension 230 V AC 0 063 mA T 550030 5 x 20 mm 115 V AC 0 125 mA T 550035 5 x 20 mm 2...

Страница 27: ...o page 25 2 Note down the color and position of the wires in the terminal blocks and then loosen the terminal screws 3 Unscrew the two screws that hold the metal cover and then remove it 4 Unscrew the...

Страница 28: ...inserted 115 V AC configuration 8 Insert and solder 2 jumpers wires in the positions indicated by the ar rows 9 Turn around the PCB and replace the 63 mAT fuse on the right side with a 125 mAT fuse o...

Страница 29: ...tputs MagFlux has two digital outputs DO 1 with an opto light triggered relay and DO 2 with an electro mechanical relay They can both be programmed for the following functions high and low flow alarms...

Страница 30: ...h 2 counters reset counters R Totalizer Forward and Reverse reset counter R Totalizer Sum DI shares the common terminal Com with DO 1 See also application examples in Appendix G Digital Input Output C...

Страница 31: ...onverter and sensor must under normal circumstances not exceed 100 meters Power lines running in par allel and noisy environments may reduce the max length to 50 meters Consult MJK personnel for advic...

Страница 32: ...igital input 10 30 V DC 4 20 mA output Power supply Electronic relay max 50 V DC 120 mA Electromechanical relay max 50 V AC 1 A 4 20 mA max 800 Fuse rating 100 mAT 115 V AC Connection for Flow Sensor...

Страница 33: ...guration The MagFlux Converter and Display Unit is mounted directly on the MagFlux Flow Sensor Order numbers for this configuration 207xxx MagFlux Flow Sensor 207920 MagFlux Converter with Display Uni...

Страница 34: ...umbers for this configuration 207xxx MagFlux Flow Sensor 207925 MagFlux Converter with Display Unit for wall mounting 691080 MagFlux Sensor cable 579035 MagFlux Gel Potting Kit IP68 207925 consists of...

Страница 35: ...ir no 3 is not used B Connection for remote converter Terminal Signal Wire Colour 1 GND Shield 2 E1 Pair no 1 Red 3 E2 Pair no 1 White 4 GND Pair no 3 Black Pair no 3 White 5 L1 Pair no 2 Green 6 L2 P...

Страница 36: ...shielded twisted 2 and 4 wire cables using the Modbus communica tion protocol on RS 485 Order numbers for this configuration 207xxx MagFlux Flow Sensor 2 pcs 207925 MagFlux Converter with Display Uni...

Страница 37: ...to slot Local flow sensor 2 2 wire twisted shield cable Connect lead 1 to slot A lead 2 to slot B and twisted shield to slot 4 wire twisted shield cable Connect lead 1 to slot A lead 2 to slot B lead...

Страница 38: ...38 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...

Страница 39: ...low converter and wait one minute 3 Verify or enter the calibration code of the flow sensor in the Converter Setup Service Menu Sensor Calibration Code menu see also page 86 If the entered calibration...

Страница 40: ...d description of the displays shown during setup configuration and normal operation A 5 line LCD screen displays symbols and the actual status during setup configuration servicing and normal operation...

Страница 41: ...d and set up as required MagFlux Flow 4 1m3 h FTot 18 77 m3 Select Setup Oxix1 Oxygen sat 91 9 Select Setup or MagFlux Flow 4 1m3 h FTot 18 77 m3 Select Setup Oxix1 Oxygen sat 91 9 Select Setup Import...

Страница 42: ...and refresh all system displays and key combinations by pressing all four keys simultaneously This feature is especially useful during for example a service call where the display language Dutch Dani...

Страница 43: ...l setup the Sensor Calibration Code menu must be addressed A password is not required to enter or change the sensor calibration code Toggle through the displayed digits with the right arrow key when p...

Страница 44: ...FTot Service Menu Sensor Calibration Code Converter SW Ver Product Data Reset Counter Time Internal Meas Cal Minimum Velocity Calibrate Flow now Calibrate Volume Calibrate mA Test Velocity Freeze Coil...

Страница 45: ...n 840020 681 Back Prod Ba Prod Ba Track Ba HW Ba DN 00025 Back Select OK Set Flow Direction Follow Arrow A Follow Arrow B A B Back Select OK OK The MagFlux is now configured with default settings and...

Страница 46: ...up Service Menu Sensor Calibration Code Converter SW Ver Product Data Reset Counter Time Internal Meas Cal Minimum Velocity Calibrate Flow now Calibrate Volume Calibrate mA Test Velocity Freeze Coil R...

Страница 47: ...enu Overview page Gf 3 Display Setup Menu Overview page Gf 4 Main Menu 1 Press the Setup key on the MagFlux display see below to enter the MagFlux Main Menu MagFlux Flow 4 1 m3 h FTot 18 77 m3 Select...

Страница 48: ...y Select Line Line 1 Sensor Name Line 2 Flow Line 3 FTot Line 4 Line 5 Back Select OK Specify Main Screen Select Line Content Not in use Flow RFTot RRTot RTTot FTot RTot Cnt Flow Direction Batch 1 Bat...

Страница 49: ...age 59 Flow Actual flow rate in units chosen in the menu for primary units RFTot Resettable Forward Totalizer counter RRTot Resettable Reverse Totalizer counter RTTot Resettable Total Totalizer counte...

Страница 50: ...s Batch 2 Cnt Batch 2 Counts number of batches Batch 1 Vol Batch 1 Volume Batch 2 Vol Batch 2 Volume Clock Time and date The size of the display lines will automatically increase or decrease as the nu...

Страница 51: ...up down keys to highlight the required menu line here Fac tory Settings and then press OK to select it Specify Main Screen Factory Settings Data Logger Password Set Sensor Name Converter Setup Displa...

Страница 52: ...lux Default DI DO Settings MagFlux Default 20 mA Settings MagFlux Default DI DO Settings Digital Output 1 opto DO1 Digital Output 2 mech DO2 Digital Input DI Counter R Totalizer Forward Counter R Tota...

Страница 53: ...3 4 50 25 20 1 75 32 30 1 100 40 50 1 200 50 75 2 300 65 100 2 500 80 200 3 800 100 300 4 1000 125 400 5 2000 150 600 6 3000 200 1000 8 5000 250 2000 10 7700 300 2500 12 10000 350 3000 14 10000 400 45...

Страница 54: ...3 sec l sec l min l h m3 h Totalizers RFTot RRTot RSTot FTot RTot Cnt l l l l l l hl hl hl hl hl hl kl kl kl kl kl kl m3 m3 m3 m3 m3 m3 Set to US All converter related units can be set to the followin...

Страница 55: ...dis carded 1 Press the up down keys to highlight the required menu line here Data Logger and then press OK to select it Specify Main Screen Factory Settings Data Logger Password Set Sensor Name Conver...

Страница 56: ...try points The log data can be shown on the Display Unit or be stored in an external CSV file MJK Field Link software is needed for transfer of data into CSV file format via the USB port in the displa...

Страница 57: ...006 08 21 16 09 42 3 039M3 H Innlet flow flow 32 5 m3 h cnt 1 312535 m3 Select Graph The Display Unit then shows the Graph screen To return to the Main Menu display screen select esc by pressing the u...

Страница 58: ...the up down keys to highlight the required menu line here Pass word and then press OK to select it Specify Main Screen Factory Settings Data Logger Password Set Sensor Name Converter Setup Display Set...

Страница 59: ...ction can be overruled with the code 01750 Change Password The present 5 digit password can be changed as required Set Sensor Name A unique name and or number a function or a location can be assigned...

Страница 60: ...d then press to proceed to the next character 4 Continue with until all numeric and alphabetical characters have been set to for example Inlet flow see below 5 Press OK Inlet flow Flow 32 5 m3 h Cnt 1...

Страница 61: ...n Factory Settings Data Logger Password Set Sensor Name Converter Setup Display Setup Back Select OK Main Menu Converter Setup 2 Press the up down keys to highlight the required option and then press...

Страница 62: ...r Reverse NR Totalizer Sum Batch Counter 1 Batch Counter 2 High Flow Low Flow Flow Direction Empty Pipe Status Service Menu Back Select OK Converter Setup 1 Select the digits one by one with the left...

Страница 63: ...put When a MagFlux is connected to a power supply for the first time the mA output is automatically set to provide 4 mA at zero flow and 20 mA at a flow corresponding to the theoretical Qmax of the fl...

Страница 64: ...20 mA level The 20 mA maximum output is rounded up to the nearest round figure Example The maximum flow of 17 676 m3 h for a DN25 is rounded up to 20 000 m3 h Flow Forward The mA signal provides 4 mA...

Страница 65: ...put 20 mA 1 000 m 3 h Back Select 4mA 0 Flow Flow Reverse mA 4 m 20 m B 1 F 2006 09 29 0 4 8 12 16 100 80 60 40 20 0 20 40 60 80 100 Flow mA 0 4 8 12 16 20 100 800 600 400 200 0 200 400 600 800 100 Fl...

Страница 66: ...ut 4 mA 1 000 m3 h 20 mA 1 000 m3 h Back Select 12mA 0 Flow 4mA 20mA Forward rev 12mA 0 mA Output 4 mA 0 00 m3 h 20 mA 1 000 m3 h Back Select 4mA 0 Flow Forward rev 4 mA 0 tbd Not in use 0 4 8 12 16 2...

Страница 67: ...figure overleaf Electro Mechanical relay Opto Relay light triggered electronic relay Display only on the Display Unit The available output option for the non resettable totalizers is Display only on t...

Страница 68: ...3 15 0 001 1 0 1 1 m3 20 0 001 1 0 1 1 m3 25 0 01 10 1 10 m3 32 0 01 10 1 10 m3 40 0 01 10 1 10 m3 50 0 01 10 1 10 m3 65 0 01 100 1 100 m3 80 0 1 100 10 100 m3 100 0 1 100 10 100 m3 125 0 1 100 10 100...

Страница 69: ...mSec 1800000 Example Min flow unit pulses for DN 100 max flow 300 m3 h Minimum flow unit pr pulses 300 m3 x 100 mSec 1800000 0 016 m3 which is rounded to 0 1 m3 by the MagFlux The formula for the maxi...

Страница 70: ...echanical Relay Opto Relay Display only Electro Electro m Opto Rela Display on Back Volume between Pulses 01 00000 m3 Back Select Totalizer Forward Unit l hl kl m3 ft3 gal MG Back Select OK Totalizer...

Страница 71: ...selected at startup The Totalizer counts in selected units and is resettable The counter can be connected to the relays or to the display only To reset the counter the totalizer must be present in the...

Страница 72: ...Reve Counter 2 NR Forward Totalizer NR FTot The Totalizer counts the forward flow volume according to the primary flow direction selected at start up The Totalizer counts in selected units and cannot...

Страница 73: ...K Pause with Digital Input Yes No Back Select OK Adaptive Maximum Correction 20 Back Select Automatic Batch Counter 1 Unit l hl kl m3 ft3 gal MG Back Select OK Pause with Digital Input Yes No Back Sel...

Страница 74: ...tion 20 Back Select Reset Batch Error Yes No Back Select OK Automatic Back Select OK Reseting the Batch Counter 1 Automatic Manually Adaptive Back Select OK On time 00100 mSec Back Select Number of pr...

Страница 75: ...of preSelected U 0 Back Se 2006 09 19 841010 No Back Select OK Ada Maximum Cor Back Se Reset Batch E Yes No Back Se Automatic No Back Select OK Reseting the Batch Counter 1 Automatic Manually Adaptiv...

Страница 76: ...e Maximum Correction 20 Back Select Reset Batch Error Yes No Back Select OK Automatic No Back Select OK Reseting the Batch Counter 1 Automatic Manually Adaptive Back Select OK On time 00100 mSec Back...

Страница 77: ...matic Manually Adaptive Back Select OK Automatic Reseting the Batch Counter Automatic Manually Adaptive Back Se On time 00100 mSec Back Select Number of preselected Units 00 02778m3 Back Select Number...

Страница 78: ...stopped or paused via the digital input DI On time The pulse length of the opto digital output DO 1 is adjustable from 1 ms to 10 secs The pulse length of the mechanical digital relay DO 2 is adjusta...

Страница 79: ...33333 0 277778 100 m3 80 0 011111 0 555556 200 1 666667 0 555556 200 m3 100 0 016667 0 833333 300 2 500000 0 833333 300 m3 125 0 022222 1 111111 400 3 333333 1 111111 400 m3 150 0 033333 1 666667 600...

Страница 80: ...pulses is flow at 20mA Example DN 100 max flow 300 m3 h Maximum flow unit pr pulses 300 m3 Limitation of the automatic batch counter on DO 2 mech relay The maximum limit is 120 pulses pr hour The for...

Страница 81: ...Relay Display only Not in use Back Select OK Delay 00010 Sec Back Select OK Electro mecha Opto Relay Display only Not in use Back Se Electro mechanical Relay Opto Relay Display only ON at Flow 10 000...

Страница 82: ...s an alarm and or sends a signal when for example a high flow limit is exceeded OFF at Flow Cancels an alarm and or sends a signal when recovering from for example an overflow situation Delay A delay...

Страница 83: ...ect Delay 00010 Sec Back Select Delay 00010 Sec Back Select Electro mech Relay Function NO NC Back Se Delay Back Se Path Main Menu Converter setup Flow Direction Empty Pipe Service Menu Relay Function...

Страница 84: ...0 Sec Back Select y Pipe Service Menu Status ect Relay Function NO NC Back Select Relay Function NO NC Back Select DO1 DO2 DI mA output Back The available output options for Empty Pipe are Electro Mec...

Страница 85: ...ates a de activated state Display only 0 Sec Delay 00010 Sec Back Select Type Password 0000 Back Select Service Menu Sensor Calibration Code Converter SW Ver Product Data Reset Counter Time Internal M...

Страница 86: ...brate Flow now Calibrate Volume Calibrate mA Test Velocity Freeze Coil Read Event Log Back on Stock Back Select OK OK Status DO1 Not in use DO2 R Totalizer Forward DI R Totalizer Forward mA output 6 2...

Страница 87: ...not required to add or change the sensor calibration code Back Select Sensor Calibration Code Converter SW Ver Product Data Reset Counter Time Internal Meas Cal Minimum Velocity Calibrate Flow now Ca...

Страница 88: ...510250 Back Select OK OK OK Rese Reset Co Systen Ru Since res Runtime Back DN 00025 Back Select OK Set Flow Direction Follow Arrow A Follow Arrow B A B Back Select OK OK Product Data Key product data...

Страница 89: ...gate Coil Current View ADC Factor Calibrate Vground Calibrate Vref View Vwater View Raw ADC View ADC Current Back Select Minimum Velocity Minimum Velocity 0 100 m sec Back Select View Vgate Coil Curre...

Страница 90: ...elect View Calibrate Vref 1208 Back Select View Vwater View Calibrate Vref Calibrate Flow now View flow now 0 0019816387 m3 sec Back Select Calibration volume The volume counter can be reset and a new...

Страница 91: ...xed current Calib current DAC zero current DAC top current Back Select OK Test Velocity Set velocity 00 000 m sec Back Select Velocity 4 039745 m sec Flow 7 136209 m3 h Back Select OK OK Enable test Y...

Страница 92: ...ct OK Test Velocity Set velocity 00 000 m sec Back Select Velocity 4 039745 m sec Flow 7 136209 m3 h Back Select OK OK Enable test Yes No Back Select OK OK Freeze Coil Freeze coil Positive Negative Ba...

Страница 93: ...56 205 0 Back Next OK No Hour Event Extension 18 306 205 0 19 306 208 0 20 163 206 0 Back OK 000 uA OK 500 uA 955 uA 776 9997 uA 3814 Read se DN Back O Serial no Back O Sensor Cal Back O Sensor zero 0...

Страница 94: ...Back OK Serial no 00006 OK Back OK Sensor Cal 19600 OK Back OK Sensor zero 0 000000 m h OK Back 3 Back on Stock The factory settings can be re etablished with the Back On Stock option MJK AUTOMATION A...

Страница 95: ...uired menu line here Dis play Setup and then press OK to select it Specify Main Screen Factory Settings Data Logger Password Set Sensor Name Converter Setup Display Setup Back Select OK Main Menu Disp...

Страница 96: ...e menu several national languages can be selected Language GB English US English Dansk Deutsch Espa ol Fran ais Italiano Nederlands Norsk Soumalainen Svenska Back Select OK Language Additional languag...

Страница 97: ...and the time format Time Format 24 hour AM PM Back Select OK Set Clock Set Clock 2006 09 19 12 43 11 Back Select 1 Select the date and time digits with the left right keys and change the setting with...

Страница 98: ...Select OK Remove Device Device 1 Back Select OK Remove Device When several converters are to be added it is necessary to change each converter device address to a unique ID address before connecting t...

Страница 99: ...Device If a device is to be removed from the Display Unit proceed as follows 1 Select the required device with the up down keys 2 Click OK to remove it The device is now removed from the Display unit...

Страница 100: ...ersion The Display SW Version menu provides a read out of the display soft ware actually firmware version the build date and last edited date of the the multiple languages file Display 841xxx xxx Buil...

Страница 101: ...6 PN 40 mm 15 40 95 65 14 4 14 M12 01 20 40 105 75 16 4 14 M12 01 25 40 115 85 16 4 14 M12 01 32 40 140 100 18 4 18 M16 01 40 40 150 110 18 4 18 M16 01 50 16 165 125 19 4 18 M16 01 65 16 185 145 20 8...

Страница 102: ...0 62 4 0 62 1 150 5 0 3 88 0 69 4 0 62 2 150 6 0 4 75 0 75 4 0 75 2 150 7 0 5 50 0 88 4 0 75 3 150 7 5 6 00 0 94 4 0 75 4 150 9 0 7 50 0 94 8 0 75 5 150 10 0 8 50 0 94 8 0 88 6 150 11 0 9 50 1 00 8 0...

Страница 103: ...20 100 73 6 4 14 25 115 83 8 4 14 32 120 87 8 4 14 40 135 98 10 4 14 50 150 114 10 4 18 65 165 127 11 4 18 80 185 146 11 4 18 100 215 178 13 4 18 150 280 235 19 8 18 200 335 292 19 8 18 250 405 356 23...

Страница 104: ...100 73 10 4 14 25 120 87 10 4 18 32 135 98 13 4 18 40 140 105 13 4 18 50 165 127 15 4 18 65 185 146 15 8 18 80 205 165 15 8 18 100 230 191 19 8 18 150 305 260 24 12 22 200 370 324 24 12 22 250 430 38...

Страница 105: ...5 83 13 4 18 25 120 87 14 4 18 32 135 98 17 4 18 40 140 105 17 4 18 50 165 127 19 4 18 65 185 146 19 8 18 80 205 165 24 8 18 100 230 191 24 8 18 150 305 260 31 12 22 200 370 324 31 12 22 250 430 381 3...

Страница 106: ...106 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...

Страница 107: ...Input over range Alarm Sensor flow can not be measured correct Input is over max level Will normally only occur starting from zero flow to high flow Will be present for max 12 min utes Factory reset h...

Страница 108: ...low Alarm Flow totalize overflow non resettable counter maybe incorrect in Eeprom mA Error Alarm Current out not connected If the current out is used deacti vate Current out to stop this pop up mA flo...

Страница 109: ...ormat Data has an illegal format Illegal data value Data has a non valid value Missing user login User password required to access Missing MJK login MJK password required to access Relay used for puls...

Страница 110: ...system error The relay is already in use by an other function USB Flash programming please wait Programming is in progress but not finished Flash programming done Programming is finished Flash crc err...

Страница 111: ...MagFlux log data must be saved in a file before transferring and installing new firmware See 2 Save Log Data overleaf 2 Note down all display and converter settings before upgrading new firmware 3 The...

Страница 112: ...the rear of the front panel 4 Connect the other end of the USB cable max 4 7 metres long to the PC 5 Select File in the menu bar and click Connect If the connection is successful a Device Clock window...

Страница 113: ...portant Always upgrade the display firmware before you upgrade the converter software 1 Select Firmware in the menu bar and click Display 2 Locate the MJK Field FW directory on the CD ROM select the 8...

Страница 114: ...displays the MJK logo the new link status is displayed and the Display Unit informs that the PC is once again connected Click OK on the PC and the MagFlux Display Unit to return to the MagFlux Flow F...

Страница 115: ...and prompts for se lecting the converter to program The converter firmware is then transferred and the converter Flash programming is initiated Expect this process to take a few minutes 4 When the Fl...

Страница 116: ...one following a firmware upgrade You can now either add or delete the required languages 3 Click Add select the required language text file or language pack in the MJK Field Display Unit text files di...

Страница 117: ...to select a too large size Question Where do I install the flow meter in relation to valves bends pumps etc Answer Minimum 3 times the flow meter s internal diameter DN up stream and minimum 2 times t...

Страница 118: ...unding rings superfluous Coated metal tubes always require grounding rings If the conductivity is less than 100 S cm grounding rings are recom mended When in doubt always contact your local MJK repres...

Страница 119: ...d 20 mA Question I do not understand the language on the display What s wrong and how do I fix it Answer For example lightning and a too noisy environment can have caused the problem The solution is t...

Страница 120: ...0 GB MagFlux Manual 0812 Electromagnetic Flow Meter Appendix D Front Panel Cut out Drawing The dotted line indicates the front panel outline and measures 155 x 145 mm Cut out area Frontpanel outline U...

Страница 121: ...07 DN50 PN16 Test conditions The meter tests were carried by a volume method with flying start Test facility Helios AG SRN electro mechanical weighing machines of capacities 4800 kgs production series...

Страница 122: ...shown below is the result of a CSV file from the con verter see Save Log Data procedure on page 113 having been opened in with Microsoft Excel spread sheet utility This example below illustrates four...

Страница 123: ...e 130 ft3 h cubic feet per hour 138 l h litres per hour 139 ppm parts per million 246 NTU Nephelometric Turbidity Units 248 FNU Formazin Nephelometric Units 249 EBC European Brewing Convention 250 FTU...

Страница 124: ...ectromagnetic Flow Meter To plot the log file s data proceed as follows 1 Start Excel and open the csv log file 2 Sort by Index click the Diagram Guide tool in the toolbar and select the required curv...

Страница 125: ...DO can be interconnected to exter nal equipment to achieve a number of functions such as alarms counter reset flow direction indication etc The two schematics below illustrate a simplified mode of op...

Страница 126: ...ollowing pages GB MagFlux Manual 0808 Electromagnetic Flow Meter Login Activate Deactivate Change Password Back Select OK Password Specify Main Screen Factory Settings Data Logger Password Set Sensor...

Страница 127: ...hange Password Back Select OK Password Log Interval 0010 sec ack Select Data Logger Set Sensor Name MagFlux1 Back Select Set Sensor Name Language Set Clock Modbus Factory Settings Display SW Version B...

Страница 128: ...w Forward Flow Reverse Forward rev 12mA 0 Forward rev 4 mA 0 Not in use Back Select OK mA Output 20 mA 20 000 m 3 t Back Select Minimum Flow 0 177 m 3 h Back Select Flow m3 sec l sec l min l h m3 h ft...

Страница 129: ...t 20 mA 20 000 m 3 t Back Select Flow ec ck Select OK Flow Forward mA Output 20 mA 20 000 m 3 t Back Select 4mA 0 Flow Flow Reverse mA Output 4 mA 20 000 m 3 t 20 mA 20 000 Back Select 12mA 0 Flow 4mA...

Страница 130: ...nical Relay Opto Relay Display only Back Select OK Volume between Pulses 01 00000 m 3 Back Select Totalizer Forward Unit l hl kl m3 ft3 gal MG Back Select OK Totalizer Forward Unit l hl kl m3 ft3 gal...

Страница 131: ...zer Forward Unit l hl kl m3 ft3 gal MG Back Select OK Totalizer Forward Unit l hl kl m3 ft3 gal MG Back Select OK Reset with Digital Input Yes No Back Select OK On time 00100 mSec Back Select Volume b...

Страница 132: ...ft3 gal MG Back Select OK Totalizer Reverse Unit l hl kl m3 ft3 gal MG Back Select OK NR Totalizer Sum Totalizer total Unit l hl kl m3 ft3 gal MG Back Select OK Batch Counter 1 Unit l hl kl m3 ft3 gal...

Страница 133: ...ic Manually Adaptive Back Select OK Electro mechanical Relay Opto Relay Not in use Back Select OK Electro mechanical Relay Opto Relay Number of preselected Units 00 002778 m 3 Back Select Not in use B...

Страница 134: ...Flow Electro mechanical Relay Opto Relay Display only Not in use Back Select OK Delay 00010 Sec Back Select OK Electro mechanical Relay Opto Relay Display only Not in use Back Select OK Electro mecha...

Страница 135: ...Display only ON at Flow 176 4 m3 h Back Select Off at Flow 170 0 m3 h Back Select ON at Flow 176 4 m3 h Back Select Off at Flow 170 0 m3 h Back Select Delay 00010 Sec Back Select Delay 00010 Sec Back...

Страница 136: ...o Relay Display only Not in use Back Select OK 00010 Sec k Select Delay 00010 Sec Back Select Delay 00010 Sec Back Select Electro mechanical Relay Opto Relay Display only Relay Function NO NC Back Sel...

Страница 137: ...r Product Data Reset Counter Time Internal Meas Cal Minimum Velocity Calibrate Flow now Calibrate Volume Calibrate mA Test Velocity Freeze Coil Read Event Log Back on Stock Back Select OK OK n Select...

Страница 138: ...set Counter Time Internal Meas Cal Minimum Velocity Calibrate Flow now Calibrate Volume Calibrate mA Test Velocity Freeze Coil Read Event Log Back on Stock Back Select OK OK Converter SW Ver Product D...

Страница 139: ...iew Vgate 3624 Back Select Coil Current 148 Back Select View ADC Factor 4 89011 Back Select Calibrate ADC ground 2270 Back Select View ADC Factor Calibrate ADC Ground View ADC Current View Raw ADC Vie...

Страница 140: ...et counter Yes No Back Select OK Reset counter Yes No Back Select OK OK View counter 1163 1950000000 m3 Back Select OK OK Set volume 1163 1950000000 m3 Back Select OK OK Calibrate mA Current Set fixed...

Страница 141: ...reeze Coil Freeze coil Positive Negative Back Select OK Freeze coil Disable Enable Back Select OK OK Read Event Log No Hour Event Extension 1 1956 0 0 2 1956 3 0 3 1956 205 0 Back Next OK No Hour Even...

Страница 142: ...nge Device Addre Device 1 Back Select O Add Device Change Device Address Remove Device Back Select O Scanning Back Set Clock Language Modbus Add Device Devices Found Device 1 Back OK Change Device Add...

Страница 143: ...xxx Build Sep 15 2006 11 18 24 Language 2006 09 21 Back Modbus Display SW Version dd Device vices Found OK Change Device Addresse Change Device 1 1 Back Select OK Remove Device Device 1 Back Select O...

Страница 144: ...144 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...

Страница 145: ...ng 23 H High Flow Low Flow 81 hotline 7 I ID 14 initial checks 39 initial setup 43 input digital 30 125 Internal Meas Cal 89 Index A accuracy 17 activate deactivate 59 Add Device 98 analogue output 29...

Страница 146: ...NR Totalizer Reverse 72 NR Totalizer Sum 72 O OFF at Flow 82 On time 67 78 On at Flow 82 options Activate Deactivate 59 Add Device 98 Averaging 62 Back on Stock 94 Batch 1 49 Batch 1Cnt 50 Batch 1 DN...

Страница 147: ...49 RRTot 49 RTot 49 RTTot 49 Sensor Name 49 Set Clock 97 Status 85 Test Velocity 92 Totalizer Forward Unit 67 78 Units 63 Volume between Pulses 68 78 outputs 29 125 P password 58 password change 59 pi...

Страница 148: ...Flow Meter Electromagnetic Flow Meter T Test Velocity 92 theory 10 Totalizer Forward Unit 67 78 totalizers 67 totalizers non resettable 72 totalizers resettable 70 trademark 7 U Units 63 upgrade 9 11...

Страница 149: ...Index 5 GB MagFlux Manual 0812 Electromagnetic Flow Meter Electromagnetic Flow Meter This page intentionally left blank...

Страница 150: ...ucts To the extent where nothing else follows in lines of invariable rules of law we are not liable for loss of profits and working deficits or other indirect losses Changes As our products are develo...

Отзывы: