Electromagnetic Flow Meter
FW: 841012/842009
Appendix A. Pop-up and Error Messages
Alarms
Sensor Error
Alarm
- The converter has expe-
rienced HW problems measuring
flow (see log for details/time)
Sensor cal. Code error
Alarm
- The calibration code con-
flicts with the sensor HW.
Output Coil Error
Alarm
- The converter has experi-
enced problems with connection to
the sensor coil (see log for details/
time)
Empty pipe
Alarm
- The converter has detect-
ed no water in the sensor
Input over range
Alarm
- Sensor flow can not be
measured correct. Input is over
max. level. Will normally only occur
starting from zero flow to high flow.
Will be present for max. 12 min-
utes.
Factory reset has occurred
Alarm
- A factory reset has oc-
curred (some settings have
changed, check all used settings)
Eeprom write error
Alarm
- Eeprom write error (see log
for details)
Flow total counter eeprom error
Alarm
- Flow totalize Eeprom error
(non- resettable counter maybe
incorrect in Eeprom)
Sensor Setting error
Alarm
- Sensor Setting error (some
settings are incorrect or changed)
Counter output Forward Pulsover-
flow
Alarm
- Counter output Forward
Pulse overflow (too low pulse
volume)
Содержание MagFlux
Страница 6: ...6 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Страница 12: ...12 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Страница 38: ...38 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Страница 106: ...106 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Страница 144: ...144 GB MagFlux Manual 0812 Electromagnetic Flow Meter This page intentionally left blank...
Страница 149: ...Index 5 GB MagFlux Manual 0812 Electromagnetic Flow Meter Electromagnetic Flow Meter This page intentionally left blank...