6. Electrical work

6.1. Indoor unit (Fig. 6-1)

1. Remove the two electrical wiring service panels.
2. Wire the power cable and control cable separately through the respective wiring

entries given in the diagram.

• Do not allow slackening of the terminal screws

.

• Leave excess cable so that the electrical box can be suspended below the unit

during servicing. (Approx. 50 to 100 mm, 2 to 4 inch)

A

Entry for control cable

B

Entry for power

C

Clamp

D

Service panel for indoor controller switch setting

E

Service panel for electrical wiring

F

Power supply terminals (separate indoor/outdoor unit power supplies,
K-control application)

G

Indoor / Outdoor unit connecting terminals

H

Remote controller connector

I

Secure with the clamp

J

Intake sensor

K

Holder

Fig. 6-1

A

E

D

J

,

K

B

C

I

G

F

H

L2 GR

L1

S3

S2

S1

1

2

6.1.1. Indoor unit power supplied from outdoor unit (A-control application)

The following connection patterns are available.
The outdoor unit power supply patterns vary on models.

1:1 System

Simultaneous twin system

* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.

A

Outdoor unit power supply

B

Wiring circuit breaker or isolating switch

C

Outdoor unit

D

Indoor unit/outdoor unit connecting cords

E

Remote controller

F

Indoor unit

G

Indoor unit earth

* Affix a label A that is included with the manuals near each wiring diagram for the indoor and outdoor units.

*1. Max. 50 m, 165 ft
*2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft
*3. The figures are NOT always against the ground.

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.

Notes: 1. Wiring size must comply with the applicable local and national code.

2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables and the indoor unit/outdoor unit connecting cables.
4. Install an earth longer than other cables.

A

Outdoor unit power supply

B

Wiring circuit breaker or isolating switch

C

Outdoor unit

D

Indoor unit/outdoor unit connecting cords

E

Remote controller

F

Indoor unit

G

Indoor unit earth

Indoor unit model
Indoor unit power supply
Minimum circuit ampacity
Maximum rating of overcurrent protective device

Indoor unit power supply
Indoor unit power supply earth
Indoor unit-Outdoor unit

*1

Indoor unit earth
Remote controller-Indoor unit

*2

Indoor unit L1-L2

*3

Indoor unit-Outdoor unit S1-S2

*3

Indoor unit-Outdoor unit S2-S3

*3

Remote controller-Indoor unit

*3

PLA-A12, 18, 24, 30

PLA-A36, 42

1A

2A

15A

15A

×

 AWG16 (polar)

×

 AWG16 (polar)

×

 Min. AWG16

×

 Min. AWG16

×

 AWG22 (Non-polar)

×

 AWG22 (Non-polar)

AC 208/230 V

AC 208/230 V

DC24 V

DC24 V

DC12 V

DC12 V

Circuit

rating

Wir

ing

Wire No

×

 siz

e

S1

S2

L1

L2

GR

1
2

S1

S2

S3

S3

A

B

C

D

E

F

G

S1

S2

L1

L2

GR

1
2

S1

S2

S3

1
2

S1

S2

S3

S3

A

B

C

E

F

F

G

G

D

 BG79U795H01_en.pm6

05.12.1, 9:48 AM

7

Содержание Mr.Slim PLA-A

Страница 1: ...rrect use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este ma...

Страница 2: ...edical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communic...

Страница 3: ...the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit B Bolt pitch C Ceiling opening D Outer side o...

Страница 4: ...mm 11 16 7 8 inch Damage could result by failing to adhere to this range Fig 3 7 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior...

Страница 5: ...Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness o...

Страница 6: ...adhesive Observe the figure for piping work Use the included drain hose to change the extraction direction Max 65ft 5 to 7ft A B C B M L K D E D H I G D F F F Max 6inch J F Fig 5 1 Fig 5 2 1 Correct p...

Страница 7: ...uded with the manuals near each wiring diagram for the indoor and outdoor units 1 Max 50 m 165 ft 2 The 10 m 30 ft wire is attached in the remote controller accessory Max 500 m 1500 ft 3 The figures a...

Страница 8: ...troller accessory Max 500 m 1500 ft 3 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires ra...

Страница 9: ...V DC12V DC12V DC12V DC12V DC12V DC12V Circuit rating Wiring Wire No size For heat pump models For heat pump models S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E F S1 S2 L1 L2 GR GR 1 2 L1 L2 S...

Страница 10: ...ntrollers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remo...

Страница 11: ...1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230...

Страница 12: ...on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode sel...

Страница 13: ...1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safegu...

Страница 14: ...or voltage shortage and abnormal synchronous signal to main circuit Current sensor error 12 13 14 Others Other errors Refer to the technical manual for the outdoor unit 1 If the beeper does not sound...

Страница 15: ...d remote controller 1 for PLP 42AAMD 9 Installing the grille 1 4 5 6 2 0 2 3 Fig 9 1 Fig 9 2 A D C B A 11 16 3 16 0 Fig 9 3 B A C 1 1 D E 2 F G F B 1 9 2 Preparing to attach the grille Fig 9 2 With th...

Страница 16: ...the connector is not covered with the glass tube tracking resulting in fire may occur 9 Installing the grille C B A D B A D Fig 9 9 A Button B Vane motor C Up down vanes D Connector A Clamp B Cable C...

Страница 17: ...on procedures while waiting for the stable operation 10 Easy maintenance function This function only for A control By using the maintenance mode you can display many types of maintenance data on the r...

Страница 18: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Отзывы: