4.3. Indoor unit (Fig. 4-2)

Heat insulation for refrigerant pipes:

1

Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that
the end of the pipe cover touches the side of the unit.

2

Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure
that the end of the pipe cover touches the side of the unit.

3

Secure both ends of each pipe cover with the enclosed bands. (Attach the bands
20 mm from the ends of the pipe cover.)

• After connecting the refrigerant piping to the indoor unit, be sure to test the pipe

connections for gas leakage with nitrogen gas. (Check that there is no refrigerant
leakage from the refrigerant piping to the indoor unit.)

4.4. For twin/triple combination

Refer to the outdoor unit installation manual.

4. Installing the refrigerant piping

Fig. 4-2

B

D

E

A

C

F

J

H

I

B

,

C

F

G

A

Refrigerant pipe and insulating ma-
terial

B

Pipe cover (large)

C

Pipe cover (small)

D

Refrigerant pipe (gas)

E

Refrigerant pipe (liquid)

F

Band

G

Cross-sectional view of connection

H

Pipe

I

Insulating material

J

Squeeze

5. Drainage piping work

5.1. Drainage piping work (Fig. 5-1)

• Use VP25 (O.D. ø32 mm, 1-1/4 inch PVC TUBE) for drain piping and provide 1/100

or more downward slope.

• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.

Max. 65ft

5 to 7ft

A

B

C

B

M

L

K

D

E

D

H

I

G

D

F

F

F

Max. 6inch

J

F

Fig. 5-1

Fig. 5-2

1

Correct piping

2

Wrong piping

A

Insulation (9 mm, 3/8 inch or more)

B

Downward slope (1/100 or more)

C

Support metal

K

Air bleeder

L

Raised

M

Odor trap

Grouped piping

D

O.D. ø32 mm, 1-1/4 inch PVC TUBE

E

Make it as large as possible

F

Indoor unit

G

Make the piping size large for grouped piping.

H

Downward slope (1/100 or more)

I

O.D.  ø38 mm, 1-1/2 inch PVC TUBE for
grouped piping.
(9 mm, 3/8 inch or more insulation)

J

Up to 85 cm, 33-7/16 inch

1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 5-2)

(Affix the tube using PVC adhesive then secure it with a band.)

2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32 mm, 1-1/4 inch).

(Affix the pipe using PVC adhesive then secure it with a band.)

3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 mm, 1-1/4 inch and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a

A

Unit

B

Insulating material

C

Band

D

Drain port (transparent)

E

Insertion margin

F

Matching

G

Drain pipe

(O.D. ø32 mm, 1-1/4 inch PVC TUBE)

H

Insulating material (purchased locally)

I

Transparent PVC pipe

J

O.D. ø32 mm, 1-1/4 inch PVC TUBE

(Slope 1/100 or more)

K

Drain socket

G

7/16

1

1

1

B

A

C

C

F

K

H

D E

E

I

J

C

(inch)

band. (Both insulating material and band are supplied with the unit.)

 BG79U795H01_en.pm6

05.12.1, 9:48 AM

6

Содержание Mr.Slim PLA-A

Страница 1: ...rrect use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este ma...

Страница 2: ...edical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communic...

Страница 3: ...the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit B Bolt pitch C Ceiling opening D Outer side o...

Страница 4: ...mm 11 16 7 8 inch Damage could result by failing to adhere to this range Fig 3 7 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior...

Страница 5: ...Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness o...

Страница 6: ...adhesive Observe the figure for piping work Use the included drain hose to change the extraction direction Max 65ft 5 to 7ft A B C B M L K D E D H I G D F F F Max 6inch J F Fig 5 1 Fig 5 2 1 Correct p...

Страница 7: ...uded with the manuals near each wiring diagram for the indoor and outdoor units 1 Max 50 m 165 ft 2 The 10 m 30 ft wire is attached in the remote controller accessory Max 500 m 1500 ft 3 The figures a...

Страница 8: ...troller accessory Max 500 m 1500 ft 3 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires ra...

Страница 9: ...V DC12V DC12V DC12V DC12V DC12V DC12V Circuit rating Wiring Wire No size For heat pump models For heat pump models S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E F S1 S2 L1 L2 GR GR 1 2 L1 L2 S...

Страница 10: ...ntrollers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remo...

Страница 11: ...1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230...

Страница 12: ...on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode sel...

Страница 13: ...1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safegu...

Страница 14: ...or voltage shortage and abnormal synchronous signal to main circuit Current sensor error 12 13 14 Others Other errors Refer to the technical manual for the outdoor unit 1 If the beeper does not sound...

Страница 15: ...d remote controller 1 for PLP 42AAMD 9 Installing the grille 1 4 5 6 2 0 2 3 Fig 9 1 Fig 9 2 A D C B A 11 16 3 16 0 Fig 9 3 B A C 1 1 D E 2 F G F B 1 9 2 Preparing to attach the grille Fig 9 2 With th...

Страница 16: ...the connector is not covered with the glass tube tracking resulting in fire may occur 9 Installing the grille C B A D B A D Fig 9 9 A Button B Vane motor C Up down vanes D Connector A Clamp B Cable C...

Страница 17: ...on procedures while waiting for the stable operation 10 Easy maintenance function This function only for A control By using the maintenance mode you can display many types of maintenance data on the r...

Страница 18: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Отзывы: