background image

14

• On wireless remote controller

The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp

• On wired remote controller

Check code displayed in the LCD.

• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.

Symptom

Cause

Wired remote controller

LED 1, 2 (PCB in outdoor unit)

PLEASE WAIT

PLEASE WAIT 

 Error code

Display messages do not appear even
when operation switch is turned ON
(operation lamp does not light up).

For about 2
minutes following
power-on

After about 2
minutes has
expired following
power-on

After LED 1, 2 are lighted, LED 2 is turned off,
then only LED 1 is lighted. (Correct operation)

Only LED 1 is lighted. 

 LED 1, 2 blink.

Only LED 1 is lighted. 

 LED 1 blinks twice,

LED 2 blinks once.

• For about 2 minutes following power-on, operation of the

remote controller is not possible due to system start-up. (Cor-
rect operation)

• Connector for the outdoor unit’s protection device is not con-

nected.

• Reverse or open phase wiring for the outdoor unit’s power

terminal block (L1, L2, GR)

• Incorrect wiring between indoor and outdoor units (incorrect

polarity of S1, S2, S3)

• Remote controller wire short

On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short pipng sound.

[Output pattern B]

Errors detected by unit other than indoor unit (outdoor unit, etc.)

Beeper sounds/OPERATION

Symptom

Remark

INDICATOR lamp flashes

Check code

(Number of times)

1

E9

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)

2

UP

Compressor overcurrent interruption

3

U3, U4

Open/short of outdoor unit thermistors

4

UF

Compressor overcurrent interruption (When compressor locked)

5

U2

Abnormal high discharging temperature/49C worked/insufficient refrigerant

6

U1, Ud

Abnormal high pressure (63H worked)/Overheating safeguard operation

7

U5

Abnormal temperature of heat sink

8

U8

Outdoor unit fan safeguard stop

9

U6

Compressor overcurrent interruption/Abnormal of power module

10

U7

Abnormality of super heat due to low discharge temperature

11

U9, UH

Abnormality such as overvoltage or voltage shortage and abnormal synchronous
signal to main circuit/Current sensor error

12

13

14

Others

Other errors (Refer to the technical manual for the outdoor unit.)

*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on,

there are no error records.

*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was received, the

specified refrigerant address is incorrect.

For details, check the LED display
of the outdoor controller board.

7. Test run

Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

LED 1 (power for microcomputer)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED 2 (power for remote controller)

Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
indoor unit which is connected to the outdoor unit refrigerant address “0”.

LED 3 (communication between indoor and outdoor units only

Indicates state of communication between the indoor and outdoor units. Make sure that this LED is

A-control)

always blinking.

7.4. Check of drainage (Fig. 7-5)

• During the test run, ensure the water is being properly drained out and that no

water is leaking from joints.

• Always check this during installation even if the unit is not required to provide cool-

ing/drying at that time.

• Similarly, check the drainage before finishing ceiling installation in a new premises.
(1) Remove the cover of the water supply inlet and add about 1000 cc, 1/4 gal of

water using a water supply pump etc. During this process, be careful not to spray
water into the drain pump mechanism.

(2) Confirm that water is being drained out through the drainage outlet, after switch-

ing over from remote control mode to test run mode.

(3) After checking the drainage, ensure that the cover is replaced and the power

supply is isolated.

(4) After confirming the drainage system is functioning, replace the drain plug.

A

B

C

D

E

Fig. 7-5

A

Insert the pump end 3 to 5 cm,

1-3/16 to 2 inch

B

Cover of water supply inlet

C

About 1000 cc, 1/4 gal

D

Water

E

Drain plug

Wireless remote controller

Wired remote

controller

 BG79U795H01_en.pm6

05.12.1, 9:48 AM

14

Содержание Mr.Slim PLA-A

Страница 1: ...rrect use read this manual and the outdoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este ma...

Страница 2: ...edical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medical care and communic...

Страница 3: ...the field Install securely ensuring that there is no clearance between the ceiling panel grille and between the main unit grille A Outer side of main unit B Bolt pitch C Ceiling opening D Outer side o...

Страница 4: ...mm 11 16 7 8 inch Damage could result by failing to adhere to this range Fig 3 7 Caution Use the top half of the box as a protective cover to prevent dust or debris from getting inside the unit prior...

Страница 5: ...Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness o...

Страница 6: ...adhesive Observe the figure for piping work Use the included drain hose to change the extraction direction Max 65ft 5 to 7ft A B C B M L K D E D H I G D F F F Max 6inch J F Fig 5 1 Fig 5 2 1 Correct p...

Страница 7: ...uded with the manuals near each wiring diagram for the indoor and outdoor units 1 Max 50 m 165 ft 2 The 10 m 30 ft wire is attached in the remote controller accessory Max 500 m 1500 ft 3 The figures a...

Страница 8: ...troller accessory Max 500 m 1500 ft 3 The figures are NOT always against the ground Notes 1 Wiring size must comply with the applicable local and national code 2 Use copper supply wires 3 Use wires ra...

Страница 9: ...V DC12V DC12V DC12V DC12V DC12V DC12V Circuit rating Wiring Wire No size For heat pump models For heat pump models S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E F S1 S2 L1 L2 GR GR 1 2 L1 L2 S...

Страница 10: ...ntrollers are connected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remo...

Страница 11: ...1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230...

Страница 12: ...on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode sel...

Страница 13: ...1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safegu...

Страница 14: ...or voltage shortage and abnormal synchronous signal to main circuit Current sensor error 12 13 14 Others Other errors Refer to the technical manual for the outdoor unit 1 If the beeper does not sound...

Страница 15: ...d remote controller 1 for PLP 42AAMD 9 Installing the grille 1 4 5 6 2 0 2 3 Fig 9 1 Fig 9 2 A D C B A 11 16 3 16 0 Fig 9 3 B A C 1 1 D E 2 F G F B 1 9 2 Preparing to attach the grille Fig 9 2 With th...

Страница 16: ...the connector is not covered with the glass tube tracking resulting in fire may occur 9 Installing the grille C B A D B A D Fig 9 9 A Button B Vane motor C Up down vanes D Connector A Clamp B Cable C...

Страница 17: ...on procedures while waiting for the stable operation 10 Easy maintenance function This function only for A control By using the maintenance mode you can display many types of maintenance data on the r...

Страница 18: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Отзывы: