5. Drainage piping work

A

B

C

5.1. Drainage piping work (Fig. 5-1)

• Drain pipes should have an inclination of 1/100 or more.
• For extension of the drain pipe, use a soft hose (inner dia. 15 mm, 19/32 inch)

available on the market or hard vinyl chloride pipe (VP-20/O.D. ø26 mm, 1-1/32
inch PVC TUBE).  Make sure that there is no water leakage from the connections.

• If the drain pipe passes indoors it must be covered with insulating material (foamed

polyethylene: specific gravity: 0.03, thickness: 9 mm, 23/64 inch or more) available on the
market.

• Do not put the drain piping directly in a drainage ditch where sulphuric gas may be

generated.

• When piping has been completed, check that water flows from the end of the drain

pipe.

A

Drain connection socket

C

Indoor unit’s drain hose

B

On site drain pipe (VP-20)

 Caution:

The drain pipe should be installed according to this Installation Manual to en-
sure correct drainage. Thermal insulation of the drain pipes is necessary to
prevent condensation. If the drain pipes are not properly installed and insu-
lated, condensation may drip on the ceiling, floor or other possessions.

Preparing left and left rear piping (Fig. 5-2)

1

Remove the drain cap.

• Remove the drain cap by holding the bit that sticks out at the end of the pipe and

pulling.

A

Drain cap

2

Remove the drain hose.

• Remove the drain hose by holding on to the base of the hose 

a

 (shown by arrow)

and pulling towards yourself 

b

.

3

Insert the drain cap.

• Insert a screwdriver etc into the hole at the end of the pipe and be sure to push to

the base of the drain cap.

4

Insert the drain hose.

• Push the drain hose until it is at the base of the drain box connection outlet.
• Please make sure the drain hose hook is fastened properly over the extruding drain

box connection outlet.

B

Hooks

Remove the side panel of the indoor unit on the drain side. Pour water in the drain
pan and check that it comes out the drain pipe end. After confirmation, reinstall the
side panel.

A

a

b

A

A

B

1

3

2

4

Fig. 5-2

4. Installing the refrigerant piping

A

B

C

D

E

F

G

Fig. 4-4

4.3. Positioning refrigerant and drain piping

1

Position of refrigerant and drain piping (Fig. 4-2)

• The drain pipe can be cut midway to meet the on-site conditions.

A

(Total length of flexible hose)

D

Drain hose

B

Liquid pipe

E

Left-side piping

C

Gas pipe

F

Right-side piping

2

Determine the position of the knockout holes on the unit body. (Fig. 4-3)

s

Cut the knockout holes using a saw blade or an adequate knife.

Take care not to damage other parts of the unit.

• Remove the corner box and drill a knockout hole. If a hole is made without remov-

ing the box, the drain hose could be damaged.

A

Left-side piping

D

Remote controller cable through hole

B

Lower piping

E

Corner box

C

Right-side piping

Fig. 4-2

E

D

B

C

A

C

B

D

F

1-3/8

17-11/16

22-7/8

11-1/32

1-7/32

2-1/8

3-3/8

6-1/32

27-9/16

A

E

2-3/8

13/32

7/8

2-3/4

13/16

9-21/32

D

5/16

B

E

D

13/32

7-15/32

7/8

2-3/4

1-3/8

5/16

2-3/8

C

E

5/16

2-3/8

13/32

7/8

2-3/4

13/16

9-21/32

D

Fig. 4-3

1

2

4.4. Refrigerant piping (Fig. 4-4)

Indoor unit

1. Remove the flare nut and cap of the indoor unit.
2. Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil

(available from your local supplier) to the flare sheet surface.

3. Quickly connect the on site cooling pipes to the unit.
4. Wrap the pipe cover 

3

 that is attached to the gas pipe and make sure that the

connection join is not visible.

5. Wrap the pipe cover of the unit’s liquid pipe and make sure that it covers the

insulation material of the on site liquid pipe.

6. Use the bands that are provided 

4

 to tighten both ends (15–20mm, 19/32 to

25/32 inch) of each pipe cover 

3

.

A

Cooling pipe and insulation (available from local supplier)

B

Unit’s gas pipe

E

Bands 

4

C

Unit’s liquid pipe

F

On site gas pipe

D

Pipe cover 

3

G

On site liquid pipe

(inch)

(inch)

 BG79U874H01_en

05.11.30, 9:23

6

Содержание Mr.Slim PKA-A GAL

Страница 1: ...e outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Espa ol MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el m...

Страница 2: ...unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the...

Страница 3: ...wall you must consult the building contractor A Supporting piece I Bottom left pipe slot knockout hole B Mount board J Bottom right pipe slot 90 mm 3 9 16 inch C Main body K Bottom right pipe slot kno...

Страница 4: ...ipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessa...

Страница 5: ...ap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness of 12 mm 1 2 inch or more The indoor parts of the drain pipe should be wrapped...

Страница 6: ...e indoor unit on the drain side Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refr...

Страница 7: ...ded with the manuals near each wiring diagram for the indoor and outdoor units A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit outdoor unit connec...

Страница 8: ...el affixed near each wiring diagram for the indoor and outdoor units Outdoor unit DIP switch settings when using separate indoor unit outdoor unit power supplies only Indoor unit specifications Requir...

Страница 9: ...re No size For heat pump models For heat pump models S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E F S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E G 1 SW5 Set the DIP switch of the ind...

Страница 10: ...onnected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1...

Страница 11: ...1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230...

Страница 12: ...st 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and s...

Страница 13: ...1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safegu...

Страница 14: ...o the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only A control Indicates state of communication between the indoor and outdoor units Make sure that this L...

Страница 15: ...button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use t...

Страница 16: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Отзывы: