15

Maintenance mode operation procedures

(1) Press the 

TEST

 button for three seconds to

activate the maintenance mode.

(2) Press the TEMP. 

 

 buttons to set the refrigerant address.

MAINTENANCE

(3) Select the data you want to display.

MENU

ON/OFF

Compressor
information

COMP ON
x10 HOURS

COMP ON
x100 TIMES

COMP ON
CURRENT (A)

Cumulative
operation time

ON/OFF
number

Operation
current

Display 

A

Display 

B

Display 

A

OUTDOOR UNIT
H·EXC. TEMP

OUTDOOR UNIT
OUTLET TEMP

OUTDOOR UNIT
OUTDOOR TEMP

Heat exchanger
temperature

Comp discharge
temperature

Outdoor ambient
temperature

Display 

A

Outdoor unit
information

INDOOR UNIT
INLET TEMP

INDOOR UNIT
H·EXC. TEMP

INDOOR UNIT
FILTER USE H

Indoor room
temperature

Heat exchanger
temperature

Filter operation
time

Display 

A

Indoor unit
information

* The filter operation time displayed is the number of hours the filter has been

used since the filter reset was performed.

(4) Press the 

FILTER

 button.

(5) The data is displayed in 

C

.

(Airflow temperature display example)

Flashing

Waiting for
response

Approx.

10 sec.

147°F

* Repeat steps (2) to (5) to check another date.

(6) Press the 

TEST

 button for three seconds or press the 

ON/OFF

 button to

deactivate the maintenance mode.

Stable operation

Using the maintenance mode, the operation frequency can be fixed and the op-
eration can be stabilized. If the air conditioner is stopped, use the following proce-
dure to start this operation.

COOL
STABLE MODE

HEAT
STABLE MODE

STABLE MODE
CANCEL

Stable cooling
operation

Stable heating
operation

Stable operation
cancellation

Display 

A

Press the 

MODE

 button to select the operation mode.

Press the 

FILTER

 button.

Waiting for stable
operation

Display 

D

Stable
operation

10-20 min.

* You can check the data using steps (3) to (5) of the maintenance mode opera-

tion procedures while waiting for the stable operation.

8. Easy maintenance function [This function only for A-control]

By using the maintenance mode, you can display many types of maintenance data
on the remote controller such as the heat exchanger temperature and compressor
current consumption for the indoor and outdoor units.
This function can be used whether the air conditioner is operating or not.
During air conditioner operation, data can be checked during either normal operation
or maintenance mode stable operation.
* This function cannot be used during the test run.
* The availability of this function depends on the connecting outdoor unit. Refer to the

brochures.

D

A

C

B

Display example (Comp discharge temperature 147°F)

Display 

C

 BG79U874H01_en

05.11.30, 9:24

15

Содержание Mr.Slim PKA-A GAL

Страница 1: ...e outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER Espa ol MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el m...

Страница 2: ...unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the...

Страница 3: ...wall you must consult the building contractor A Supporting piece I Bottom left pipe slot knockout hole B Mount board J Bottom right pipe slot 90 mm 3 9 16 inch C Main body K Bottom right pipe slot kno...

Страница 4: ...ipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessa...

Страница 5: ...ap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C 212 F or more thickness of 12 mm 1 2 inch or more The indoor parts of the drain pipe should be wrapped...

Страница 6: ...e indoor unit on the drain side Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 4 Installing the refr...

Страница 7: ...ded with the manuals near each wiring diagram for the indoor and outdoor units A Outdoor unit power supply B Wiring circuit breaker or isolating switch C Outdoor unit D Indoor unit outdoor unit connec...

Страница 8: ...el affixed near each wiring diagram for the indoor and outdoor units Outdoor unit DIP switch settings when using separate indoor unit outdoor unit power supplies only Indoor unit specifications Requir...

Страница 9: ...re No size For heat pump models For heat pump models S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E F S1 S2 L1 L2 GR GR 1 2 L1 L2 S1 S2 S3 S3 A B C H D B E G 1 SW5 Set the DIP switch of the ind...

Страница 10: ...onnected set one to Main and the other to Sub For setting procedures refer to Function selection of remote controller in the operation manual for the indoor unit 6 2 2 For wireless remote controller 1...

Страница 11: ...1 to 04 7 Press the G button and the current set setting number 2 will flash Use the F button to switch the setting number in response to the power supply voltage to be used Power supply voltage 230...

Страница 12: ...st 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and s...

Страница 13: ...1 P1 Intake sensor error 2 P2 P9 Pipe Liquid or 2 phase pipe sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error 5 P5 Drain pump error 6 P6 Freezing Overheating safegu...

Страница 14: ...o the outdoor unit refrigerant address 0 LED 3 communication between indoor and outdoor units only A control Indicates state of communication between the indoor and outdoor units Make sure that this L...

Страница 15: ...button to deactivate the maintenance mode Stable operation Using the maintenance mode the operation frequency can be fixed and the op eration can be stabilized If the air conditioner is stopped use t...