9.1 Requirements for Conformance to EMC Directive
9.1.1 Standards relevant to the EMC Directive
9
EMC AND LOW VOLTAGE DIRECTIVES
*1: QP : Quasi-peak value, Mean : Average value
*2: The PLC is an open type device (device installed to another device) and must be installed in a conductive control panel.
The tests for the corresponding items were performed while the PLC was installed inside a control panel.
Table9.1 Standards relevant to the EMC Directive (Continue)
Specification
Test Item
Test Details
Standard Value
EN61131-2 :
2003
EN61000-4-2
Electrostatic discharge
immunity
*2
Immunity test in which
electrostatic is applied to the
cabinet of the equipment.
8kV Air discharge
4kV Contact discharge
EN61000-4-3
Radiated electromagnetic
field immunity
*2
Immunity test in which electric
fields are irradiated to the
product.
1.4GHz-2.0GHz, 80-1000MHz, 10V/m,
80%AM modulation 1kHz
EN61000-4-8
Power frequency
magnetic field immunity
*2
Immunity test in which the
product is installed in the
magnetic field of the induction
coil.
50Hz/60Hz, 30A/m
EN61000-4-4
Electrical fast transient/
burst immunity
*2
Immunity test in which burst
noise is applied to the power line
and signal line.
AC power line: 2kV
DC power line: 2kV
DC I/O, analog, communication line: 1kV
EN61000-4-5
Surge immunity
*2
Immunity test in which lightning
surge is applied to the power line
and signal line.
AC power line:
Common mode 2kV, differential
mode 1kV
DC power line:
Common mode 1kV, differential
mode 0.5kV
DC I/O, analog, communication (shielded):
Common mode 1kV
DC I/O, analog (unshielded):
Common mode 0.5kV, differential
mode 0.5kV
Communication (unshielded):
1kV
EN61000-4-6
Conducted disturbances
immunity
*2
Immunity test in which high
frequency noise is applied to the
power line and signal line.
0.15-80MHz, 80%AM modulation 1kHz,
3Vrms