144
OUT C
(2) The following program uses the BCD data at X10 to X1F as the timer's set value.
[Ladder Mode]
[List Mode]
(3) The following program turns Y10 ON 250 ms after X0 goes ON.
[Ladder Mode]
[List Mode]
*4:
The setting value of the high-speed timer indicates its default time limit (10 ms).
: Counter number (bits)
Set value: Counter setting value (BIN 16 bits
*1
)
*1:
Counter value cannot be set by indirect designation.
See Page 100, Section 3.4 for further information on indirect designation.
*2:
Counter value can be set only with a decimal constant (K). A hexadecimal constant (H) or a real number cannot be used for
the counter value setting.
OUT C
Counter
5.3.3
OUT C
Setting
Data
Internal Devices
R, ZR
J \
U \G
Zn
Constants
K
Other
Bit
Word
Bit
Word
(Only C)
––
––
––
––
––
––
––
Set value
––
(Other
than T, C)
––
––
*2
––
Converts the BCD data at X10 to X1F to BIN
and stores the converted value at D10.
When X2 is turned ON, T2 starts measurement
using the data stored in D10 as the set value.
Y15 goes ON at the count-up of T2.
Step
Instruction
Device
4
*
Step
Instruction
Device
Basic
Process
High
performance
Redundant Universal
LCPU
C0
Set value
Setting in the range
from 1 to 32767 is valid.
K50
C1
Set value
Data register value in
the range from 1 to
32767 is valid.
D10
OUT C
Command
Command
D
D
@D0
C0
Indirect designation is
not permitted.