5
No. Name and appearance
Description
1)
“RUN” LED
Displays the operating status of the A1S68AD.
On
:Normal operation.
Flash :Write disabled error or average time/count setting error.
Off
:5 V power cut or watchdog timer error.
2)
Input range selector
switch SW1
Used to set the input range of each channel.
(Factory default: 0 to 10V)
The DIP switch numbers 1-8 correspond to the channel numbers.
3)
Input range selector
switch SW2
Setting of CH1
Input Range
SW1-1
SW2-1
SW3-1
-10 to 10V
OFF
OFF
OFF
0 to 10V
ON
0 to 5V
OFF
ON
1 to 5V
ON
0 to 20mA
OFF
ON
ON
4 to 20mA
ON
Setting disabled
OFF
OFF
Setting disabled
ON
Set CH2-CH8 in the same manner.
4)
Input range selector
switch SW3
RUN
12
34
56
78
ON
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
12
34
56
78
ON
SW1
123
45
678
ON
SW2
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
ON
OFF
SW3