Communication connectors and terminals
48
2.8
Communication connectors and terminals
2.8.1
PU connector
Mounting the operation panel or parameter unit
• With a connection cable, the operation panel or the parameter unit can be connected to the inverter.
Use the option FR-CB2[ ], or connectors and cables available on the market.
(To mount the operation panel, the optional connector (FR-ADP) is required.)
Securely insert one end of the connection cable until the stoppers are fixed.
• If the operation panel is removed from the inverter, the inverter does not conform to IP55.
NOTE
• Refer to the following table when fabricating the cable on the user side. Keep the total cable length within 20 m.
• Commercially available products (as of February 2015)
Communication operation
• Using the PU connector enables communication operation from a personal computer, etc. When the PU connector is
connected with a personal, FA or other computer by a communication cable, a user program can run to monitor the inverter
or read and write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation).
For the details, refer to the FR-A800 Instruction Manual (Detailed).
• If the operation panel is removed from the inverter, the inverter does not conform to IP55.
Operation panel connection cable
(FR-CB2[ ]) (option)
Operation panel
(FR-DU08-01)
Parameter unit
(FR-PU07) (option)
Operation panel connection connector
(FR-ADP) (option)
STF FWD PU
Operation panel
(FR-LU08-01) (option)
Name
Model
Manufacturer
Communication cable
SGLPEV-T (Cat5e/300 m)
24AWG
4P
Mitsubishi Cable Industries, Ltd.
RJ-45 connector
5-554720-3
Tyco Electronics