60
-
Use the fitting supplied with the unit to connect the drain hose, fastening it at the lowest point so that there is no slack, and
establishing a 10 mm drain slope. * Keep electrical wiring from running beneath the drain hose.
Be sure to fasten the drain hose down with a clamp.
There is danger of water overflowing the drain hose.
WARNING
After piping has been installed, check to make sure water drains well and that there is no overflow.
Drain hose
Lowest Point
(
)
Drain hose
Hose Clamp
It can be fastened
from inside or
outside the unit.
10mm
Avoidriding across an elevation
The drain hose
should slope
downward.
Keep free from trape
Do not pipe under water