108
-
1
Error display
:
e5
[Communications error during operation]
Indoor unit
Red LED
Green LED
2 time flash
Keeps flashing
Red LED
Green LED
2 time flash
Keeps flashing
Outdoor unit
Is the connection
of the signal wires at the
outdoor unit poor?
Is the connection
of the signal wires at the
indoor unit poor?
Did the remote
controller’s LCD return
to normal?
“ WAIT ”
The unit is normal.
Malfunction was due to
transient noise, etc.
Go to display diagnosis (page 95).
YES
(1)
(2)
NO
Repair
Repair
Reset power
supply.
YES
YES
NO
“ WAIT ”
Notes (1) Check for poor connections (disconnection, looseness) on the outdoor unit’s terminal block.
(2) Check for poor connections or disconnection of the signal lines between the indoor and outdoor units.
Reset power supply.
Did it return to normal?
YES
NO
Outdoor unit’s control PCB is
faulty. (Network communications
circuit is faulty.) Replace
Malfunction is due to noise, etc.
(The outdoor unit’s CPU went
out of control due to noise during
power on.)
Indoor unit
Red LED
Green LED
2 time flash
Keeps flashing
Red LED
Green LED
Stays OFF
Keeps flashing
Outdoor unit
2
Error display
:
e34
[Power supply open phase]
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
Green LED
1 time flash
Keeps flashing
Outdoor unit
YES
NO
Check the power supply.
Measure the power supply voltage.
Is the voltage between the phases
AC 220/230 V
YES
NO
Replace the noise filter
Noise filter
Is the voltage between the secondary side
phases AC 220/230 V
YES
NO
Replace the fuse
Is the fuse on the control
PCB blown?
YES
NO
Connect them correctly.
The outdoor unit control
PCB is faulty. Replace.
Are the connections between
the noise filter and the outdoor
unit control PCB good?
YES
NO
Check the inverter.
*
Inverter check before replacing the power fuse.
*
Replace the fuse
Is the power supply
fuse blown?
NO
NO
NO
YES
Is there a short between
phases in the noise filter?
Is the power transistor module or
diode stack cracked or damaged?
Is the reactor abnormal?
Replace the
noise filter
Change of outdoor
unit control PCB
Replace the
reactor.
Replace the
power fuse.
YES
YES
• Display Conditions
After the power goes ON, if the power supply is 0 V at either L1, N phase.