104
-
(4)
Error diagnosis procedures at the outdoor unit side
At the error diagnosis related to the outdoor unit, check at first the error code of remote controller and the illumination patterns of
norma1 and inspection display lamps in the same manner as the case of indoor unit.
Then estimate the outline, the cause and the location of error based on the pattern and proceed to the inspcetion and repair.
Since the self diagnosis function by means of the microcomputers of indoor/outdoor units provide the judgement of error of
microcomputers them selves irregularity power supply line, overload, etc. caused by the installation space, inadequate volume of
refrigerant etc., the location and cause of trouble will be discovered without difficulty.
In addition, the display lamps error code of indoor/outdoor unit is kept flashing, (except when the power supply is iterrupted) after
the irregularity is automatically recovered to give irregularity information to the service presonnel. If any mode of higher priority
than the error retained in memory occurs after the reset of error, it is switched to that mode and saved in the memory.
(a)
Replacement parts assembly related to the outdoor unit controller
Outdoor unit PCB, power transistor module, capacitor, noise filter, thermistor, (heat exchanger, discharge pipe, outdoor
temperature, power transistor), fuse, transformer, etc.
(b)
Replacement procedure of outdoor unit microcomputer printed circuit board.
Microcomputer printed circuit board can replaced with following procedure.
1) Confirm the parts numbers.
Applicable Model
FDCVA302HENR
PCA505A102ZZ
Parts No.
1 2 3 4
ON
Switch setting table
Set the switches ON or
OFF for each switch
No.
( ON, OFF)
Model
FDCVA
302HENR
2) Set the model using the model setting switch (SW4).
Switch setting table (All switches are set in the OFF position when shipped from the factory.)
3) Set the control select switch to match the previously set settings on the previous PCB.
If the previously set settings were set with jumper wires, the control select switch should be set in the ON position if there
was a jumper wire and in the OFF position if there wasn’t a jumper wire.
4) Connect the faston terminals and connectors to the control PCB.
When connecting the wires to the faston terminals, connect each wire to the terminal printed with the same color on the
PCB.
Note (1) When connecting the faston terminals to the control PCB, connect them so that there is no deformation of the far end of the PCB.
(c)
Parts layout on the outdoor unit inverter PCB
●
Replacement procedure of outdoor unit inverter PCB
Inverter PCB can replaced with following procedure.
1) Confirm the parts numbers.
Model
FDCVA302HENR
PCA505A103ZY
Parts No.