Manual No. '06

PAC-T-109

PACKAGED AIR-CONDITIONER

Air-Conditioning & Refrigeration Systems Headquarters

16-5, 2-chome, Kounan, Minato-ku, Tokyo, 108-8215, Japan

Fax : (03) 6716-5926

PACKAGED AIR-CONDITIONER

(Split system, Air to air heat pump type)

MULTI-TYPE (V-MULTI)
PACKAGED AIR-CONDITIONER

CEILING RECESSED TYPE

FDTVA302HEN1R

CEILING SUSPENDED TYPE

FDENVA302HEN1R

SATELLITE DUCTED TYPE

FDUMVA302HEN2R

(OUTDOOR UNIT)

FDCVA302HENR

(INDOOR UNIT)

FDTCA151R
FDTA151R
FDENA151R
FDKNA151R

Содержание FDCVA302HENR

Страница 1: ...it system Air to air heat pump type MULTI TYPE V MULTI PACKAGED AIR CONDITIONER CEILING RECESSED TYPE FDTVA302HEN1R CEILING SUSPENDED TYPE FDENVA302HEN1R SATELLITE DUCTED TYPE FDUMVA302HEN2R OUTDOOR U...

Страница 2: ...1 TABLE OF CONTENTS 1 PACKAGED AIR CONDITIONER 2 2 MULTI TYPE V MULTI PACKAGED AIR CONDITIONER 122 3 WIRELESS KIT OPTIONAL PARTS 190...

Страница 3: ...onal parts 12 3 Outdoor unit 14 1 2 4 Inside view 15 1 2 5 Exterior appearance 16 1 2 6 Piping system 17 1 2 7 Selection chart 18 1 2 8 Characteristics of fan 23 1 2 9 Noise level 23 1 Indoor unit 23...

Страница 4: ...ctions using the wired remote controller 76 8 Checking operation data 80 9 Test run 81 1 6 MAINTENANCE DATA 82 1 6 1 Servicing 82 1 6 2 Trouble shooting for refrigerant circuit 83 1 6 3 Diagnosing of...

Страница 5: ...temperature 4 There are only three power lines between the outdoor and indoor unit One cabtyre cable with 3 wires encased in one sheath is enough for conducting the wiring work between the outdoor un...

Страница 6: ...ubber mount for compressor Electric heater W 20 Crank case heater Operation control Wired remote control switch Optional RC E1R Operation switch Wireless remote control switch Optional RCN T 35W ER In...

Страница 7: ...for fan motor Rubber mount for compressor Electric heater W 20 Crank case heater Operation control Wireless remote control switch Optional RCN E1R Operation switch Wired remote control switch Optiona...

Страница 8: ...essure Pa Standard 50 Max 85 Outside air intake Air filter Q ty Shock vibration absorber Rubber sleeve for fan motor Rubber mount for compressor Electric heater W 20 Crank case heater Operation contro...

Страница 9: ...tage Voltage at starting Cycle Time Stop Time Dew point temperature 28 C or less relative humidity 80 or less Indoor unit 18 30 CD B Outdoor unit 15 43 CD B Max 50m 7 minutes or more 4 minutes or more...

Страница 10: ...pitch 675 Suspension bolts pitch Control box Outside air opening for ducting Exhaust air opening for ducting Control box Gas piping 9 52 3 8 Liquid piping or more Lug for suspension bolts Space for in...

Страница 11: ...Holes for suspension bolts M8 to M10 4pcs Not included Liquid piping Gas piping Liquid piping Gas piping Space for installation and service or more or more or more Obstacles Air ireturn grille Drain h...

Страница 12: ...Hole for wiring Inspection space 200 80 5 18 213 205 59 71 950 18 45 118 284 986 Suspension bolts pitch Unit mm VIEW A Liquid piping 9 52 3 8 472 Suspension bolts pitch Drain hose piece Accessory Inst...

Страница 13: ...ntend ed for screw holes and then fix it with screws This side is not grounded Earth wiring Remote control switch Remote control cord Shielded wire Precation in Extending the Remote control cord The c...

Страница 14: ...13 b Wireless remote controller 60 17 150...

Страница 15: ...3 L1 Open Open 500 L2 300 250 Open L3 100 150 100 L4 250 250 250 Installation type Notes 1 It is prohibited to install in a space enclosed with walls at four sides 2 Unit must be secured with anchor...

Страница 16: ...door unit Control box 4way valve High pressure switch 63H1 Low pressure sensor PSL Electronic expansion valve EEVH Electronic expansion valve EEVC Solenoid valve SV1 Compressor Service valve Liquid si...

Страница 17: ...er white Plaster white Plaster white Plaster white Front panel Front panel Side panel Vertical louver Horizontal louver Light gray Light gray Air return grille Plaster white b Ceiling suspended type F...

Страница 18: ...sor accumlator Check joint Check joint Check valve Indoor unit Outdoor unit Electronic expansion valve Electronic expansion valve EEVC Strainer Strainer Receiver Parts name Mark Thermistor for protect...

Страница 19: ...oor air temperture 12 W B Indoor air temperture 16 W B 2 Heating 15 16 17 18 19 20 21 22 24 23 25 Indoor air temperature DB Capacity compensation coeffcient 0 50 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1 4...

Страница 20: ...perture 24 W B Indoor air temperture 19 W B Indoor air temperture 12 W B Indoor air temperture 16 W B Indoor air temperature DB Power consumption correction factor 0 50 0 60 0 70 0 80 0 90 1 00 1 10 1...

Страница 21: ...temperature DB Sensible heat factor 0 60 0 65 0 70 0 75 0 80 0 85 0 90 0 95 1 00 1 05 15 10 5 0 5 10 15 20 25 30 35 40 43 Indoor air temperture 12 W B Indoor air temperture 24 W B Indoor air tempertu...

Страница 22: ...tance limit actual length for each respective piping system Equivalent length Actual length equivalent length of bends x number of bends in the piping Equivalent length for 1 bend 0 15 9 52 15 88 0 25...

Страница 23: ...of the model FDTVA302HEN1R with the air flow High the piping length of 15m the outdoor unit located 5m lower than the indoor unit indoor wet bulb temperature at 19 0 C and outdoor dry bulb temperature...

Страница 24: ...oor unit a Ceiling recessed type FDT Measured based on JIS B 8616 Mike position as right 1 5m Mike center low points Model FDTA301R Noise level 38 dB A at HIGH 35 dB A at MEDIUM 33 dB A at LOW N60 40...

Страница 25: ...ion as right Model FDUMA302R Noise level 35 dB A at HIGH 32 dB A at MEDIUM 29 dB A at LOW 2 Outdoor unit Measured based on JIS B 8616 Mike position at highest noise level in position as below Distance...

Страница 26: ...output XR5 X1 2 3 6 X4 TB CnB Z mark Remote operation input volt free contact Auxiliary relay For FM Auxiliary relay For DM Terminal block mark Connector Closed end connector Mark Parts name Mark Part...

Страница 27: ...output DC12V output Thermo ON output DC12V output Inspection output DC12V output Remote operation input volt free contact Auxiliary relay For FM Terminal block mark Connector mark LED 1 LED 2 LED 3 S...

Страница 28: ...ration Operation output DC12V output XR2 XR3 XR4 XR5 X1 2 3 6 X4 TB CnA Z mark Heating output DC12V output Thermo ON output DC12V output Inspection output DC12V output Remote operation input volt free...

Страница 29: ...ay for CH Parts name Crankcase heater SM1 20S 52X3 CH 52X1 Fan motor Compressor motor FMO1 Mark Meaning of marks CM High pressure switch Thermistor H X temp Thermistor discharge temp Low pressure sens...

Страница 30: ...n Check indicator light During operation Lit in green In case of error Flashing in red FAN SPEED switch This switch is used to set the airflow volume SET switch This switch is used to apply the timer...

Страница 31: ...is pressed the mode is sequentially changed in order HI LO MED OPERATION MODE select button The operation mode on the side of the indicator is the currently selected opera tion mode It will switch in...

Страница 32: ...depending on the room temperature and the temperature of indoor heat exchanger When the switching between the cooling and the heating is made within 3 minutes the compressor will not operate for 3 min...

Страница 33: ...Pattern of operation Operation block Thermal drying starting for 8 or 16 minutes after operation started A 16 minutes The air flow is set at 1 speed lower than the set air flow 8 minutes Continuous c...

Страница 34: ...C or above or 7 minutes passes Heat exchanger temperature 35 C or above or 7 minutes passes Compressor ON Defrosting ends Thermostat ON Thermostat OFF Defrosting starts Compressor OFF Notes 1 If J2 s...

Страница 35: ...R model 1 Louver Control a While the air conditioner is operating press the LOUVER switch AUTO is displayed for 3 seconds and the swing louvers move up and down continuously b When fixing the position...

Страница 36: ...e thermostat goes OFF the louver position is set in the horizontal position Note 1 The compressor stops when protection control starts n Heating overload porotection If an overload condition is sensed...

Страница 37: ...output connectors CnT are provided on the control PCB of indoor unit Operation output Power to engage DC 12V relay provided by the customer is outputted during operation Heating output Power to engage...

Страница 38: ...it is turned on at the field Input signal to CnT becomes Valid at OFF ON only and the motion of air conditioner ON OFF is inverted CnT Input Air Conditioner A Air Conditioner B OFF OFF ON ON ON ON ON...

Страница 39: ...n memory regardless of whether power failure compensation is enabled or disabled and the quiet mode setting is cancelled regardless of whether power failure compensation is enabled or disabled 1 When...

Страница 40: ...after the compressor starts the speed is set at the target speed ii Compressor protective start 3 3 3 3 3 1 The first additional time the compressor starts after the power is turned ON compressor pro...

Страница 41: ...sor speeds and times Specified speed 42 rps Time 10 min Note 1 During this control if the compressor is stopped by the remote controller etc this control is repeated 2 This control is stopped after 10...

Страница 42: ...C Zone a Zone b Zone c Zone Outdoor air temperature C Outdoor heat exchanger temperature C 3 Snow protection fan control When DIP switch SW3 2 on the outdoor unit s control PCB is ON or when in the st...

Страница 43: ...mperature Tho P is 75 C the outdoor unit fan tap speed is lowered by 1 speed d End conditions When the conditions in item 3 above and the outdoor unit fan tap speed determined in item i are sensed 2 t...

Страница 44: ...perature or lower as shown in the figure at right for 15 seconds continuously or the intake gas saturation temperature SST obtained from the low pressure sensor s LPT de tected value and outdoor air t...

Страница 45: ...arge pipe temperature If it rises still higher the com pressor is stopped 1 Compressor speed control 2 Discharge pipe temperature abnormal a If the discharge pipe temperature has risen to 115 C or hig...

Страница 46: ...e cooling mode the compressor is stopped When the temperature drops to or below the set value compressor operation resumes automatically b If the outdoor heat exchanger temperature exceeds the set val...

Страница 47: ...utside the control region shown in item d above for 6 minutes continuously h Inverter protection control i Current cut control This prevents overcurrent at the inverter If the current exceeds the set...

Страница 48: ...r each model 2 Each protective control and abnormal sensing control is activated 3 If the setting of SW5 4 is changed during trial operation stop control is performed and the compressor is stopped tem...

Страница 49: ...op control is executed according to any of the following conditions 1 A low pressure of 0 087 MPa or lower is detected continuously for 5 seconds a Red LED On Green LED flashing Remote controller disp...

Страница 50: ...substance other than the specified refrigerant R410A such as air from entering the refrigerant cycle in installing or moving the air conditioning system Contamination by air or a foreign substance can...

Страница 51: ...ipes and drain pipes should be further covered with insulation materials of 10 20 mm thick 3 Consider the supporting strength of the location If the strength is not sufficient to sustain the unit weig...

Страница 52: ...1 When a hanging bolt exceeds 1 3 m in length use an M10 bolt and give it reinforcements such as braces Refrigerant piping Drain bolt Suspension Nut Washer Spring Washer Main body Level gauge 10 25mm...

Страница 53: ...e such harmful or flammable gas to flow into the room 1 5 m 2 m Suspension bolts Desceding slope greater than 1 100 Insulation material No bump Air vent No trap Not touching the water As wide as possi...

Страница 54: ...and fix the unit s installation height Remove the level gauge before installing the unit The unit s installation height can be minutely ad justed by means of the corner openings after the panel is in...

Страница 55: ...5 mm Fasten the drain piping side and the opposite corner temporarily 2 Hang the panel on the two suspension bolts to install it temporarily 3 Install the two remaining suspension bolts and tighten a...

Страница 56: ...ntrols are disabled The actual setting may also differ from the LCD display in the remote controller 1 Turn off the main power supply turn it off at the ground fault circuit breaker 2 Disconnect the c...

Страница 57: ...FDENA301R 8 Unit m Conditions 1 Installation height 2 4 3 0 m above the floor 2 Fan speed Hi 3 Location Free space without obstacles 4 Distance of reach indicates the horizontal distance after the win...

Страница 58: ...ral number of indoor units Condition Illuminance at the recelver area 360 lux When no lighting fixture is located within 1 m of indoor unit in an ordinary office When the remote control unit is used w...

Страница 59: ...0 215 Fasten the bolts to the front of the slotted holes Air supply Flat washer accessory parts Ceiling board Fasten it securely with double nuts Suspension bolts Lug for suspension Unit Double nuts F...

Страница 60: ...rain piping left 53 53 109 10 Drain piping For left Drain piping For left back 175 19 Top Cover Unit mm Back cutout Back cover Cutting margin Right side cutout Top cutout 60 100 120 60 47 60 108 31 27...

Страница 61: ...e sure to fasten the drain hose down with a clamp There is danger of water overflowing the drain hose WARNING After piping has been installed check to make sure water drains well and that there is no...

Страница 62: ...nt on the part of your client user a Places where chilled or heated air circulates freely When the installation height exceeds 3m warmed air stays close to the ceiling In such cases suggest your clien...

Страница 63: ...slightly lower 3 Blower fan tap switch The following two methods are available in switching the blower fan tap Switch to the high speed tap with one of these methods 1 Set SW9 4 provided on the indoo...

Страница 64: ...air port lies on the back When connecting the duct to the return air port remove the air filte if it is fitted to return air port When placing the return air port to carry out suction from the bottom...

Страница 65: ...ss wool 25mm Use a wire net or equivalent to hold glass wool in place It may run out the allowable limit of unit operation Example When outdoor air temperature is 35 CD B return air temperature is 27...

Страница 66: ...0 1 100 and avoid riding across an elevation or makeing traps 2 When connecting the drain pipe to the unit pay suffcient attention not to apply excess force to the piping on the unit side Also fix the...

Страница 67: ...exists in the ceiling space elevate the piping to avoid the obstacle using an elbow or corresponding gadget When doing this if the stretch for the needed height is too high the back flow quantity of d...

Страница 68: ...econds or longer The display will change from SELECT ITEM SET TEST RUN 2 Press the button once while TEST RUN is displayed and cause DRAIN PUMP to be displayed 3 When the SET button is pressed a drain...

Страница 69: ...tions Terminals xRed wire YWhite wire ZBlack wire Use a cord of 0 3mm2 recommended 0 5mm2 maximum for a remote controller cord Remove a sheathe of the remote control ler cord for the section laid with...

Страница 70: ...nd the unit by the obstruction Secure the top space for 1 m or more Requ When more than one unit are installed side by side provide a 250mm or wider interval between them as a service space In order t...

Страница 71: ...ormance degradation a rise of high pressure resulting is an operation interruption a broken fan etc 3 Where the foundation is not stable secure the unit with wire etc Wind direction 1 Install the unit...

Страница 72: ...during a cooling opera tion which may become drain water causing a water leak accident or a risk of burns during a heating operation if touched accidentally with its surface reaching a high temperatu...

Страница 73: ...the vacuum gauge s needle pointer 3 Air tightness test and air purge Always use a vacuum pump to purge air trapped within an indoor and the refrigerant piping a Air tightness test 1 When all the flare...

Страница 74: ...erature drops below zero for several days in a row do not install a drain elbow or grommets Because of freezing drain water could be blocked from running freely There are 3 drain holes provided on the...

Страница 75: ...s are connected please make sure that all electrical components within the electrical component box are free of loose connector coupling or terminal connection and then attach the cover securely Impro...

Страница 76: ...controller b Set the SW1 select switch on the slave remote controller on the Slave setting It is set on the Master setting at the factory Note 1 Remote controller sensor activation settings are possi...

Страница 77: ...ing Indoor unit fan speed setting Louver control setting 01 03 04 05 06 07 08 09 10 Function number A Default setting Hi CEILING SET FILTER SIGN SET POSITION EXTERNAL INPUT SET ROOM TEMP OFFSET FAN CO...

Страница 78: ...be displayed one by one Select a desired function 3 Press the SET button The screen display will be switched as follows SETTING Setting C ex AUTO RUN ON 4 Press either or button A list of Settings C...

Страница 79: ...on setting process is completed Then the screen display will be switched to Function number A Function description B so if you want to continue to set another function repeat the stepa as explained ab...

Страница 80: ...temperature is set at a value lower than the upper limit value The set temperature is transmitted b If the lower limit is set q When in an operating mode other than the heating mode if a temperature t...

Страница 81: ...SET OPERATION DATA 2 Press the SET button while OPERATION DATA is displayed 3 The display will change to I U No 00 blinking indication Select the indoor unit number you want to have data displayed wit...

Страница 82: ...est run from an outdoor unit 1 Test run method a A test run can be initiated from an outdoor unit by using SW5 3 and SW5 4 for on site setting b Switching SW5 3 to ON will start the compressor c The u...

Страница 83: ...should be relived through the service port b Connect the charging hose of the gauge mani fold to the service port of the gas piping Close high pressure valve 2 of gange mani fold c Connect the chargi...

Страница 84: ...ting condition by operation pressure and temperature difference Making an accurate judgement requires a skill that is acquired only after years of experience one trouble may lead to an another trouble...

Страница 85: ...controller error code No indication LCD flashes continuously or is off E1 E5 E6 E7 E9 E10 E28 Cause Keeps flashing Keeps flashing 1 time flash Stays OFF E8 Stays OFF Stays OFF Stays OFF Power OFF L ph...

Страница 86: ...shing Stays OFF 1 time flash E35 Keeps flashing Stays OFF 1 time flash Current Abnormalities in a compressor over current E42 Keeps flashing Keeps flashing Keeps flashing Stays OFF 1 time flash Invert...

Страница 87: ...are control by a single remote controller Broken wire of indoor unit return air thermistor Error detail Error code Timing of error detection Broken wire of heat exchanger thermister Broken wire of dis...

Страница 88: ...nnect the power supply connector CNW1 or CNW0 on the indoor unit control PCB or turn the main power supply OFF Turn the main power supply OFF 3 Error diagnosis procedures at the indoor unit side To di...

Страница 89: ...me 1000hrs Display Setting time 600hrs Display Setting time 180hrs when shipped from factory SW5 4 SW5 3 ON OFF ON OFF ON OFF Switch Function Emergency operation Normal Fan control Powerful mode Fan c...

Страница 90: ...one 1 With None 1 With None 1 With None 1 With None 1 With None 1 Name Function Note 1 2 None means that jumper wire is not provided on the PCB or the connection is cut The replacement PCB is not equi...

Страница 91: ...1 With None 1 Name Function Note 1 2 None means that jumper wire is not provided on the PCB or the connection is cut The replacement PCB is not equipped with jumpers J1 J7 Instead SW7 and 8 with the...

Страница 92: ...nutes Louver close Dryness operation 120 minutes Louver close Dryness operation Invalid OFF ON OFF ON OFF ON OFF ON ON OFF ON OFF Switch Function OFF ON Note 1 It is normally ON only in the case of SW...

Страница 93: ...2 None means that jumper wire is not provided on the PCB or the connection is cut The replacement PCB is not equipped with jumpers J1 J4 J6 Instead SW7 and 8 with the same functions as jumpers J1 J4 J...

Страница 94: ...to normal when the power supply is reset Notes 1 In models other than FDT replace the fuse 2 FDT only Note 3 In models other than FDT it is CNW2 Notes 4 3 is GND 5 FDT only Control lines connected wr...

Страница 95: ...Z YES Note 1 Z is GND Note 2 3 is GND 2 1 Power supply reset Maltifunction by accidental noise YES Normal NO YES Remote controller wire short circuit Remote controller defective Remote controller wire...

Страница 96: ...s the voltage on the outdoor unit s transformer secondary side red red AC15V Is the voltage between the red and black wires in the remote controller DC10 11V when the remote controller is disconnected...

Страница 97: ...are connected directly to the outdoor unit operate The outdoor unit operates normally Press the check SW and check the registered indoor units Remote controller display is normal Only the indoor units...

Страница 98: ...acement indoor unit control PCB Power supply reset Normal Normal NO NO Replacement remote controller NO YES Replacement indoor unit control PCB Remote controller wire short circuit YES NO Replacement...

Страница 99: ...ment Defective indoor unit heat exchanger thermistor input circuit Defective indoor unit heat exchanger thermistor Replacement YES YES NO NO Is the air return thermistor connector connection OK Correc...

Страница 100: ...teristics of the indoor heat exchanger thermistor OK Does the heating overload state exist NO YES NO NO YES Notes 1 Check if the overload state exists or not using the following check points Is there...

Страница 101: ...ommunications are faulty between master and slave indoor units YES NO Are the settings between the master and slave indoor units good Are the unit settings correct YES NO NO Is the wiring between the...

Страница 102: ...hite DC15V Replacement indoor unit control PCB Replacement indoor unit control PCB Detective fan motor Replacement indoor unit control PCB Replacement transformer 3 White is GND 1 2 3 White is GND Not...

Страница 103: ...unit control PCB Replacement indoor unit control PCB Detective fan motor Replacement indoor unit control PCB Replacement transformer 3 Black is GND 1 2 3 Black is GND Note 2 CNM 3 Black is GND Is the...

Страница 104: ...stics of remote controller therm istor OK or is there any broken wire Is the remote controller thermistor connector co nnection OK Correction Temperrature C 0 1 2 4 6 8 10 12 Resistance value k 65 62...

Страница 105: ...apacitor noise filter thermistor heat exchanger discharge pipe outdoor temperature power transistor fuse transformer etc b Replacement procedure of outdoor unit microcomputer printed circuit board Mic...

Страница 106: ...rost prohibited temperature 45 min Test run operation Normal Test run operation Heating Test run operation Cooling SW3 1 SW3 2 SW3 4 SW5 3 SW5 4 Switch Function ON OFF ON OFF ON OFF ON OFF ON OFF Note...

Страница 107: ...then mount it on the PCB If the grease is not applied the power transistor may be damaged Use all the silicone grease Tighten the power transistor mounting screws of the inverter PCB and connect the t...

Страница 108: ...T1 T2 T8 T9 T4 T10 T11 Noise filter PCB PWB3 T5 T6 CNO2 CNO1 CNQ1 CNG1 CNI1 CNI3 CNG2 CNI2 CNI4 CNQ2 CNFAN CNQ1 CNQ2 When the outdoor unit fan motor is abnormal Refer to page 114 Must be conductive W...

Страница 109: ...D Green LED 2 time flash Keeps flashing Red LED Green LED Stays OFF Keeps flashing Outdoor unit 2 Error display e34 Power supply open phase Indoor unit Red LED Green LED Stays OFF Keeps flashing Red L...

Страница 110: ...outdoor unit Is the installation space proper Is the refrigerant level too high Is the heat exchanger dirty or clogged When the following conditions exist the compressor s speed is controlled If the c...

Страница 111: ...nute Hold Discharge pipe temperature C Temperature T C Compressor control 100 105 Discharge pipe temp C Release Operoble Error stop Thermistor resistance k 85 115 Abnormal temperature detection Is the...

Страница 112: ...compressor restarts If this state is detected 3 times in 40 minutes Is the outdoor air temperature thermistor connector connection OK Repair NO NO YES YES Is the outdoor air temperature thermistor ch...

Страница 113: ...3 minute delay the com pressor restarts If this state is detected 3 times in 40 minutes Error display e40 NO Is the service valve fully open The outdoor unit s control PCB is faulty the 63H1 input ci...

Страница 114: ...S YES Replace the compressor Check the power transistor module See page 118 OK NG Replace the outdoor unit inverter PCB Replace the outdoor unit inverter PCB It may be malfunction due to transient noi...

Страница 115: ...voltage NO Reset the power supply YES Depends on whether or not transient noise passed through Is fuse F2 blown YES Replace the fuse 12 DC Fan motor abnormal Indoor unit Red LED Green LED Stays OFF K...

Страница 116: ...pressure sensor is 0 079 MPa or lower continuously for 15 seconds the compressor stops After a 3 minute delay the compressor starts again but if it happens 3 times within 60 minutes Indoor unit Red LE...

Страница 117: ...OK Are the suction pipe thermistor characteristics OK is there any broken wire Correction NO YES YES NO Defective outdoor unit PCB Replacement Defective suction pipe thermistor input circuit Defectiv...

Страница 118: ...reen LED Stays OFF Keeps flashing Red LED Green LED 5 time flash Keeps flashing Outdoor unit NG NG NO NG YES Check of power supply Replacement compressor Replacement compressor OK Check the refrigeran...

Страница 119: ...es on each terminal P Power transistor P terminal U End of red harness to compressor N Power transistor N terminal V End of white harness to compressor W End of black or blue harness to compressor Nor...

Страница 120: ...the louver operated with the remote controller YES NO Repair the wire Normal Is LM wire locked NO YES Replace LM Defective indoor unit PCB Operate more than 1 min later Defective indoor unit PCB Repl...

Страница 121: ...o will change from flashing to light up continuously Example E8 DATA LOADING This message flashes while data are being read E8 ERROR DATA The data are then displayed beginning with item No 01 Displaye...

Страница 122: ...ck display Yellow The following three kinds are displayed Lights continuously Under timer operation Long lighting 2 seconds lighting 1 second stays OFF Filter sign Clean the air filter when this displ...

Страница 123: ...ons 126 1 Indoor unit 126 2 Outdoor unit 130 3 Operation chart 131 2 2 2 Range of usage limitations 133 2 2 3 Exterior dimensions 134 1 Indoor unit 134 2 Remote controller Optional parts 137 3 Outdoor...

Страница 124: ...emote controller 175 2 5 3 Installation of outdoor unit 176 1 Installation 176 2 Refrigerant piping work 178 3 Air tightness test and air purge 180 4 Refrigerant quantity 180 5 Drain piping work 181 6...

Страница 125: ...in the outdoor unit has its own self protection function that reacts according to abnormal high pressure and excessive high temperature 4 There are only three power lines between the outdoor and indoo...

Страница 126: ...iling recessed compact type FDTC Ceiling recessed type FDT Ceiling suspended type FDEN Wall mounted type FDKN Outdoor unit to be combined FDC 151 FDCVA302HENR 3 Horse Power Indoor unit assembly capaci...

Страница 127: ...re piping Connectable with VP25 I D 25 mm O D 32 mm Necessary both Liquid Gas lines Mounting kit Drain hose Decorative Panel Thermostat by electronics Turbo fan 1 mm in Safety equipment Wired remote c...

Страница 128: ...n motor Flare piping Connectable with VP25 I D 25 mm O D 32 mm Necessary both Liquid Gas lines Mounting kit Drain hose Decorative Panel Thermostat by electronics Turbo fan 1 mm in Safety equipment Wir...

Страница 129: ...Direct line start Unavailable Polypropylene net 2 Washable Rubber sleeve for fan motor Flare piping Connectable with VP20 I D 20 mm O D 26 mm Necessary both Liquid Gas line Mounting kit Drain hose Th...

Страница 130: ...230 240V 50Hz Direct line start Unavailable Long life fillter 2 Washable Rubber sleeve for fan motor Flare piping Connectable with VP16 I D 16 mm O D 22 mm Necessary both Liquid Gas lines Mounting ki...

Страница 131: ...e Q ty Noise level 1 The cooling and heating capabilities imply the values when the indoor unit of rated capacity is connected under the condition specified in ISO T1 2 The refrigerant quantity in the...

Страница 132: ...andard ISO T1 UNITARY AIR CONDITIONERS 2 The values shown in the above table are common to both cooling and heating operations FDT 151R FDTC 151R FDEN 151R FDKN 151R Cooling power consumption Heating...

Страница 133: ...urrent A Power source 100 Total operation characteristics Operation characteristic value of outdoor unit Operation characteristic value of indoor unit Example Conditions Operation Voltage Indoor unit...

Страница 134: ...4 minutes or more from start to stop or 3 minutes or more from stop to start 3 minutes or more In the illustration the L is main piping and ra andrb are branch piping Request 1 When the capacity of th...

Страница 135: ...115 140 Lug for suspension bolts Control box Drain hose piece Gas piping Liquid piping Suspension bolts Drain 12 7 1 2 6 35 1 4 Accessory Installed at site Connectable with VP25 M10 or M8 Max Drain up...

Страница 136: ...780 Suspension bolts pitch 675 Suspension bolts pitch Control box Outside air opening for ducting Exhaust air opening for ducting Control box Gas piping 6 35 1 4 Liquid piping or more Lug for suspensi...

Страница 137: ...nded type FDEN Model FDENA151R Unit mm If you are mounting units close together leave a space of 4000 or greater between unit Service space 4 12 18 long hole Service space Space for installation and s...

Страница 138: ...intend ed for screw holes and then fix it with screws This side is not grounded Earth wiring Remote control switch Remote control cord Shielded wire Precation in Extending the Remote control cord The...

Страница 139: ...138 b Wireless remote controller Unit mm 60 17 150...

Страница 140: ...2 3 L1 Open Open 500 L2 300 250 Open L3 100 150 100 L4 250 250 250 Installation type Notes 1 It is prohibited to install in a space enclosed with walls at four sides 2 Unit must be secured with anchor...

Страница 141: ...door unit Control box 4way valve High pressure switch 63H1 Low pressure sensor PSL Electronic expansion valve EEVH Electronic expansion valve EEVC Solenoid valve SV1 Compressor Service valve Liquid si...

Страница 142: ...er white Front panel Front panel Side panel Vertical louver Horizontal louver Light gray Light gray Air return grille Plaster white 2 2 5 Exterior appearance 1 Indoor unit a Ceiling recessed compact t...

Страница 143: ...142 Cool white d Wall mounted type FDKN 2 Outdoor unit Stucco white...

Страница 144: ...Check joint Check valve Indoor unit Outdoor unit Electronic expansion valve Electronic expansion valve EEVC Strainer Strainer Receiver Preset point of the protective devices Parts name Mark Thermisto...

Страница 145: ...door air temperture 12 W B Indoor air temperture 16 W B 2 Heating 15 16 17 18 19 20 21 22 23 24 25 Indoor air temperature DB Capacity compensation coeffcient 0 50 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1...

Страница 146: ...perture 24 W B Indoor air temperture 19 W B Indoor air temperture 12 W B Indoor air temperture 16 W B Indoor air temperature DB Power consumption correction factor 0 50 0 60 0 70 0 80 0 90 1 00 1 10 1...

Страница 147: ...temperature DB Sensible heat factor 0 60 0 65 0 70 0 75 0 80 0 85 0 90 0 95 1 00 1 05 15 10 5 0 5 10 15 20 25 30 35 40 43 Indoor air temperture 12 W B Indoor air temperture 24 W B Indoor air tempertu...

Страница 148: ...tance limit actual length for each respective piping system Equivalent length Actual length equivalent length of bends x number of bends in the piping Equivalent length for 1 bend 0 15 9 52 15 88 0 25...

Страница 149: ...y of the model FDCVA302HENR with the air flow High the piping length of 15m the outdoor unit located 5m lower than the indoor unit indoor wet bulb temperature at 19 0 C and outdoor dry bulb temperatur...

Страница 150: ...ir temperature Indoor unit 27 C DB 19 C WB Outdoor unit 35 C DB Notes 2 The data in the chart are measured in an unechonic room Notes 3 The noise levels measured in the field are usually higher than t...

Страница 151: ...d Wall mounted type FDKN 2 Outdoor unit Measured based on JIS B 8616 Mike position at highest noise level in position as below Distance from front side 1m Height 1m Model FDCVA302HENR Noise level 48...

Страница 152: ...V output XR2 XR3 XR4 XR5 X4 TB CnA Z mark Heating output DC12V output Thermo ON output DC12V output Inspection output DC12V output Remote operation input volt free contact Auxiliary relay For DM Termi...

Страница 153: ...utput Inspection output DC12V output XR5 X1 2 3 6 X4 TB CnB Z mark Remote operation input volt free contact Auxiliary relay For FM Auxiliary relay For DM Terminal block mark Connector Closed end conne...

Страница 154: ...2V output Thermo ON output DC12V output Inspection output DC12V output Remote operation input volt free contact Auxiliary relay For FM Terminal block mark Connector mark LED 1 LED 2 LED 3 SW1 SW2 Clos...

Страница 155: ...t Heating output DC12V output XR3 XR4 XR5 TB CnA Z AMP Thermo ON output DC12V output Inspection output DC12V output Remote operation input volt free contact Terminal block mark Connector Wirelss recei...

Страница 156: ...se heater SM1 20S 52X3 CH 52X1 Fan motor Compressor motor FMO1 Mark Meaning of marks CM High pressure switch Thermistor H X temp Thermistor discharge temp Low pressure sensor Thermistor suction temp T...

Страница 157: ...0A such as air from entering the refrigerant cycle in installing or moving the air conditioning system Contamination by air or a foreign substance can cause an abnormal pressure build up inside the re...

Страница 158: ...dity conditions there is danger of water drops dripping down If there is a possibility that the unit will be used under such conditions install 10 to 20 mm of insulation material to the main unit pipi...

Страница 159: ...it main body which can result in such problems that you cannot attach the panel or noises are generated from the interfering fan When embedded into ceiling 1 Determine the positions of hanging bolts 5...

Страница 160: ...VP 25 to be procured locally to the joint b Give the drain piping a descending grade 1 50 1 100 and never create a bump to go over or a trap c In connecting drain pipes care must be taken so as not to...

Страница 161: ...installation 1 Accessories It is attach to the panel 2 Make sure that the unit main body is positioned at the correct height and the opening on the ceiling is made to the correct dimensions with the l...

Страница 162: ...of a control box 11 Like drain pump wiring please band together by the clamp and put in louver motor wiring into a control box Figure 6 12 Please connect a louver motor connector Figure 6 Figure 6 Dr...

Страница 163: ...es should be further covered with insulation materials of 10 20 mm thick 3 Consider the supporting strength of the location If the strength is not sufficient to sustain the unit weight use reinforcing...

Страница 164: ...1 When a hanging bolt exceeds 1 3 m in length use an M10 bolt and give it reinforcements such as braces Refrigerant piping Drain bolt Suspension Nut Washer Spring Washer Main body Level gauge 10 25mm...

Страница 165: ...e such harmful or flammable gas to flow into the room 1 5 m 2 m Suspension bolts Desceding slope greater than 1 100 Insulation material No bump Air vent No trap Not touching the water As wide as possi...

Страница 166: ...and fix the unit s installation height Remove the level gauge before installing the unit The unit s installation height can be minutely ad justed by means of the corner openings after the panel is in...

Страница 167: ...5 mm Fasten the drain piping side and the opposite corner temporarily 2 Hang the panel on the two suspension bolts to install it temporarily 3 Install the two remaining suspension bolts and tighten a...

Страница 168: ...tion is fixed remote control operation and all automatic controls are disabled The actual setting may also differ from the LCD display in the remote controller 1 Turn off the main power supply turn it...

Страница 169: ...Air throw 7 5 Unit m Conditions 1 Installation height 2 4 3 0 m above the floor 2 Fan speed Hi 3 Location Free space without obstacles 4 Distance of reach indicates the horizontal distance after the w...

Страница 170: ...ral number of indoor units Condition Illuminance at the recelver area 360 lux When no lighting fixture is located within 1 m of indoor unit in an ordinary office When the remote control unit is used w...

Страница 171: ...0 215 Fasten the bolts to the front of the slotted holes Air outlet Flat washer accessory parts Ceiling board Fasten it securely with double nuts Suspension bolts Lug for suspension Unit Double nuts F...

Страница 172: ...Drain piping left 53 53 109 10 Drain piping For left Drain piping For left back 175 19 Top Cover Unit mm Back cutout Back cover Cutting margin Right side cutout Top cutout 60 100 120 60 47 60 108 31 2...

Страница 173: ...pply grills f Location not exposed to direct sunshine g Avoid the location exposed to oil splash or vapor h Avoid the location near to the machine emitting high frequency radio wave i Avoid the locati...

Страница 174: ...of mounting plate 1 The indoor unit weighs approx 12kg Therefore check whether the portion to install the unit can bear the weight of unit If it seems to be danger reinforce the portion by a plate or...

Страница 175: ...d The end shall not be sub merged in wa ter g Drain piping 1 Lay the drain piping with downgrade to facilitate flow of drain and do not make a trap or chevron shaped bend The drain piping can be taken...

Страница 176: ...tions Terminals xRed wire YWhite wire ZBlack wire Use a cord of 0 3mm2 recommended 0 5mm2 maximum for a remote controller cord Remove a sheathe of the remote control ler cord for the section laid with...

Страница 177: ...nd the unit by the obstruction Secure the top space for 1 m or more Requ When more than one unit are installed side by side provide a 250mm or wider interval between them as a service space In order t...

Страница 178: ...formance degradation a rise of high pressure resulting is an operation interruption a broken fan etc 3 Where the foundation is not stable secure the unit with wire etc Wind direction 1 Install the uni...

Страница 179: ...cooling opera tion which may become drain water causing a water leak accident or a risk of burns during a heating operation if touched accidentally with its surface reaching a high temperature becaus...

Страница 180: ...of the pipes 0 0 5 6 35 9 52 12 7 15 88 Copper pipe outer diameter Copper pipe protrusion for flaring B mm 1 0 1 5 With an R410A tool In the case of a rigid clutch type With a conventional tool B Ope...

Страница 181: ...perature and the pressure d If the pressure does not drop after the units is left for approximately one day the airtighteness is acceptable When the ambient temperature changes 1 C the pressure also c...

Страница 182: ...he other two drain holes with grommets 6 Electrical wiring Electrical installation work must be performed by an electrical installation service provider qualified by a power provider of the country El...

Страница 183: ...nduit and a voltage drop is 2 For an installation falling outside of these conditions please follow the internal cabling regulations Adapt it to the regulation in effect in each country L1 1 2 3 N Out...

Страница 184: ...ocation where it can sense the room temperature 2 Controlling multiple indoor units using a single remote controller Up to 16 indoor units can be controlled with a single remote controller a Run 3 wir...

Страница 185: ...ting Indoor unit fan speed setting Louver control setting 01 03 04 05 06 07 08 09 10 Function number A Default setting Hi CEILING SET FILTER SIGN SET POSITION EXTERNAL INPUT SET ROOM TEMP OFFSET FAN C...

Страница 186: ...l be displayed one by one Select a desired function 3 Press the SET button The screen display will be switched as follows SETTING Setting C ex AUTO RUN ON 4 Press either or button A list of Settings C...

Страница 187: ...ion setting process is completed Then the screen display will be switched to Function number A Function description B so if you want to continue to set another function repeat the stepa as explained a...

Страница 188: ...temperature is set at a value lower than the upper limit value The set temperature is transmitted b If the lower limit is set q When in an operating mode other than the heating mode if a temperature t...

Страница 189: ...SET OPERATION DATA 2 Press the SET button while OPERATION DATA is displayed 3 The display will change to I U No 00 blinking indication Select the indoor unit number you want to have data displayed wi...

Страница 190: ...est run method a A test run can be initiated from an outdoor unit by using SW5 3 and SW5 4 for on site setting b Switching SW5 3 to ON will start the compressor c The unit will start a cooling operati...

Страница 191: ...screw for holder Parts set Remote controller holder Quantity Quantity Name TIMER CHECK RUN TIMER CHECK RUN Receiver Check monitor Remote controller signal receiving part Backup switch Operation displa...

Страница 192: ...l installation Refer to 165 page 2 Remove the air return grille Refer to 166 page 3 Remove a corner panel located on the refrigerant pipe side 4 Remove three screws and detach the cover indicated as a...

Страница 193: ...her with other wiring laid on site into the indoor unit 4 Connect the wiring to the terminal block provided in the control box as follows X Red Y White Z Black 5 Attach the wireless kit to the panel a...

Страница 194: ...e controller is operated 1m above the floor under the ceilling that is 2 4m above the floor When illuminance doubles the receivable range drops to two thirds 3 Points for attention in connecting a plu...

Страница 195: ...tions or fixing could cause heating and fires Always use the enclosed parts and designated parts for the installation work parts Use of parts not designated by Mitsubishi could cause electric shocks o...

Страница 196: ...type or where light may directly contact the light detection surface 6 Places hidden by the indoor unit etc when looking from the wireless remote controller operation positions 7 Places subject to the...

Страница 197: ...through the hole on the lower case 4 Fit the lower case onto the bracket and fix the lower case to the bracket using the two installation holes shown above The other four holes are not used 5 Follow s...

Страница 198: ...ated at a height of 1 m from the floor with a ceiling height of 2 4 m The reception distance becomes 2 3 when the illuminance is double Conditions b When installed on wall Reception section illuminanc...

Страница 199: ...PACKAGED AIR CONDITIONER Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 P M P...