6.  Electrical work

6.1.  Electric wiring

 PKFY-P·VHM-E (Fig. 6-1)

Connection can be made without removing the front panel.

1. Open the front grille, remove the screw (1 piece), and remove the electrical 

parts cover. 

*  Electrical work can be conducted more effectively with the panel removed.

  When attaching the panel, check that the hooks 

N

 at five locations on the air 

outlet side are connected securely.

2. Securely connect each wire to the terminal board.

*  In consideration of servicing, provide extra length for each of the wires. 

*  Take care when using strand wires, because beards may cause the wiring to 

short out.

3. Install the parts that were removed back to their original condition. 

4. Fasten each of the wires with the clamp under the electrical parts box. 

Elactrical box cover

Fixing screw

Clamp 

Ground wire connection portion 

MA remote control terminal board: (1, 2) do not have polarity

Transmission terminal board: 

(M1, M2, S) do not have polarity

Power supply terminal board (L, N, Earth).

Lead 

Terminal screw 

Ground wire connection portion: Connect the ground wire in the direction illustrated in the 

diagram. 

Remote control cable 

Transmission cable 

Power supply cable

Hook

6..  Power supply wiring

•  Wiring size must comply with the applicable local and national code.

•  Power supply codes of appliance shall not be lighter than design 245 IEC 53 or 

227 IEC 53.

•  Install an earth line longer than other cables.

•  A switch with at least 3 mm, 1/8 inch contact separation in each pole shall be 

provided by the air conditioner installation.

Power cable size : more than 1.5 mm

2

 (3-core)

 Warning:

Never splice the power cable or the indoor-outdoor connection cable, 

otherwise it may result in a smoke, a fire or communication failure.

[Fig.6-]

Switch 16 A 

Overcurrent protection 16 A

Indoor unit

Total operating current be less than 16 A

Pull box

 Selecting non-fuse breaker (NF) or earth leakage breaker (NV).  

For breaker, means shall be provided to ensure disconnection of all active 

phase conductors of the supply.

6..  Types of control cables

1.  Wiring transmission cables

Types of transmission cable

Shielding wire CVVS or CPEVS

Cable diameter

More than 1.25 mm

2

Length

Less than 200 m

.  M-NET Remote control cables

Types of remote control cable Shielding wire MVVS
Cable diameter

More than 0.5 to 1.25 mm

2

Length

Add any portion in excess of 10 m to within the 

longest allowable transmission cable length 200 m.

.  MA Remote control cables

Types of remote control cable

2-core cable (unshielded)

Cable diameter

0.3 to 1.25 mm

2

Length

Less than 200 m

6.4.  Connecting remote controller, indoor and 

outdoor transmission cables (Fig. 6-)

•  Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire) The “S” 

on indoor unit TB5 is a shielding wire connection. For specifications about the 

connecting cables, refer to the outdoor unit installation manual.

•  Install a remote controller following the manual supplied with the remote controller.

•  Connect the remote controller’s transmission cable within 10 m using a 0.75 mm

2

 

core cable. If the distance is more than 10 m, use a 1.25 mm

2

 junction cable.

1

  MA Remote controller

•  Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-

polarized 2-wire)

•  DC 9 to 13 V between 1 and 2 (MA remote controller)

2

  M-NET Remote controller

•  Connect the “M1” and “M2” on indoor unit TB5 to a M-NET remote controller. 

(Nonpolarized 2-wire)

•  DC 24 to 30 V between M1 and M2 (M-NET remote controller)

3

  Wireless remote controller (When installing wireless signal receiver)

•  Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor 

con-troller board.

•  When more than two units are run under group control using wireless remote 

controller, connect TB15 each with the same number.

•  To change Pair No. setting, refer to installation manual attached to wireless re-

mote controller. (In the default setting of indoor unit and wireless remote control-

ler, Pair No. is 0.)  

Terminal block for indoor transmission cable 

Terminal block for outdoor transmission cable (M1(A), M2(B),  (S))

Remote controller 

Wireless signal receiver 

E

  Wireless remote controller

 PKFY-P·VHM-E

Fig. 6-1

12mm

55mm

KLM

C

M

H

L

K

D

G

F

E

A

B

Fig. 6-

Fig. 6-

A

A

C

TB5

TB15 TB5

TB15

S

M1 M2

S

M1 M2

B

TB3

M1 M2

2

1

C

2

1

1

A

A

C

TB5

TB5

S

M1M2

S

M1M2

C

B

TB3

M1M2

2

3

A

B

E

C

L N

TB2

TB5

TB15

S

1 2

M1 M2

N

L

N

M

J

RG79D840H01_en.indd   9

2012/10/25 (木)   午後 4:10:35

Содержание City Multi PKFY-P

Страница 1: ...DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUAL DE INSTALA O Para seguran a e utiliza o correctas lei...

Страница 2: ...y precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotati...

Страница 3: ...the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor PKFY P VHM E Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole 65 D...

Страница 4: ...e marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Referenc...

Страница 5: ...Move the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs...

Страница 6: ...pply refrigerating machine oil over the entire flare seat surface 4 Installing the refrigerant piping B C D Fig 4 1 4 1 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap...

Страница 7: ...ible 5 Wrap the pipe cover of the unit s liquid pipe and make sure that it covers the insulation material of the on site liquid pipe 6 The portion where the insulation material is joined is sealed by...

Страница 8: ...Fig 5 2 1 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pipe and pulling A Drain cap 2 Remove the drain hose Remove the drain hose by holding on to the...

Страница 9: ...ransmission cables Types of transmission cable Shielding wire CVVS or CPEVS Cable diameter More than 1 25 mm2 Length Less than 200 m 2 M NET Remote control cables Types of remote control cable Shieldi...

Страница 10: ...efore the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the...

Страница 11: ...related Products Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D840H01 The product at hand is...

Отзывы: