background image

4

GB

.  Installing the indoor unit

 PKFY-P·VHM-E

Fig. -6

B

A

C

E

D

...  Installing the wall mounting fixture

 Since the indoor unit weighs near 1 kg, selection of the mounting 

location requires thorough consideration. If the wall does not seem to be 

strong enough, reinforce it with boards or beams before installation.

 The mounting fixture must be secured at both ends and at the centre, if 

possible. Never fix it at a single spot or in any nonsymetrical way.

  (If possible, secure the fixture at all the positions marked with a bold 

arrow.)

 Warning:

If possible, secure the fixture at all positions indicated with a bold arrow.

 Caution:

•  The unit body must be mounted horizontally.

•  Fasten at the holes marked with 

 as shown by the arrows.

 PKFY-P·VHM-E (Fig. -4)

Min. 90 mm (617.6 mm or greater with optional drain pump installation)

Min. 200 mm

Min. 72 mm (142.5 mm or greater with left, rear left, or lower left piping, and optional drain 
pump installation)

Fixing screws (4 × 35) 

2

Level

Fasten a thread to the hole.

Place the level against the horizontal reference line of the mount board and mount so that it is 
level. Hang a weight from the thread and align with   EPK of the mount board to permit leveling.

Weight

Mount board 

1

..  When embedding pipes into the wall (Fig. -5)

•  The pipes are on the bottom left.

•  When the cooling pipe, drain pipes internal/external connection lines etc are to 

be embedded into the wall in advance, the extruding pipes etc, may have to be 

bent and have their length modified to suit the unit.

•  Use marking on the mount board as a reference when adjusting the length of the 

embedded cooling pipe.

•  During construction, give the length of the extruding pipes etc some leeway.

Mount board 

1

Reference marking for flare connection

Through hole

On-site piping

.4.  Preparing the indoor unit

*  Check beforehand because the preparatory work will differ depending on the 

exiting direction of the piping.

*  When bending the piping, bend gradually while maintaining the base of the 

piping exiting portion. (Abrupt bending will cause misshaping of the piping.)

Extraction and processing of the piping and wiring (Fig. -6)

1. Connection of indoor/outdoor wiring 

 See page. 8.

2. Wrap the felt tape 

3

 in the range of the refrigerant piping and drain hose which 

will be housed within the piping space of the indoor unit. 

•  Wrap the felt tape 

3

 securely from the base for each of the refrigerant piping 

and the drain hose. 

•  Overlap the felt tape 

3

 at one-half of the tape width. 

•  Fasten the end portion of the wrapping with vinyl tape.

Liquid pipe

Gas pipe

Indoor/outdoor connection cable

Drain hose

Felt tape 

3

3. Be careful that the drain hose is not raised, and that contact is not made with the 

indoor unit box body.  

Do not pull the drain hose forcefully because it might come out. 

Rear, right and lower piping (Fig. -7)

1) Be careful that the drain hose is not raised, and that contact is not made with 

the indoor unit box body.  

Arrange the drain hose at the underside of the piping and wrap it with felt 

tape 

3

2) Securely wrap the felt tape 

3

 starting from the base. (Overlap the felt tape at 

one-half of the tape width.) 

Cut off for right piping. 

Cut off for lower piping. 

Fig. -4

A

B

C

D

I

G

F

H

E

Fig. -5

B

A

C

D

Fig. -7

B

A

1)

2)

RG79D840H01_en.indd   4

2012/10/25 (木)   午後 4:10:30

Содержание City Multi PKFY-P

Страница 1: ...DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUAL DE INSTALA O Para seguran a e utiliza o correctas lei...

Страница 2: ...y precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotati...

Страница 3: ...the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor PKFY P VHM E Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole 65 D...

Страница 4: ...e marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Referenc...

Страница 5: ...Move the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs...

Страница 6: ...pply refrigerating machine oil over the entire flare seat surface 4 Installing the refrigerant piping B C D Fig 4 1 4 1 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap...

Страница 7: ...ible 5 Wrap the pipe cover of the unit s liquid pipe and make sure that it covers the insulation material of the on site liquid pipe 6 The portion where the insulation material is joined is sealed by...

Страница 8: ...Fig 5 2 1 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pipe and pulling A Drain cap 2 Remove the drain hose Remove the drain hose by holding on to the...

Страница 9: ...ransmission cables Types of transmission cable Shielding wire CVVS or CPEVS Cable diameter More than 1 25 mm2 Length Less than 200 m 2 M NET Remote control cables Types of remote control cable Shieldi...

Страница 10: ...efore the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the...

Страница 11: ...related Products Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D840H01 The product at hand is...

Отзывы: