5.  Drainage piping work

5.1.  Drainage piping work (Fig. 5-1)

•  Drain pipes should have an inclination of 1/100 or more.

•  For extension of the drain pipe, use a soft hose (inner dia. 15 mm) available on 

the market or hard vinyl chloride pipe (VP-16/O.D. ø22 PVC TUBE).  Make sure 

that there is no water leakage from the connections.

•  Do not put the drain piping directly in a drainage ditch where sulphuric gas may 

be generated.

•  When piping has been completed, check that water flows from the end of the 

drain pipe.

 Caution:

The drain pipe should be installed according to this Installation Manual to 

ensure correct drainage. Thermal insulation of the drain pipes is necessary 

to prevent condensation. If the drain pipes are not properly installed and 

insulated, condensation may drip on the ceiling, floor or other possessions.

Inclined downwards

Must be lower than outlet point

Water leakage

Trapped drainage

Air

Wavy

The end of drain pipe is under water.

Drainage ditch

I

  5 cm or less between the end of drain pipe and the ground.

Drain hose

Soft PVC hose (Inside diameter 15 mm)  
or  
Hard PVC pipe (VP-16) 
* Bond with PVC type adhesive 

Preparing left and left rear piping (Fig. 5-)

Remove the drain cap.

•  Remove the drain cap by holding the bit that sticks out at the end of the pipe and 

pulling.

Drain cap

Remove the drain hose.

•  Remove the drain hose by holding on to the base of the hose 

a

 (shown by 

arrow) and pulling towards yourself 

b

.

Insert the drain cap.

•  Insert a screwdriver etc into the hole at the end of the pipe and be sure to push 

to the base of the drain cap.

Insert the drain hose.

•  Push the drain hose until it is at the base of the drain box connection outlet.

•  Please make sure the drain hose hook is fastened properly over the extruding 

drain box connection outlet.

Hooks

  Storing in the piping space of the indoor unit (Fig. 5-)

*  When the drain hose will be routed indoors, be sure to wrap it with commercially 

available insulation. 

*  Gather the drain hose and the refrigerant piping together and wrap them with the 

supplied felt tape 

3

*  Overlap the felt tape 

3

 at one-half of the tape width. 

*  Fasten the end portion of the wrapping with vinyl tape, etc. 

Gas pipe

Liquid pipe

Drain hose

Indoor/outdoor connection wiring 

Felt tape 

3

  Check of drainage (Fig. 5-4)

1. Open the front grille and remove the filter. 

2. Facing the fins of the heat exchanger, slowly fill with water. 

3. After the drainage check, attach the filter and close the grille. 

A

B

C

E

D

C

F

C

G

H

I

A

A

1

3

Fig. 5-

Fig. 5-

Fig. 5-4

A

B

D

E

C

J

K

 PKFY-P·VHM-E

a

b

A

B

2

4

RG79D840H01_en.indd   8

2012/10/25 (木)   午後 4:10:33

Содержание City Multi PKFY-P

Страница 1: ...DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUAL DE INSTALA O Para seguran a e utiliza o correctas lei...

Страница 2: ...y precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotati...

Страница 3: ...the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor PKFY P VHM E Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole 65 D...

Страница 4: ...e marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Referenc...

Страница 5: ...Move the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs...

Страница 6: ...pply refrigerating machine oil over the entire flare seat surface 4 Installing the refrigerant piping B C D Fig 4 1 4 1 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap...

Страница 7: ...ible 5 Wrap the pipe cover of the unit s liquid pipe and make sure that it covers the insulation material of the on site liquid pipe 6 The portion where the insulation material is joined is sealed by...

Страница 8: ...Fig 5 2 1 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pipe and pulling A Drain cap 2 Remove the drain hose Remove the drain hose by holding on to the...

Страница 9: ...ransmission cables Types of transmission cable Shielding wire CVVS or CPEVS Cable diameter More than 1 25 mm2 Length Less than 200 m 2 M NET Remote control cables Types of remote control cable Shieldi...

Страница 10: ...efore the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the...

Страница 11: ...related Products Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D840H01 The product at hand is...

Отзывы: