6.5.  Setting addresses (Fig. 6-4)

(Be sure to operate with the main power turned OFF.)

•  There are two types of rotary switch setting available: setting addresses 1 to 9 

and over 10, and setting branch numbers.

1

 How to set addresses

  Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match SW11 

(for 1 to 9) with “3”.

2

 How to set branch numbers SW14 (Series R2 only)

  Match the indoor unit’s refrigerant pipe with the BC controller’s end connection 

number.

  Remain other than series R2 at “0”.

•  The rotary switches are all set to “0” when shipped from the factory. These 

switches can be used to set unit addresses and branch numbers at will.

•  The determination of indoor unit addresses varies with the system at site. Set 

them referring to the Data Book.

6.6.  Sensing room temperature with the built-in 

sensor in a remote controller

If you want to sense room temperature with the built-in sensor in a remote 

controller, set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-

8 as necessary also makes it possible to adjust the air flow at a time when the 

heating thermometer is OFF.

7.  Test run (Fig. 7-1)

Turn on the power at least 12 hours before the test run.

2

 Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

 Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

 Press the [Mode selection] button and switch to the cooling (or heating) mode. 

 

 Make sure that cold (or warm) wind is blown out.

5

 Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

 Check operation of the outdoor unit fan.

7

 Release test run by pressing the [ON/OFF] button. 

 Stop

8

 Register a telephone number.

  The telephone number of the repair shop, sales office, etc., to contact if an 

error occurs can be registered in the remote controller. The telephone number 

will be displayed when an error occurs. For registration procedures, refer to the 

operation manual for the indoor unit.

6.  Electrical work

Fig. 6-4

SW14

0

SW11

SW12

1 2 3 4 5 6 7 8 9 10

ON

OFF

SW1

SWA

CN82

CN43

3
2

1

F

E

D

C

B

A 9 8 7 6

5

4

3

2

1

5

0

4

9

3

8

2

7

1

6

5

0

4

9

3

8

2

7

1

6

ಽጘญ0Qࡍࠕ0Q

㧔$4#0%*0Q

㧔U&+)+6

㧔VJU&+)+6

A

Fig. 7-1

°C

°C

SIMPLE

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

TEST RUN

COOL, HEAT

A

F

C

E

D

B

M

I

HG

ON/OFF button

Test run display

Indoor temperature liquid 
line temperature display

ON/OFF lamp

Power display

Error code display

  Test run remaining time 

display

Set temperature button

Mode selection button

Fan speed button

TEST button

RG79D840H01_en.indd   10

2012/10/25 (木)   午後 4:10:35

Содержание City Multi PKFY-P

Страница 1: ...DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUAL DE INSTALA O Para seguran a e utiliza o correctas lei...

Страница 2: ...y precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotati...

Страница 3: ...the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor PKFY P VHM E Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole 65 D...

Страница 4: ...e marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Referenc...

Страница 5: ...Move the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs...

Страница 6: ...pply refrigerating machine oil over the entire flare seat surface 4 Installing the refrigerant piping B C D Fig 4 1 4 1 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap...

Страница 7: ...ible 5 Wrap the pipe cover of the unit s liquid pipe and make sure that it covers the insulation material of the on site liquid pipe 6 The portion where the insulation material is joined is sealed by...

Страница 8: ...Fig 5 2 1 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pipe and pulling A Drain cap 2 Remove the drain hose Remove the drain hose by holding on to the...

Страница 9: ...ransmission cables Types of transmission cable Shielding wire CVVS or CPEVS Cable diameter More than 1 25 mm2 Length Less than 200 m 2 M NET Remote control cables Types of remote control cable Shieldi...

Страница 10: ...efore the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the...

Страница 11: ...related Products Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D840H01 The product at hand is...

Отзывы: