5) The coaxial cable is wired in the following manner.
There is no program even if not wiring in order of the station number.
There is no program even if station how many become control station.
AJ71
QBR11
AJ71
QBR11
AJ71
QBR11
Terminal resistor
Control station
Station number 1
Normal station
Station number 2
Normal station
Station number 3
6) Install the coaxial cables at least 100 mm (3.94 in.) away from other power
cables and control cables.
7) Consider wiring using double-shielded coaxial cable in places that are
subject to large amounts of noise.
Double shielded coaxial cable
Mitsubishi Cable...5C-2V-CCY
Grounding
8) Do not pull any of the connected coaxial cables.
This will cause a faulty contact, cable disconnection, or damage to the
module.
9) Make sure to connect a terminal resistor to both terminal stations of the
coaxial bus type network system.
10)The F type connector has the possibility to extract a white oxide according
to the use enviroment.
However, there is no problem on the function because the oxide is not
generated in connected part.