8
No.
Name
Contents
Mode setting (factory setting at time of shipping: 0)
Mode
Name
Contents
0
On-line (automatic
double line existent)
Data link
(automatic double line existent)
1
Use not possible
-
2
Off-line
Placing local station in parallel condition
3
Forward loop
Data link system
Check of all forward loop side circuits is
executed.
4
Reverse loop
Data link system
Check of all reverse loop side circuits is
executed.
5
Test
between
stations
(master
stations)
6
Test
between
stations (sub master
stations)
By the mode which checks circuits
between 2 stations, execute the check
of the one which has a smaller number
as the master station and the other as
the sub master station.
7
Self back to back test By the module simplex, check the
hardware including the sending and
receiving communication circuit of the
transmission system and the cable.
8
Internal self back to
back test
By the unit simplex, check the hardware
including the sending and receiving
communication
circuit
of
the
transmission system.
9
Hardware test
Check the internal hardware of the
network module.
5)
*2
Mode setting switch
3
2
0
5
9
4
8
7
6
1
MODE
MODE
0:FOML TIME(A,R)
2:FOFFLINE
A to
F
Use prohibited
(Do not set the mode.)
Operation condition setting
(factory setting at the time of shipping: all off)
SW
Contents
OFF
ON
1
Network type
PC Network
Remote I/O network
2
Station type
Normal station/ Multiple
sub master
Control station/ parallel
sub masters
3
Use
parameters
Parameters in common Default Parameters
4
Number of
stations
OFF
ON
OFF
ON
5
[
Valid when
SW3 is ON
]
OFF
8
stati
ons
OFF
16
statio
ns
ON
32
statio
ns
ON
64
stati
ons
6
B/W number of
general point
OFF
ON
OFF
ON
7
[
Valid when
SW3 is ON
]
OFF
2k
point
s
OFF
4k
statio
ns
ON
6k
point
s
ON
8k
stati
ons
6)
*2
Conditions setting
switch
SW
1
2
3
4
5
6
7
8
OFF
PC
N.ST
PRM
ON
REM.
MNG
D.PRM
ST,SIZE
8,16,32,64
LB/LW SIZE
2,4,6,8k
OFF ON
SW
1
2
3
4
5
6
7
8
*3
*4
8
Use prohibited
(always off)