MITSUBISHI
ELECTRIC
2033C SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-2
MITSUBISHI ELECTRIC 2033C SERIES UPS
3.3 Installation Procedure
A) Note the load tolerance of the floor
Refer to Table 3.2 for list of UPS weights:
TABLE 3.2
List of UPS weights
UPS Capacity (kVA)
7.5
10
15
20
30
40
50
Weight (lb.)
562
562
816
816
1235
1082
1082
Note: 40kVA and 50kVA UPS have batteries external to module cabinet
Please refer to the remote battery supply installation manual.
B) Minimum clearance required for ventilation
Right side
1.0" (25 mm) (not required when sidecars are used)
Left side
1.0" (25 mm) (not required when sidecars are used)
Back side
7.8" (200 mm)
Top side
39.4" (1000 mm)
C) Space requirement for routine maintenance
Allow for the following space at the time of installation.
Front
39.4" (1000 mm)
Sides
1.0" (25 mm)
Rear
7.8" (200 mm)
D) Battery
Please refer to the following when installing and maintaining batteries:
1. Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
2. When installing or replacing batteries, install or replace with the same number
and type per Table 3.3
TABLE 3.3
Type and number of battery
Type
Manufacturer
Number
7.5kVA,10kVA PM12-7.2
NP7-12
Power Battery Inc.
Yuasa Corp.
30
15kVA,20kVA PM12-18
NP18-12B
Power Battery Inc.
Yuasa Corp.
30
30kVA PM12-18
NP18-12B
NP18-12BFR
Power Battery Inc.
Yuasa Corp.
Yuasa Corp.
30
40kVA,50kVA