-
131
-
'19 • SCM-SM-276
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E8
Heating overload operation
Keeps flashing
1
-
time flash
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
(2)
Is the air filter clogged?
Is the
indoor heat exchanger
temperature sensor
connection OK?
Are the
characteristics of indoor
heat exchanger temperature
sensor OK?
NO
Check the error data with the
remote control.
YES
Is the unit
operating in the state of
heating overload?
Note (1) Judge if it is in the state of overload or not as follows.
࣭
Is there any short-circuit of air?
࣭
Isn’t there any fouling or clogging on the indoor heat exchanger?
࣭
Is the outdoor fan control normal?
࣭
Isn't the room and outdoor air temperature too high?
Note (2) For characteristics of indoor heat exchanger temperature sensor,
see the error display E6.
YES
NO
YES
NO
Error stop
Reset
Indoor heat exchanger temperature (°C)
56
63
Wash.
Defective indoor heat
exchanger temperature
sensor connector
➞
Correct.
Defective indoor heat
exchanger temperature
sensor.
Check refrigerant system.
Adjust.
2. Error detection method
Indoor heat exchanger
temperature sensor (Thi-R1, R2,
R3)
3. Condition of error displayed
When it is detected 5 times
within 60 minutes from initial
detection or when the overload
condition is detected for 6
minutes continuously.
4. Presumable cause
• Clogged air filter
• Defective indoor heat
exchanger temperature sensor
connector
• Defective indoor heat
exchanger temperature sensor
• Anomalous refrigerant system
Note:
During heating operation; After starting compressor, compressor rotation speed is decreased by detecting indoor heat
exchanger temperature (Thi-R) in order to control high pressure.
Содержание SRK60ZSX-W
Страница 2: ......