<<Reference>> How to initialize the gateway's IP address
If you do not know the gateway's IP address setting, you can reset the IP address setting to the factory
default by following the procedure described below.
(1) Turn the gateway off.
(2) Connect (short-circuit) the terminal (DI3 terminal) used to initialize the gateway's IP address using a
harness, etc.
(3) Turn the gateway on, and wait for about two minutes.
Then, the gateway's IP address setting is reset to the factory default.
[Gateway network settings at factory default]
IP address:
192.168.0.110
Subnet mask:
255.255.255.0
Default gateway: No setting
(4) After completing the procedure, turn the gateway off again, remove the harness connected in step (2),
and then turn the power on again.
If you leave the harness attached, unintended initialization of the IP address settings may be performed.
Connect both terminals using
a harness, etc.