Follow step (3-2) to log in to the gateway setting screen. Start this procedure when two or more minutes
have elapsed after setting the gateway in step (3-3). The connection may fail because the gateway is
being rebooted.
After login, click [CGW Status] from the menu on the left side of the screen. By referring to the displayed
details, check the connection status on the remote terminal communication side (Remote Terminal Status).
According to Remote Terminal Status, execute the following:
[OK]
: Confirm whether the Remote terminal board communication wire is securely connected
to the heat source unit for which the [×] icon is displayed on the M-ACCESS screen.
[NG]
: Confirm whether the Remote terminal board communication wire is securely connected
to the gateway.
[--]
: Confirm that the gateway is connected to the network and that the activation is completed,
then reboot the gateway.