Model FD-PAC / FDC100VS
Model
Technical specifications
Control kit
Outdoor unit
FD-PAC FDC100VS
Nominal coolingcapacity
(1)
10000 (6100 ~ 11200)
Nominal heating capacity
(1)
11200 (5600 ~ 12500)
Power source
1 fase, 220/230/240V, 50Hz, N, PE
Opera
tio
n da
ta (
3
)
Cooling power consumption
2,85/2,85
Running current (cooling)
12,5/13,1
Power factor (cooling)
99/99
Heating power consumption
2,97/2,97
Running current (heating)
13,0/13,6
Power factor (heating)
99/99
Inrush current
5,0
Moise level
-
50
Exterior dimensions (height x width x depth)
400 x 300 x 120
845 x 970 x 370
Nett weight
8
74
Compressor type
-
RM-B5125MD11
Compressor motor
-
2,4
Refrigerant oil
-
0,9
(M-MA68)
Carterheating
-
20 (carterheating)
Starting method
-
Direct
Heat exchanger
-
Air (straight fin)
Defrost control
Microprocessor controller de-icer
Refrigerant
R410A
Refrigerant amount
-
3,8 (pre-charged to 30 mtr)
Refrigerant expansion
Elektronic expansion valve
Air handling equipment, fan type
-
Axiaal ventilator x 1
Motor
-
120 x 1
Air flow
Min.1600
4500
Air entrance temperature cooling min./ max.
16 / 32
-
Air entrance temperature heating min./ max.
10 / 32
-
Water entrance temperature cooling min./
max.
16 / 32
-
Water entrance temperature heating min./
max.
10 / 32
-
Safety equipment
-
Internal thermostat for fanmotor,
anomalous discharge temperature
protection
Refrigerant piping
Liquid line 10mm, Gas line 16mm
Piping size
Liquid line 9,52 mm (3/8”), Gas line 15,88mm (5/8”)
Connecting method
Flare piping
Isolation
Necessary (liquid and gasline)
Drain hose
-
Drain pan3x Ø20 mm
Accessoires
-
Paneel (separate packing)
-
Optional accessoires
-
-
Remote controller
RC-E3
-
Notes
(1) The data are measured at the following conditions.
Item
Mode
Indoor temperature
Outdoor temperature
standard
d.b. temp.
w.b. temp.
d.b. temp.
w.b. temp.
Cooling 27°C
19°C
35°C
24°C
ISO-T1, JIS
B8616
Heating 20°C - 7°C 6°C
(2) This airconditioner is manufactured and tested in conformity with the following standards: ISO-T1”unitary
airconditioner”.
(3) The operation data indicate when the airconditioner is operated at 230V, 50hz.
(4) Values in ( ~ ) show the minimum to maximum range.
(5) Adjustment of the estimated output via DIP switch (see page 16).
-
7
-
Содержание FD-PAC
Страница 1: ...Technical manual Version 01 10 FD PAC Controlkit R410A FDC71 250V FD PAC ...
Страница 15: ...3 3 Lay out plate heat exchanger ...
Страница 16: ...3 4 Lay out heat exchanger ...
Страница 17: ...3 4 Lay out wiring diagram ...
Страница 18: ...4 Troubleshooting ...
Страница 19: ... 19 ...
Страница 20: ... 20 ...
Страница 21: ... 21 ...
Страница 22: ... 22 ...