45˚± 2˚

A

C

D

B

ø

A

R1/64 to R1/32

(inch)

A

 Liquid pipe

B

 Gas pipe

C

 Insulation

D

 Taping

A

 Flare cutting dimensions

B

 Flare nut tightening torque

90˚± 0.5˚

Fig. 4-5

5

4. Refrigerant piping work

4.3. Connecting pipes (Fig. 4-4, Fig. 4-5)

•  Fasten flare nut with a torque wrench as specified in the table (refer to 4.2.).

•  When fastened too tight, flare nut may eventually break and cause refrigerant leak

-

age.  

[Fig. 4-5]

• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening 

flare nut. 

A

 

•  Use 2 wrenches to tighten piping connections. 

B

•  Use  leak  detector  or  soapy  water  to  check  for  gas  leaks  after  connections  are 

completed. 

•  Apply refrigerant oil over the entire flare seat surface. 

C

•  Use the flare nuts for the following pipe size. 

D

NTXSKS09A112A

NTXSKS12A112A

NTXSKS15A112A

Gas side

Pipe size inch (mm)

3/8 (9.52)

1/2 (12.7)

Liquid side

Pipe size inch (mm)

1/4 (6.35)

1/4 (6.35)

*1: The flare nut is attached to its pipe.

*2: The flare nut is in the outdoor unit accessory.

   Do not use the flare nuts other than the attachment. If it is used, a gas leakage or 

even a pipe extraction may occur.

•  Refrigerant pipe bending radius must be 4 in. (100 mm) or more.

•  Make sure the pipes do not contact the compressor. Abnormal noise or vibration 

may result.

1

 Pipes must be connected starting from the indoor unit.

Flare nuts must be tightened with a torque wrench.

2

 Flare the liquid pipes and gas pipes and apply a thin layer of refrigerant oil

(Applied on site).

 Warning:

Be careful of flying flare nut. (Internally pressurized)

Remove the flare nuts as follows:

1. Loosen the nut until you hear a hissing noise.

2. Do not remove the nut until the gas has been completely released (i.e., hiss

-

ing noise stops)

3. 

Check that the gas has been completely released, and then remove the nut.

A

 (Fig. 4-5)

Pipe diameter

Flare dimensions

øA dimensions

inch

(mm)

inch

(mm)

1/4”

(6.35)

11/32 - 23/64

(8.7 - 9.1)

3/8”

(9.52)

1/2 - 33/64

(12.8 - 13.2)

1/2”

(12.7)

41/64 - 21/32

(16.2 - 16.6)

A

B

C

D

Fig. 4-4

4.4. Purging procedures and leak test

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe.

2) Connect gauge manifold valve and vacuum pump to service port of stop valve on 

the gas pipe side of the outdoor unit.

3) Run the vacuum pump 15 minutes or more.

4) Check the vacuum with the gauge manifold valve, then close it and shut off the 

vacuum pump.

5) Leave as it is for one or two minutes. Make sure pointer gauge manifold valve 

remains in the same position. Confirm that pressure gauge shows -0.101 MPa 

[Gauge] (-30 in.Hg [-760 mmHg]).

6) Quickly remove gauge manifold valve from service port of stop valve.

7) After refrigerant pipes are connected and evacuated, fully open all stop valves on 

both sides of gas pipe and liquid pipe. Operating the unit without fully opening the 

valves lowers the performance and causes problems.

8) Refer to 4.1. Refrigerant pipe, and charge the prescribed amount of refrigerant if 

needed. Be sure to charge slowly with liquid refrigerant. Otherwise, composition 

of the refrigerant in the system may be changed and affect performance of the air 

conditioner.

9) Tighten cap of service port.

10) Conduct a leak test.

A

When attaching the control valve to the 

service port, valve core may deform or 

loosen if excess pressure is applied. 

This may cause gas leak.

When attaching the control valve to the 

service port, make sure that the valve 

core is in closed position, and then 

tighten part A. Do not tighten part A 

or turn the body when valve core is in 

open position.

Precautions when using the control valve

*4 to 5 turns

*Close

*Open

Stop valve for 

LIQUID

Adapter for 

preventing the 

back flow

Stop valve for 

GAS

Handle 

Low

Handle High

Charge hose

Service port

Control valve

Open

Close

Body

Charge hose 

(for R410A)

Vacuum pump (or the vacuum 

pump with the function to 

prevent the back flow)

Hexagonal 

wrench

Service port cap 

(Torque 13.7 to 17.7 

N•m, 140 to 180 

kgf•cm)

Compound pressure gauge 

(for R410A)

Pressure gauge 

(for R410A)

Gauge manifold valve 

(for R410A)

–0.101 MPa 

(–30 in.Hg 

[–760 mmHg])

Stop valve cap 

(Torque 19.6 to 

29.4 N•m, 200 to 

300 kgf•cm)

BH79A499H01_EN.indd   5

2018/09/04   16:49:03

Содержание TRANE NTXSKS09A112A

Страница 1: ...le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Air Conditioners NTXSKS09A112A NTXSKS12A112A NTXSKS15A112A POUR L INSTALLATEUR PARA EL INSTALADOR FOR INSTALLER Français Español En...

Страница 2: ...ould cause a fire or an electric shock When installing or relocating the unit make sure that no substance other than the specified refrigerant R410A enters the refrigerant circuit Any foreign substances in the refrigerant circuit can cause abnormal pressure rise or an explosion Do not discharge the refrigerant into the atmosphere Check that the refrig erant gas does not leak after installation has...

Страница 3: ...here there is high frequency or wireless equipment The outdoor unit produces condensate during the heating operation Select the in stallation place to ensure to prevent the outdoor unit and or the grounds from being wet by drain water or damaged by frozen drain water 2 Selecting the installation location When the piping is to be attached to a wall containing metals tin plated or metal netting use ...

Страница 4: ... of specified thickness table on the above Excessive insulation may cause incorrect installation of the indoor unit and too little insulation may cause condensate to form The unit has flared connections on both indoor and outdoor sides Remove the valve cover from the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Be careful not to crush or ove...

Страница 5: ... D Fig 4 4 4 4 Purging procedures and leak test 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit 3 Run the vacuum pump 15 minutes or more 4 Check the vacuum with the gauge manifold valve then close it and shut off the vacuum pump 5 Leave as it is for...

Страница 6: ...ure Be careful not to contact connecting cable with piping Caution Use care not to make miswiring Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the indoor unit securely If it is not attached correctly it could result in a fire or an electric shock due to dust ...

Страница 7: ...local and national code 2 Use copper supply wires 3 Use wires rated 600V or more for the power supply cables and the indoor outdoor unit connecting cables 4 Install an earth longer than other cables 6 1 Gas charge Fig 6 1 1 Connect gas cylinder to the service port of stop valve 3 way 2 Execute air purge of the pipe or hose coming from refrigerant gas cylinder 3 Replenish specified amount of refrig...

Страница 8: ...rigérant spécifié R410A ne pénètre dans le cir cuit de réfrigération La présence d une substance étrangère dans le circuit de réfrigération peut pro voquer une augmentation anormale de la pression voire une explosion Ne libérez pas le réfrigérant dans l atmosphère Vérifiez l absence de fuites de gaz réfrigérant une fois l installation terminée En cas de fuite de réfrigé rant pendant l installation...

Страница 9: ... sulfurique source thermale En présence d équipements haute fréquence ou sans fil L unité extérieure produit de la condensation lors du mode de chauffage Choisir l endroit où le climatiseur sera monté de façon à éviter à l unité extérieure et ou aux sols d être mouillés par les condensats ou endommagés par le gel des condensats 2 Choisir l emplacement de l installation NTXSKS09A112A NTXSKS12A112A ...

Страница 10: ...urs un matériau d isolation de l épaisseur spécifiée tableau à droite Une isolation trop épaisse peut être à l origine d une installation incorrecte de l unité interne une isolation trop fine peut provoquer la formation de condensation L unité comporte des raccordements évasés sur les faces intérieure et extérieure Retirez le couvercle de vanne de l unité externe et raccordez le tuyau Les conduite...

Страница 11: ...es de purge et test de contrôle des fuites 1 Retirez le bouchon de l ouverture de service du robinet d arrêt du côté du tuyau de gaz de l unité externe 2 Raccordez la vanne du collecteur à jauge et la pompe à vide à l ouverture de service du robinet d arrêt du côté du tuyau de gaz de l unité externe 3 Faites fonctionner la pompe à vide pendant 15 minutes minimum 4 Contrôlez la dépression ainsi obt...

Страница 12: ...on Faites attention de brancher les fils correctement Serrer fermement les vis des bornes pour les empêcher de se desserrer Puis tirer légèrement sur les fils pour vous assurer qu ils ne bougent pas Avertissement Veiller à visser correctement le panneau de service à l appareil extérieur Si le panneau de service n est pas bien installé de l eau des poussières etc pourraient pénétrer à l intérieur d...

Страница 13: ...ucher les bornes S1 S2 et S3 lorsque l alimentation est sous tension S il faut placer un sectionneur entre les appareils extérieur et intérieur en utiliser un de type tripolaire 6 Entretien 6 1 Charge de Gaz Fig 6 1 1 Raccorder le tuyau de gaz au port de service de la vanne d arrêt à 3 voies 2 Purger l air du tuyau raccordé au tuyau de gaz réfrigérant 3 Ajouter la quantité spécifiée de réfrigérant...

Страница 14: ...l circuito de refrigeración puede provocar una elevación anómala de la presión o una explosión No descargue el refrigerante en el ambiente Una vez acabada la instala ción compruebe que no haya fugas de gas refrigerante Si se producen fugas de refrigerante durante la instalación ventile la habitación Si el refrigerante entra en contacto con una llama podría generarse gas nocivo Si se produjeran pér...

Страница 15: ...haya gas sulfúrico como en zonas de baños termales Donde haya algún equipo inalámbrico o de alta frecuencia La unidad exterior provoca condensación durante la función de calefacción Selec cione un lugar para la instalación en el que la unidad exterior y las tomas de tierra no se humedezcan con agua de drenaje ni se dañen debido a la congelación de este agua de drenaje 2 Selección del lugar de inst...

Страница 16: ... tabla de la derecha El uso excesivo de aislante puede causar una instalación incorrecta de la unidad interior y el uso de una cantidad insuficiente de aislante puede provocar la condensación Las unidad tiene conexiones abocinadas en los lados interior y exterior Retire la tapa de la válvula de la unidad exterior y a continuación conecte la tubería Las tuberías de refrigerante se emplean para cone...

Страница 17: ...ón situada en el lado de la tubería de gas de la unidad exterior 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en funcionamiento la bomba de vacío durante 15 minutos o más 4 Compruebe el vacío con la válvula colectora de manómetro cierre luego esta válvula y detenga la ...

Страница 18: ...gún las medidas que aparecen en la figura Tenga cuidado de que el cable de conexión no haga contacto con los tubos Cuidado Asegúrese de no realizar un mal cableado Apriete firmemente los tornillos de la terminal para evitar que se aflojen Tras apretarlos tire ligeramente de los cables para confirmar que no se muevan Atención Asegúrese de fijar firmemente el panel de servicio de la unidad exterior ...

Страница 19: ...para los cables de la fuente de alimentación y los cables de conexión de las unidades inte rior exterior 4 Instale un cable de toma de tierra más largo que el resto de los cables 6 1 Carga de gas Fig 6 1 1 Conecte el cilindro de gas a la abertura de servicio de la válvula de parada de 3 vías 2 Purgue el aire del tubo o conducto procedente del cilindro de gas refrigerante 3 Vuelva a llenar la canti...

Страница 20: ...his manual before handing it to the customer HEAD OFFICE 1340 SATELLITE BOULEVARD SUWANEE GA 30024 USA MITSUBISHI ELECTRIC TRANE HVAC US LLC Printed in Mexico BH79A499H01_cover4 indd 20 2018 08 31 14 37 18 Publication No DL SVN007A XX Published Nov 2018 BH79A499H01 ...

Отзывы: