24
OCH699A
L Check of inverter P.C. board
Check the outdoor fan motor.
(Refer to "10-5. . Check of outdoor fan motor".)
Is the fuse (F901) blown on the inverter
P.C. board?
Check the connection of the connectors
(CN931, CN932) of the outdoor fan motor.
If the connection is poor, make it correct.
Operate the outdoor unit by starting
EMERGENCY OPERATION.
Check the LED indication on the in-
verter P.C. board.
Does the LED blink 10 times?
Replace the inverter P.C. board.
Check the corresponding parts
following LED indication.
(Refer to "10-3. HOW TO PR-
CEED "SELF-DIAGNOSIS"".)
Yes
No
Yes
(10-time blink)
No