background image

11

OCH699A

Representative matching

PEAD-A09AA7

PEAD-A12AA7

PEAD-A15AA7

Item

Unit

Cooling

Heating

Cooling

Heating

Cooling

Heating

Total

Capacity

BTU/h

9000

12000

12000

15000

15000

18000

SHF

-

0.9

0.9

0.9

Input

kW

0.72

0.9

0.93

1.16

1.15

1.35

Electrical circuit

Indoor unit

PEAD-A09AA7

PEAD-A12AA7

PEAD-A15AA7

Power supply (V, phase, Hz)

230, 1, 60

Input

kW

0.07

0.05

0.09

0.07

0.11

0.09

Current

A

0.54

0.43

0.67

0.56

0.95

0.84

Outdoor unit

SUZ-KA09NA(H)2

SUZ-KA12NA(H)2

SUZ-KA15NA(H)2

Power supply (V, phase, Hz)

230, 1, 60

Input

kW

0.65

0.85

0.84

1.09

1.04

1.26

Current

A

2.55

3.48

3.36

4.45

4.01

5.01

Refrigerant circuit

Condensing pressure

PSIG

358

380

383

374

412

343

Suction pressure

PSIG

133

111

153

93

144

97

Discharge temperature

°F

157

162

167

175

165

167

Condensing temperature

°F

108

113

113

111

119

105

Suction temperature

°F

57

38

49

40

57

38

Ref. pipe length

ft

25

Refrigerant charge (R410A)

-

1.05

1.15

Indoor  unit

Intake air temperature

DB

°F

80

70

80

70

80

70

WB

°F

67

60

67

60

67

60

Discharge air temperature

DB

°F

58

103

59

100

58

99

Outdoor

 

unit Intake air temperature

DB

°F

95

47

95

47

95

47

WB

°F

75

43

75

43

75

43

Representative matching

SVZ-KP12NA

MLZ-KP09NA

MLZ-KP12NA

Item

Unit

Cooling

Heating

Cooling

Heating

Cooling

Heating

Total

Capacity

BTU/h

12000

11000

9000

12000

12000

15400

SHF

-

0.89

0.82

0.74

Input

kW

0.94

1.24

0.71

0.86

0.96

1.3

Electrical circuit

Indoor unit

SVZ-KP12NA

MLZ-KP09NA

MLZ-KP12NA

Power supply (V, phase, Hz)

230, 1, 60

230, 1, 60

Input

kW

0.1

0.04

Current

A

0.9

0.3

Outdoor unit

SUZ-KA12NA(H)2

SUZ-KA09NA(H)2

SUZ-KA12NA(H)2

Power supply (V, phase, Hz)

230, 1, 60

230, 1, 60

Input

kW

0.84

1.11

0.67

0.82

0.92

1.26

Current

A

3.18

4.33

2.77

3.4

3.92

5.32

Refrigerant circuit

Condensing pressure

PSIG

384

374

355

344

372

437

Suction pressure

PSIG

153

96

130

108

137

98

Discharge temperature

°F

167

170

158

162

165

172

Condensing temperature

°F

113

111

108

105

96

109

Suction temperature

°F

70

41

56

41

65

37

Ref. pipe length

ft

25

 25

Refrigerant charge (R410A)

-

1.05

1.05

1.15

Indoor  unit

Intake air temperature

DB

°F

80

70

80

70

80

70

WB

°F

67

60

67

60

67

60

Discharge air temperature

DB

°F

59

100

57

104

57

111

Outdoor

 

unit Intake air temperature

DB

°F

95

47

95

47

95

47

WB

°F

75

43

75

43

75

43

Содержание SUZ-KA09NA2

Страница 1: ...SUZ KA12NA2 MX SUZ KA12NAH2 MX SUZ KA15NA2 MX SUZ KA15NAH2 MX SUZ KA09NA H 2 MX Air outlet Drain outlet Piping Drain hose Air inlet back and side CONTENTS 1 COMBINATION OF INDOOR AND OUTDOOR UNITS 2 2 PART NAMES AND FUNCTIONS 2 3 SPECIFICATION 3 4 OUTLINES AND DIMENSIONS 4 5 WIRING DIAGRAM 5 6 REFRIGERANT SYSTEM DIAGRAM 9 7 DATA 10 8 ACTUATOR CONTROL 12 9 SERVICE FUNCTION 13 10 TROUBLESHOOTING 13 ...

Страница 2: ...ef Heat pump without electric heater KA15 NA H 2 MX HWE08020 KA12 NA H 2 MX KA09 NA H 2 MX SLZ KF09 12 15NA TH SEZ KD09 12 15NA4R1 TH PEAD A09 12 15AA7 MX SVZ KP12NA MX MLZ KP09 12NA U1 OCH699 HWE1608A OBH802 Air outlet Drain outlet Piping Drain hose Air inlet back and side SUZ KA09NA H 2 MX SUZ KA12NA H 2 MX SUZ KA15NA H 2 MX 0 0 0 0 0 0 0 0 0 0 0 0 ...

Страница 3: ... 21 5 8 Weight Ib 81 External finish Munsell 3Y 7 8 1 1 Control voltage by built in transformer VDC 12 24 Refrigerant piping Not supplied Refrigerant pipe size Min wall thickness Liquid in 1 4 0 0315 Gas in 3 8 0 0315 1 2 0 0315 Connection method Indoor Flared Outdoor Flared Between the indoor outdoor units Height difference ft 40 Piping length ft 65 Refrigerant charge R410A 2 lb 5 oz 2 lb 9 oz No...

Страница 4: ...he unit are clear holes KA09 12 15NA KA09 12 15NAH REQUIRED SPACE Liquid refrigerant pipe joint Refrigerant pipe flared Ø 1 4 Gas refrigerant pipe joint Refrigerant pipe flared Ø 3 8 KA09 12 Ø 1 2 KA15 4 in 100 mm or more 14 in 350 mm or more 8 in 200 mm or more 2 4 in 100 mm or more Unit inch mm SUZ KA09NA H 2 MX SUZ KA12NA H 2 MX SUZ KA15NA H 2 MX 2 3 4 ...

Страница 5: ...V MF FAN MOTOR TB DEFROST HEATER OPTION PARTS PTC64 PTC65 CIRCUIT PROTECTION T801 POWER MODULE RT61 DEFROST THERMISTOR X63 X64 X66 POWER DEVICE RT62 DISCHARGE TEMP THERMISTOR 2184 LED RT64 FIN TEMP THERMISTOR 26H EXPANSION VALVE COIL RT65 AMBIENT TEMP THERMISTOR NAME OUTDOOR HEAT EXCHANGER TEMP THERMISTOR TERMINAL BLOCK TRANSFORMER RELAY REVERSING VALVE COIL HEATER PROTECTOR OPTION PARTS LEV NOTES...

Страница 6: ...N VALVE COIL RT65 1fQQl 2 I RT64 3 1 1 MF NAME SYMBOL REACTOR RT68 COMPRESSOR FAN MOTOR TB CIRCUIT PROTECTION T801 DEFROST THERMISTOR X63 X64 X66 DISCHARGE TEMP THERMISTOR 21S4 FIN TEMP THERMISTOR 26H AMBIENT TEMP THERMISTOR NAME OUTDOOR HEAT EXCHANGER TEMP THERMISTOR TERMINAL BLOCK TRANSFORMER RELAY REVERSING VALVE COIL HEATER PROTECTOR RD LEV NOTES 1 About the indoor side electric wiring refer t...

Страница 7: ... POWER MODULE RT61 DEFROST THERMISTOR X63 X64 X66 POWER DEVICE RT62 DISCHARGE TEMP THERMISTOR 21S4 LED RT64 FIN TEMP THERMISTOR 26H EXPANSION VALVE COIL RT65 AMBIENT TEMP THERMISTOR IC802 r 7 __ 1 INVERTER P C BOARD LD61 LD E1 fl LED NAME OUTDOOR HEAT EXCHANGER TEMP THERMISTOR TERMINAL BLOCK TRANSFORMER RELAY REVERSING VALVE COIL HEATER PROTECTORIOPTION PARTS YE LD71 PTC65 LEV NOTES RD 1 About the...

Страница 8: ...MISTOR X63 X64 X66 DISCHARGE TEMP THERMISTOR 21S4 FIN TEMP THERMISTOR 26H AMBIENTTEMP THERMISTOR L61 BN WH r 1 INVERTER P C BOARD LD61 f YE PTC64 NAME OUTDOOR HEAT EXCHANGER TEMP THERMISTOR TERMINAL BLOCK TRANSFORMER RELAY REVERSING VALVE COIL HEATER PROTECTOR LED LD71 PTC65 LEV NOTES RD 1 About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing 2 Use co...

Страница 9: ...at insulator ø1 2 ø12 7 KA15 Stop valve with service port Capillary tube O D 0 157 I D 0 094 9 7 16 ø4 0 ø2 4 240 KA12 15 Muffler SUZ KA09NA H 2 MX SUZ KA12NA H 2 MX SUZ KA15NA H 2 MX Max Length A Max Height difference B Indoor unit Outdoor unit MAX REFRIGERANT PIPING LENGTH and MAX HEIGHT DIFFERENCE Model Refrigerant piping ft Piping size O D in Max Length A Max Height difference B Gas Liquid SUZ...

Страница 10: ...air temperature DB F 59 104 57 105 57 101 Outdoor unit Intake air temperature DB F 95 47 95 47 95 47 WB F 75 43 75 43 75 43 Representative matching SLZ KF09NA SLZ KF12NA SLZ KF15NA Item Unit Cooling Heating Cooling Heating Cooling Heating Total Capacity BTU h 9000 11000 12000 13000 14100 18000 SHF 0 87 0 74 0 75 Input kW 0 67 0 81 0 9 1 31 1 15 1 73 Electrical circuit Indoor unit SLZ KF09NA SLZ KF...

Страница 11: ...mperature DB F 58 103 59 100 58 99 Outdoor unit Intake air temperature DB F 95 47 95 47 95 47 WB F 75 43 75 43 75 43 Representative matching SVZ KP12NA MLZ KP09NA MLZ KP12NA Item Unit Cooling Heating Cooling Heating Cooling Heating Total Capacity BTU h 12000 11000 9000 12000 12000 15400 SHF 0 89 0 82 0 74 Input kW 0 94 1 24 0 71 0 86 0 96 1 3 Electrical circuit Indoor unit SVZ KP12NA MLZ KP09NA ML...

Страница 12: ...tor R V coil ON OFF ON OFF COOL 5 seconds HEAT 5 seconds 8 ACTUATOR CONTROL 8 3 RELATION BETWEEN MAIN SENSOR AND ACTUATOR Sensor Purpose Actuator Compressor LEV Outdoor fan motor R V coil Indoor fan motor Defrost heater Discharge temperature thermistor Protection Indoor coil temperature thermistor Cooling Coil frost prevention Heating High pressure protec tion Defrost thermistor Heating Defrosting...

Страница 13: ...S ON TROUBLESHOOTING 1 Before troubleshooting check the following 1 Check the power supply voltage 2 Check the indoor outdoor connecting wire for miswiring 2 Take care of the following during servicing 1 Before servicing the air conditioner be sure to turn OFF the main unit first with the remote controller and turn off the breaker 2 Be sure to turn OFF the power supply before removing the front pa...

Страница 14: ... thermistor frequency lowers How to check in 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 A 10 2 TROUBLE SHOOTING CHECK TABLE SUZ KA09NA H 2 MX SUZ KA12NA H 2 MX SUZ KA15NA H 2 MX No Symptoms LED indication check code Abnormal point Condition Condition Remedy 1 Outdoor unit does not operate 1 time blink every 2 5 seconds UP Outdoor power system Overcurrent protection cut out operates 3 consecut...

Страница 15: ...ory Ref address Cancel OK F1 F2 F3 F4 Self check Return Ref address Error history deleted 2 With the F1 or F2 button enter the refrigerant address and press the button Select Self check with the F1 or F2 button and press the button 1 Select Service from the Main menu and press the button 3 Check code unit number attribute will appear will appear if no error history is available 4 Resetting the err...

Страница 16: ...emits an intermittent buzzer sound the operation light blinks and the check code is output It takes 3 seconds at most for check code to appear 4 Point the remote controller at the sensor on the indoor unit and press the ON OFF button The check mode is cancelled Malfunction diagnosis method at maintenance service 10 3 2 Self diagnosis Wireless remote controller In case of trouble during operation W...

Страница 17: ...gnal receiving error Errors detected by unit other than indoor unit outdoor unit etc Symptom 1 Indoor outdoor unit communication error 2 Transmitting error Outdoor unit 3 Open short of outdoor unit thermistors UP U3 U4 Others 14 Other errors Refer to the technical manual for the outdoor unit 12 14 Fb FB PL Indoor unit control system error memory error etc E0 E3 E1 E2 Remote controller control boar...

Страница 18: ...Inverter P C board in 10 6 TEST POINT DIAGRAM AND VOLTAGE for the chart of thermistor Compressor Measure the resistance between terminals with a tester Temperature 14 104 F 10 40 C Normal Ω KA09 KA12 KA15 U V U W V W 1 26 1 72 1 60 2 17 0 82 1 11 Outdoor fan motor Measure the resistance between lead wires with a tester Temperature 14 104 F 10 40 C Color of lead wire Normal Ω KA09 12 15 RD BK BK WH...

Страница 19: ...to the COOL or HEAT mode 3 Compressor starts at rated frequency in COOL mode or 58 Hz in HEAT mode 4 Indoor fan operates at High speed 5 To cancel test run operation press the ON OFF button on remote controller Measurement point at 3 points BK U WH V BK U RD W WH V RD W NOTE 1 Output voltage varies according to power supply voltage 2 Measure the voltage by analog type tester 3 During this check LE...

Страница 20: ...ter P C board and balance of them See 10 5 3 Direct current voltage between DB61 and on the inverter P C board 4 Voltage between outdoor terminal block S1 S2 1 Heat the compressor with a drier for about 20 minutes Do not recover refrigerant gas while heating Heating part Connect the compressor and activate the inverter Then measure the time until the inverter stops due to over current Operation me...

Страница 21: ...ITERION OF MAIN PARTS In case CN721 is disconnected or R V coil is open voltage is generated between the terminal pins of the connector although no signal is being transmitted to R V coil Check if CN721 is connected Is there 208 230 VAC between CN721 and on the inverter P C board 3 minutes after the power supply is turned ON No Yes Replace the inverter P C board Replace the 4 way valve Unit operat...

Страница 22: ...y and measure the voltage of CN931 Between 1 and 5 Between 2 and 5 Between 3 and 5 Does the voltage between each terminal become 5 and 0 VDC repeatedly Does the outdoor fan motor rotate smoothly Replace the outdoor fan motor Replace the inverter P C board Yes Yes No Fixed to either 5 or 0 VDC No No Yes Check the connection between the connector CN931 and CN932 Disconnect the connectors CN931 and C...

Страница 23: ...d Refer to 10 6 TEST POINT DIAGRAM AND VOLTAGE No Check the electric parts in main circuit Yes Yes No Disconnect the connector between compressor and intelligent power module Turn ON power supply and press the TEST button twice on the indoor unit or remote controller Inverter P C board Solder side DB61 260 370 VDC K Check of LEV Expansion valve Turn on power supply to the outdoor unit after checki...

Страница 24: ... CN931 CN932 of the outdoor fan motor If the connection is poor make it correct Operate the outdoor unit by starting EMERGENCY OPERATION Check the LED indication on the in verter P C board Does the LED blink 10 times Replace the inverter P C board Check the corresponding parts following LED indication Refer to 10 3 HOW TO PR CEED SELF DIAGNOSIS Yes No Yes 10 time blink No 10 CD t t t I I t t I 1 ...

Страница 25: ...N the power supply Does the LED on the inverter P C board or the outdoor electronic control P C board repeat 3 6 second OFF and 0 8 second ON quick blinking 3 Yes No Lighted or not lighted Replace the inverter P C board 2 Is there amplitude of 10 to 20 VDC between the indoor terminal block S2 and S3 Confirmation of serial signal Yes Check the wiring If there are any error of the indoor outdoor con...

Страница 26: ...re both ambient temperature thermistor and circuit of defrost heater securely connected to connectors Is there 208 230 VAC between CN722 and on the inverter P C board Refer to 10 6 1 Not the problem of the inverter P C board Replace the inverter P C board No Yes In HEAT mode for more than 5 minutes let the ambient temperature thermistor continue to read 32 F 0 C or below and let the defrost thermi...

Страница 27: ...trength or the installation condition combination of specific conditions such as antennas or wiring Check the followings before asking for service 1 Devices affected by the electromagnetic noise TV sets radios FM AM broadcast shortwave 2 Channel frequency broadcast station affected by the electromagnetic noise 3 Channel frequency broadcast station unaffected by the electromagnetic noise 4 Layout o...

Страница 28: ... VAC Outdoor heat exchanger temperature thermistor RT68 CN644 Jumper wire for pre heat control setting JK Heater connector CN722 SUZ KA09 12 15NAH2 Fuse F801 T3 15AL250V Back side of unit LEV connector CN724 Output to drive outdoor fan motor CN932 LED 4 14 32 50 68 86 104 0 10 20 30 40 50 60 70 80 90 100 Temperature F Defrost thermistor RT61 Ambient temperature thermistor RT65 Outdoor heat exchang...

Страница 29: ...ating thermo OFF Stop 25 125 1 Set fan speed 2 27 127 1 2 Detection of abnormality of the pipe temperature P8 1 28 128 2 Set temperature in heating 24 124 mode 3 Refer to the table below Refer to the table below Available Not available Fan speed during the cooling thermo OFF Set fan speed Stop Available Not available Heater control 2 SEZ SLZ Set temp 4 5 F ON SEZ SLZ Set temp 1 8 F ON 23 123 1 2 C...

Страница 30: ...intenance setting Maintenance password is required Note The initial maintenance password is 9999 Change the default password as necessary to prevent unauthorized access Have the password available for those who need it If you forget your maintenance password you can initialize the password to the default password 9999 by pressing and holding the F1 and F2 buttons simultaneously for three seconds o...

Страница 31: ...rom the Main menu and press the button Checking the indoor unit No When the button is pressed the target indoor unit will start fan operation If the unit is common or when running all units all indoor units for the selected refrigerant address will start fan operation F1 F2 F3 F4 Function setting Ref address Sending data Grp 5 When the settings are completed press the button to send the setting da...

Страница 32: ...RE PHOTOS FIGURES 1 Removing the cabinet 1 Remove the screw fixing the service panel 2 Pull down the service panel and remove it 3 Remove the screws fixing the conduit cover 4 Remove the conduit cover Photo 4 5 Remove the screw fixing the conduit plate Photo 5 6 Remove the conduit plate 7 Disconnect the power supply wire and indoor outdoor connecting wire 8 Remove the screws fixing the top panel 9...

Страница 33: ...xing screws of the terminal block support and the back panel 6 Remove the inverter assembly 7 Remove the screw of the ground wire and screw of the ter minal block support 8 Remove the heat sink support from the P C board support 9 Remove the screw of the inverter P C board and remove the inverter P C board from the P C board support Photo 6 3 Removing R V coil 1 Remove the cabinet and panels Refer...

Страница 34: ...tor and discharge temperature ther mistor CN643 Ambient temperature thermistor CN644 Outdoor heat exchanger temperature thermistor 3 Pull out the discharge temperature thermistor from its holder 4 Pull out the defrost thermistor from its holder 5 Pull out the outdoor heat exchanger temperature thermistor from its holder 6 Pull out the ambient temperature thermistor from its holder Photo 8 Photo 9 ...

Страница 35: ...35 OCH699A ...

Страница 36: ...HIYODA KU TOKYO100 8310 JAPAN Copyright 2018 MITSUBISHI ELECTRIC CORPORATION Issued Jun 2021 No OCH699 REVISED EDITION A Published Dec 2018 No OCH699 Made in Japan Specifications are subject to change without notice MITSUBISHI ELECTRIC CORPORATION ...

Отзывы: