3
OCH699A
Outdoor unit model
SUZ-KA09NA(H)2
SUZ-KA12NA(H)2
SUZ-KA15NA(H)2
Power supply
V , phase , Hz
208/230 , 1 , 60
Max. fuse size (time delay)
A
15
Min. circuit ampacity
A
9
9
10
Fan motor
F.L.A
0.50
Compressor
Model
KNB073FRVMC
SNB092FQAMT
SNB130FQBMT
R.L.A
6.2
6.6
7.4
L.R.A
7.7
8.2
9.3
Refrigeration oil oz(L)/
(Model)
9.1(0.27)/(FV50S)
11.8(0.35)/(FV50S)
11.8(0.35)/(FV50S)
Refrigerant control
Linear expansion valve
Sound level
*
1
Cooling
dB(A)
48
49
49
Heating
dB(A)
50
51
51
Defrost method
Reverse cycle
Dimensions
W
in
31-1/2
D
in
11-1/4
H
in
21-5/8
Weight
Ib
81
External finish
Munsell 3Y 7.8/1.1
Control voltage (by built-in transformer)
VDC
12 - 24
Refrigerant piping
Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid
in
1/4 (0.0315)
Gas
in
3/8 (0.0315)
1/2 (0.0315)
Connection method Indoor
Flared
Outdoor
Flared
Between the indoor
& outdoor units
Height difference
ft
40
Piping length
ft
65
Refrigerant charge (R410A)
2 lb 5 oz
2 lb 9 oz
Note: Test conditions are based on AHRI 210/240.
Rating conditions (Cooling) — Indoor: 80˚F D.B., 67˚F W.B., Outdoor: 95˚F D.B., (75˚F W.B.)
(Heating) — Indoor: 70˚F D.B., 60˚F W.B., Outdoor: 47˚F D.B., 43˚F W.B.
3
SPECIFICATION
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage
Guaranteed voltage (V)
Outdoor unit
208/230 V
1 phase
60 Hz
Min. 187
208
230 Max. 253