5.1 Selection of location for installation
(1)
Indoor unit
(a)
Where there is no obstructions to the air flow and where the cooled
air can be evenly distributed.
(b)
A solid place where the unit or the wall will not vibrate.
(c)
(d)
A place where there will be enough space for servicing. (Where
space mentioned below can be secured)
Where wiring and the piping work will be easy to conduct.
(e)
The place where receiving part is not exposed to the direct rays of
the sun or the strong rays of the street lighting.
(f)
A place where it can be easily drained.
(g)
A place se
(h)
A place that home appliance and household goods, etc. are not below unit.
parated at least 1m away from the television or the radio.
(To prevent interference to images and sound.)
(2)
Outdoor unit
(a)
A place where good air circulation can be obtained and where rain, snow or sunshine will not directly strike the unit.
• A place where intake air temperature is over 46˚C , it is desirable to install a roof avoiding the sunlight.
(b)
A place where discharged hot air or unit’s operating sound will not be a nuisance to the neighborhood.
(c)
(d)
A place where servicing space can be secured.
A place where vibration will not be enlarged.
(e)
Avoid installing in the following places.
• A place near the bedroom and the like, so that the operation noise will cause no trouble.
• A place where there is possibility of flammable gas leakage.
• A place exposed to strong wind.
• In a salt-laden atmosphere or a place where the generation of oil mist, vapor or fume is expected.
.
Model
All models
Item
One way piping length (
r
)
25 m
Outdoor
unit is lower
15 m
Outdoor unit
is higher
15 m
Left
side
Right
side
5 cm
10 cm
1.5 cm
6.5 cm
Air inlet
Air inlet
Air
Outlet
100
100
600
No obstacles
(Service space
for electrical
parts)
Unit : mm
Notes (1) Blowing out port and suction port on the back side of the unit can be
installed at a distance of 10cm from walls.
In case the barrier is 1.2m or above in height, or is overhead, the
sufficient space between the unit and wall shall be secured.
(2) When the unit is installed, the space of the following dimension and
above shall be secured.
(3)
Limitations for one way piping length and vertical
height difference.
( )
Vertical height
difference (h)
h
r
Содержание SRK19CIS
Страница 2: ... 1 TECHNICAL MANUAL ...
Страница 43: ... 42 MEMO ...
Страница 44: ... 43 PARTS LIST INDOOR UNIT SRK19CIS SRK25CIS OUTDOOR UNIT SRC19CIS SRC25CIS ...
Страница 45: ... 44 ...
Страница 46: ... 45 ...
Страница 47: ... 46 ...
Страница 48: ... 47 ...
Страница 49: ... 48 ...
Страница 50: ... 49 ...
Страница 51: ... 50 ...
Страница 52: ... 51 ...
Страница 53: ... 52 ...
Страница 54: ... 53 ...
Страница 55: ... 54 ...
Страница 56: ... 55 ...
Страница 57: ... 56 ...
Страница 58: ... 57 ...
Страница 59: ... 58 ...
Страница 60: ... 59 ...
Страница 61: ... 60 ...
Страница 62: ... 61 ...
Страница 63: ... 62 ...
Страница 64: ... 63 ...
Страница 65: ...ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST Manual No 09 SRK T 086 ...