2 SPECIFICATIONS
2.1 Performance Specifications
17
2
2
SPECIFICATIONS
This chapter describes the performance specifications.
2.1
Performance Specifications
This section describes the performance specifications of temperature input modules.
Thermocouple input module
*1 Except for the conditions under noise influence.
*2 This conversion speed is the time required to store a measured temperature value into the buffer memory in sampling processing.
*3 No isolation is provided between the cold junction compensation channel and the programmable controller power supply.
*4 A count more than 50000 times causes Number of writes to offset/gain settings reach limit error (error code: 1080H).
Item
Specifications
Model
R60TD8-G
Number of analog input channels
8 ch Cold junction compensation channel per module
Output
Measured temperature value
16-bit signed binary value (-2700 to 18200)
Scaling value
16-bit signed binary value
Compliant thermocouple standard
JIS C1602-1995, IEC 60584-1(1995), IEC60584-2(1982)
Usable thermocouples and conversion accuracy
For details, refer to the following.
Page 40 Usable thermocouple, conversion accuracy, and effect per wiring resistance 1
Cold junction compensation accuracy
1.0
Accuracy
For details, refer to the following.
Page 40 Accuracy of the thermocouple input module
Resolution
B, R, S, N: 0.3
K, E, J, T: 0.1
Conversion speed
30ms/channel
Isolation method
Between thermocouple input channel and
programmable controller power supply
Transformer isolation
Between thermocouple input channels
Transformer isolation
Withstand voltage
Between thermocouple input channel and
programmable controller power supply
500VACrms for 1 minute
Between thermocouple input channels
1000VACrms for 1 minute
Insulation
resistance
Between thermocouple input channel and
programmable controller power supply
500VDC 10M
or higher
Between thermocouple input channels
500VDC 10M
or higher
Disconnection detection
Built-in
Number of offset/gain settings
50000 times maximum
Number of occupied I/O points
16 points (I/O assignment: Intelligent 16 points)
External interface
40-pin connector
Applicable wire
size
When A6CON1 and A6CON4 are used
0.088 to 0.3mm
2
(28 to 22 AWG) (stranded wire)
When A6CON2 is used
0.088 to 0.24mm
2
(28 to 24 AWG) (stranded wire)
Connector for external devices
A6CON1, A6CON2, A6CON4 (sold separately)
Internal current consumption (5VDC)
0.36A
External
dimensions
Height
106mm
Width
27.8mm
Depth
110mm
Weight
0.19kg