3 - 3 3 - 3
MELSEC-Q
3 SPECIFICATIONS
(3) QD62D (differential input sinking output type) performance
specifications
Model name
Item
QD62D
Counting speed switch settings 1
500 k
(200 k to 500 kPPS)
200 k
(100 k to 200 kPPS)
100 k
(10 k to 100 kPPS)
10 k
(10 kPPS or less)
I/O occupied points
16 points (I/O assignment: Intelligent 16 points)
Number of channels
2 channels
Phase
1-phase input, 2-phase input
Count input
signal
Signal level (
φ
A,
φ
B)
EIA Standard RS-422-A
Differential line driver level (AM26LS31 [manufactured by Texas Instruments] or equivalent)
Counting speed (max)
2
500 kPPS
200 kPPS
100 kPPS
10 kPPS
Counting range
32-bit signed binary values (–2147483648 to 2147483647)
Model
UP/DOWN Preset c Ring counter function
Counter
Minimum count pulse
width (Duty ratio 50 %)
1
1
2
(Unit: s)
(Min. phase
differential for 2-phase
input: 0.5
μ
s)
2.5 2.5
5
(Unit: s)
(Min. phase
differential for 2-phase
input: 1.25
μ
s)
5
5
10
(Unit: s)
(Min. phase
differential for 2-phase
input: 2.5
μ
s)
50 50
100
(Unit: s)
(Min. phase
differential for 2-phase
input: 25
μ
s)
Comparison range
32-bit signed binary values
Coincidence
output
Comparison result
Set value < Count value
Set value = Count value
Set value > Count value
Preset
External
input
Function start
5/12/24 V DC 2 to 5 mA
(EIA Standard RS-422-A Differential Line Driver may be connected)
External
output
Coincidence output
Transistor (sinking type) output: 2 points/channel
12/24 V DC 0.5 A/point 2 A/common
5 V DC internal current consumption
0.38 A
Weight
0.12 kg
1: The counting speed switch settings can be set using the intelligent function module switch.
2: Counting speed is affected by pulse rise and fall time. Possible counting speeds are shown in the following
table. Note that if a pulse that has a large rise and/or fall time is counted, a miscount may occur.
Counting speed switch settings
500 k
200 k
100 k
10 k
Rise/fall time
Both 1 and 2 phase input
t = 0.5
μ
s or less
500 kPPS
200 kPPS
100 kPPS
10 kPPS
t = 1.25
μ
s or less
200 kPPS
200 kPPS
100 kPPS
10 kPPS
t = 2.5
μ
s or less
—
100 kPPS
100 kPPS
10 kPPS
t = 25
μ
s or less
— —
10 kPPS
10 kPPS
t = 500
μ
s
— — —
500 PPS
t
t
Содержание QD62
Страница 1: ......
Страница 2: ......
Страница 13: ...A 11 A 11 MEMO ...
Страница 55: ...4 18 4 18 MELSEC Q 4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION MEMO ...
Страница 91: ...7 17 7 17 MELSEC Q 7 UTILITY PACKAGE GX Configurator CT Counter selection 1 Coincidence output Ring counter ...
Страница 97: ...8 5 8 5 MELSEC Q 8 PROGRAMMING 3 Program example a Set only when the linear counter is used ...
Страница 100: ...8 8 8 8 MELSEC Q 8 PROGRAMMING 2 Program example a Set only when the ring counter is used ...
Страница 127: ......
Страница 128: ......