3 - 5 3 - 5
MELSEC-Q
3 SPECIFICATIONS
3.3 I/O Signals for the Programmable Controller CPU
3.3.1 List of I/O signals
The I/O signals for the QD62(E/D) programmable controller CPU are listed in the table
below.
For the I/O numbers (X/Y) and I/O addresses indicated in this and succeeding sections,
it is assumed that the QD62(E/D) is mounted into I/O slot 0 of the standard base
module.
Input signal (Signal direction QD62(E/D)
programmable controller CPU)
Output signal (Signal direction programmable
controller CPU QD62(E/D))
Device No.
Signal name
Device No.
Signal name
X00
Module ready
Y00
Coincidence signal No. 1 reset command
X01
Counter value large (point No. 1)
Y01
Preset command
X02
Counter value coincidence (point No. 1)
Y02
Coincidence signal enable command
X03
Counter value small (point No. 1)
Y03
Down count command
X04
External preset request detection
Y04
Count enable command
X05
Counter value large (point No. 2)
Y05
External preset detection reset command
X06
Counter value coincidence (point No. 2)
Y06
Counter function selection start command
X07
CH1
Counter value small (point No. 2)
Y07
CH1
Coincidence signal No. 2 reset command
X08
Counter value large (point No. 1)
Y08
Coincidence signal No. 1 reset command
X09
Counter value coincidence (point No. 1)
Y09
Preset command
X0A
Counter value small (point No. 1)
Y0A
Coincidence signal enable command
X0B
External preset request detection
Y0B
Down count command
X0C
Counter value large (point No. 2)
Y0C
Count enable command
X0D
Counter value coincidence (point No. 2)
Y0D
External preset detection reset command
X0E
CH2
Counter value small (point No. 2)
Y0E
Counter function selection start command
X0F
Fuse broken detection flag
Y0F
CH2
Coincidence signal No. 2 reset command
Содержание QD62
Страница 1: ......
Страница 2: ......
Страница 13: ...A 11 A 11 MEMO ...
Страница 55: ...4 18 4 18 MELSEC Q 4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION MEMO ...
Страница 91: ...7 17 7 17 MELSEC Q 7 UTILITY PACKAGE GX Configurator CT Counter selection 1 Coincidence output Ring counter ...
Страница 97: ...8 5 8 5 MELSEC Q 8 PROGRAMMING 3 Program example a Set only when the linear counter is used ...
Страница 100: ...8 8 8 8 MELSEC Q 8 PROGRAMMING 2 Program example a Set only when the ring counter is used ...
Страница 127: ......
Страница 128: ......