VIII
Test Run Mode ]
- 117 -
HWE1517A
GB
[2] Operating the Unit
1. Initial Operation
(1) Make sure the Run/Stop switch that controls the unit on the local control panel is switched off.
(2) Switch on the main power.
(1) To start the unit
(2) To stop the unit
Set the switch SWS1 on the circuit board to "LOCAL."
Set the switch SWS1 on the circuit board to "OFF."
(3) Leave the main power switched on for at least 12 hours before turning on the Run/Stop switch that controls the
(The compressor will not be warmed up if initial settings have not been made. Make sure to make initial settings.)
unit on the on-site control panel to warm up the compressor.
(4) Switch on the Run/Stop switch that controls the unit on the on-site control panel.
2. Daily Operation
3. Operating the unit from the control board on the unit.
To start an operation
Switch on the Run/Stop switch that controls the unit on the local control panel, or press the ON/OFF button on the
remote controller. (*1)
Note
The unit described in this manual features a circuit that protects the compressor from short-cycling. Once the
compressor stops, it will not start up again for up to 10 minutes. If the unit does not start when the ON/OFF switch
is turned on, leave the switch turned on for 10 minutes. The unit will automatically start up within 10 minutes.
To stop an operation
Switch off the Run/Stop switch that controls the unit on the on-site control panel, or press the ON/OFF button on
the remote controller. (*1)
Refer to the following pages for how to use the remote controller.
IMPORTANT
• Keep the main power turned on throughout the operating season, in which the unit is stopped for three days or
shorter (e.g., during the night and on weekends).
• Unless in areas where the outside temperature drops to freezing, switch off the main power when the unit will not
be operated for four days or longer. (Switch off the water circulating pump if the pump is connected to a separate
circuit.)
• When resuming operation after the main power has been turned off for a full day or longer, follow the steps under
“Initial Operation” above.
• If the main power was turned off for six days or longer, make sure that the clock on the unit is correct.
0000001906.book 117 ページ 2018年7月19日 木曜日 午前7時22分
Содержание QAHV-N560YA-HPB
Страница 1: ......
Страница 7: ...CONTENTS HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 9: ... 2 HWE1517A GB 0000001906 book 2 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 21: ... I Read Before Servicing 14 HWE1517A GB 0000001906 book 14 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 23: ... 16 HWE1517A GB 0000001906 book 16 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 53: ... 46 HWE1517A GB 0000001906 book 46 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 65: ... 58 HWE1517A GB 0000001906 book 58 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 77: ... 70 IV Remote Controller GB HWE1517A 0000001906 book 70 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 79: ... 72 HWE1517A GB 0000001906 book 72 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 85: ... 78 HWE1517A GB 0000001906 book 78 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 91: ... 84 HWE1517A GB 0000001906 book 84 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 121: ... 114 HWE1517A GB 0000001906 book 114 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 127: ... 120 HWE1517A GB 0000001906 book 120 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 173: ... 166 HWE1517A GB 0000001906 book 166 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 175: ... X Attachments 168 HWE1517A GB 0000001906 book 168 ページ 2018年7月19日 木曜日 午前7時22分 ...
Страница 176: ......