PWFY-7
PWFY-P-NMU-E-BU/PWFY-P-NMU-E-AU (Sept. 2010)
PWF
Y-P-N
MU-E-BU
PWF
Y-P-N
MU-E-AU
3. EXTERNAL DIMENSIONS
(23-5/8)
(11-13/16)
300
600
Fig.
A
Ser
vice space
(front side)
Top vie
w
400(15-3/4)
Piping space (r
ight side)
Drain (R1 scre
w)
ø9.52(3/8) <Braz
ed>
P72:Use the Expansion joint of accessor
ie
s
ø27(1-3/32) Knoc
kout hole
<Hole f
or control wir
ing>
ø27(1-3/32) Knoc
kout hole
<Hole f
or po
wer supply>
W
ater outlet
(RC3/4 scre
w)
W
ater inlet
(R3/4 scre
w)
P36:ø15.88(5/8) <Braz
ed>
P72:ø19.05(3/4) <Braz
ed>
ø27(1-3/32) Knoc
kout hole
<Hole f
or e
xter
nal wir
ing input>
ø27(1-3/32) Knoc
kout hole
<Hole f
or e
xter
nal wir
ing output>
Connection pipe of outdoor unit
(Gas)
Connection pipe of outdoor unit (Liquid)
Front vie
w
Right side vie
w
Control bo
x
Ser
vice panel
Top vie
w
2X2-ø14(9/16) Hole
<Accessor
ies>
• Y
-type strainer (RC3/4) ················ 1pc.
•
Heat Insulation mater
ial ·············· 1pc.
•
Connector set ······························ 2set
•
W
asher ········································ 2pcs
.
•
Expansion joint(P72) ··················· 2pcs
.
[F
rom RC3/4 to RC1]
(3-15/16)
(8-1/8)
(4-1/2)
(2-3/8)
(3-5/32)(5-17/32)
(5-9/32)
(1-13/16)
(7-17/32)
(6-1/2)
(2-5/32)
(4-1/32)
(1-13/32)
(2-3/16)
525(20-11/16)
91(3-19/32)
91(3-19/32)
35(1-13/32)
55
35
480(18-29/32)
102
206
134
114
100
191
46
60
140
80
165
54
(Mounting pitch)
450(17-23/32)
300(11-13/16)
(Mounting pitch)
205(8-3/32)
800(31-1/2)
500(19-11/16)
<Unit:mm(in)>
Note 1.
Ensure no
wa
ter or debr
is can enter the unit through an
y gaps around
wi
ring or piping.
2.
Ensure adequate ser
vice space is
right around the unit, according to Fig A.
3.
Please al
wa
ys mak
e w
ater circulate or add the br
ine to the circulation w
ater
when the ambient temper
ature becomes 0degC(32
°
F )or less
.
4.
The unit is not designed f
or outside installations
.
5.
Install the unit in an en
vironment where the
we
t bu
lb
Temp
.
will not e
xceed 32degC(90
°
F)
.
6.
The w
ater circuit must use the closed circuit.
7.
Please don't use the steel mater
ial
fo
r the
wa
ter piping mater
ial.
8.
Connect the st
ra
iner which is put as accessor
y to
wa
ter inlet pipe
.
PWFY-P36,72NMU-E-AU