58
Active filter module
PUZ-HA30NHA5 PUZ-HA36NHA5
L1, L2
Connect to the
DCL(Reactor)
Connect to the
outdoor power
circuit board
(TABP1)
Connect to the outdoor power
circuit board(TABN1)
+
–
Io
Connect to the outdoor power
circuit board (TABN2)
N2
Non-connect
N1
Non-connect
P
Connect to the outdoor power
circuit board (TABP2)
Connect to the outdoor power
circuit board(CNAF)
1
: GND
2
–
1
: 18 V DC
3
–
1
: Control signal
4
,
5
: Not used
6
–
1
: Control signal
Upper side
Lower side
+
DCL
L1
L2
ACTM
P
Io
N1
N2
(+)
(- )
Load
Connection and internal circuit diagram
Error condition Normal value (reference)
Symptom when the unit is in trouble
(–) and Io
open
less than 1
"
1
The unit does not operate (cannot be switched ON)
(–) and L2
short
100 k
"
to 1 M
"
1
The breaker operates
open
*1
1
The unit does not operate (cannot be switched ON)
2
U9 Abnormal stop (*2)
P and L2
short
100 k
"
to 1 M
"
1
The breaker operates
open
*1
1
The unit does not operate (cannot be switched ON)
2
U9 Abnormal stop (*2)
P and Io
short
100 k
"
to 1 M
"
1
The breaker operates
open
*1
1
The unit does not operate (cannot be switched ON)
2
U9 Abnormal stop (*2)
L2 and Io
short
100 k
"
to 1 M
"
1
The breaker operates
open
*1
1
The unit does not operate (cannot be switched ON)
2
U9 Abnormal stop (*2)
Tester check points of Active filter module
*1. The symptom when the unit is in open error condition is described to determine open error by tester check.
*2. SW2 setting : Code "20" display
1
6
ON
OFF
OCH607