II
Restrictions ]
- 52 -
HWE09130
GB
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes
will be used between the main and the sub BC controllers.
2) When connecting two sub BC controllers, observe the maximum allowable length in the table above.
3) When connecting two sub BC controllers, install them in parallel.
4) To connect the P72 through P96 models of indoor units, use an optional twinning pipe kit (Model: CMY-R160-J) and merge
the two ports before connecting them.
5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
6) Note the following when connecting multiple indoor units to a single port.
Those indoor units connected to the same port must be installed in the same room.
Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or
below (when two GB type controllers are connected P126 or below for both combined) .
The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below.
If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with
two sub controllers is P168 or below.
0
10
20
30
40
50
60
70
0
5
10
15
[PURY-P168TSJMU-A]
[PURY-P168YSJMU-A]
[PURY-P192TSJMU-A]
[PURY-P192YSJMU-A]
[PURY-P264, P288TSJMU-A]
[PURY-P264, P288YSJMU-A]
10
20
30
40
50
60
70
80
90
100 110
[32] [64]
[98] [131] [164] [196] [229] [262] [295] [328] [360]
1000
900
800
700
600
500
400
300
200
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
[PURY-P216, P240TSJMU-A]
[PURY-P216, P240YSJMU-A]
The height difference and the pipe length between BC controller and indoor units
Restrictions on pipe length
Aggregate length of all pipes(m[ft])
Aggregate length of all pipes(m[ft])
Aggregate length of all pipes(m[ft])
Aggregate length of all pipes(m[ft])
Pipe length between main BC
controller and farthest indoor unit (m[ft])
Height difference between main BC controller and farthest indoor unit (m[ft])
[32]
[16]
[32]
[49]
[64]
[98]
[131]
[164]
[196]
[229]
110
1000
900
800
700
600
500
400
300
200
10
20
30
40
50
60
70
80
90
100
Pipe length between outdoor unit and BC controller (m[ft])
[32] [64]
[98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
110
1000
900
800
700
600
500
400
300
200
10
20
30
40
50
60
70
80
90
100
Pipe length between outdoor unit and BC controller (m[ft])
[32] [64]
[98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
110
1000
900
800
700
600
500
400
300
200
10
20
30
40
50
60
70
80
90
100
Pipe length between outdoor unit and BC controller (m[ft])
Pipe length between outdoor unit and BC controller (m[ft])
[32] [64]
[98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Содержание PURY-P120
Страница 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 36: ... II Restrictions 27 HWE09130 GB ...
Страница 50: ... II Restrictions 41 41 HWE09130 GB ...
Страница 67: ... 58 II Restrictions GB HWE09130 ...
Страница 69: ... 60 ...
Страница 94: ... III Outdoor Unit Components 85 HWE09130 GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Страница 97: ... 88 ...
Страница 105: ... 96 IV Remote Controller GB HWE09130 ...
Страница 107: ... 98 ...
Страница 124: ... 115 HWE09130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 117 2 Principal Parts and Functions 126 ...
Страница 125: ... 116 ...
Страница 145: ... 136 ...
Страница 175: ... 166 VII Control GB HWE09130 ...
Страница 177: ... 168 ...
Страница 203: ... 194 ...
Страница 363: ... 354 IX Troubleshooting GB HWE09130 ...
Страница 364: ... 355 HWE09130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 357 ...
Страница 365: ... 356 ...