IX
Troubleshooting ]
- 296 -
HWE09130
GB
YES
YES
YES
YES
YES
NO
NO
NO
NO
Replace the control board.
Replace 52F.
Is the wiring between the
FAN board, 52F, and fan
motor connected correctly?
Does 52F operate on the
coil voltage (206-252V)?
Check the wiring between
52F and the control board.
Check that the secondary voltage on the
transformer is between 206V and 252V.
Fuse is normal
Is a voltage of
between 188V and 253V (TJMU) or
between 414V and 506V (YJMU)
applied to the power supply input?
Correct the wiring according to the wiring
diagram.
Correct the wiring according to the
wiring diagram.
NO
Replace the transformer and fuse.
Содержание PURY-P120
Страница 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 36: ... II Restrictions 27 HWE09130 GB ...
Страница 50: ... II Restrictions 41 41 HWE09130 GB ...
Страница 67: ... 58 II Restrictions GB HWE09130 ...
Страница 69: ... 60 ...
Страница 94: ... III Outdoor Unit Components 85 HWE09130 GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Страница 97: ... 88 ...
Страница 105: ... 96 IV Remote Controller GB HWE09130 ...
Страница 107: ... 98 ...
Страница 124: ... 115 HWE09130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 117 2 Principal Parts and Functions 126 ...
Страница 125: ... 116 ...
Страница 145: ... 136 ...
Страница 175: ... 166 VII Control GB HWE09130 ...
Страница 177: ... 168 ...
Страница 203: ... 194 ...
Страница 363: ... 354 IX Troubleshooting GB HWE09130 ...
Страница 364: ... 355 HWE09130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 357 ...
Страница 365: ... 356 ...