IX
Troubleshooting ]
- 236 -
HWE09130
GB
1. Error
Code
Liquid inlet temperature sensor (TH11) fault (BC controller)
Bypass outlet temperature sensor (TH12) fault (BC controller)
LEV3 outlet temperature sensor (TH15) fault (BC controller)
LEV3 inlet temperature sensor (TH16) fault (BC controller)
2. Error definition and error detection method
If a shorted (high temperature intake) or open (low temperature intake) thermistor (TH11, TH12, TH15, or TH16) is detected
during operation, the unit makes an error stop, and an error code "5111," "5112," "5115," or "5116" appears on the display.
Detection of a short- or open-circuit as described above is suspended during the defrost cycle and for 3 minutes after the
operation mode is changed.
3. Cause, check method and remedy
<Reference>
5111
5112
5115
5116
Cause
Check method and remedy
(1)
Thermistor failure
Check thermistor resistance.
(2)
Pinched lead wire
Check for pinched lead wire.
(3)
Torn wire coating
Check for wire coating.
(4)
A pin on the male connector is missing or
contact failure
Check connector.
(5)
Disconnected wire
Check for wire.
(6)
Thermistor input circuit failure on the control
board
Check the intake temperature of the sensor with the LED monitor.
When the temperature is far different from the actual temperature,
replace the control board.
TH11
TH12
TH15
TH16
Open detection
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
-40 C [ -40 F ] and below (130 k )
Short detection
110 C [230 F ] and above (0.4 k )
110 C [230 F ] and above (0.4 k )
70 C [158 F ] and above (0.4 k )
110 C [230 F ] and above (0.4 k )
Содержание PURY-P120
Страница 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 36: ... II Restrictions 27 HWE09130 GB ...
Страница 50: ... II Restrictions 41 41 HWE09130 GB ...
Страница 67: ... 58 II Restrictions GB HWE09130 ...
Страница 69: ... 60 ...
Страница 94: ... III Outdoor Unit Components 85 HWE09130 GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Страница 97: ... 88 ...
Страница 105: ... 96 IV Remote Controller GB HWE09130 ...
Страница 107: ... 98 ...
Страница 124: ... 115 HWE09130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 117 2 Principal Parts and Functions 126 ...
Страница 125: ... 116 ...
Страница 145: ... 136 ...
Страница 175: ... 166 VII Control GB HWE09130 ...
Страница 177: ... 168 ...
Страница 203: ... 194 ...
Страница 363: ... 354 IX Troubleshooting GB HWE09130 ...
Страница 364: ... 355 HWE09130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 357 ...
Страница 365: ... 356 ...