IX
Troubleshooting ]
- 323 -
HWE09130
GB
Items to be checked
Phenomena
Remedy
[4]
Check whether
the inverter is
damaged.
(During com-
pressor opera-
tion)
Put the outdoor unit into oper-
ation.
Check the inverter output volt-
age after the inverter output
frequency has stabilized.
1)
Overcurrent-related problems oc-
cur immediately after compressor
startup.Error code : 4250Detail
code : 101, 106, 107
a.Check items [1] through [3]
for problems.
b.Check that high and low
pressures are balanced.
c.Check that no liquid refriger-
ant is present in the com-
pressor.
Go to "d." when the prob-
lem persists after compres-
sor startup was repeated
several times.
If normal operation is re-
stored, check the belt heater
for problems.
d.Check that there is a pres-
sure difference between
high and low pressures after
compressor startup.
Check the high pressure
with LED monitor for chang-
es.
Replace the compressor if
there is no pressure differ-
ence. (the compressor may
be locked.)
2)
There is a voltage imbalance be-
tween the wires after the inverter
output voltage is stabilized.
Greater than the larger of the fol-
lowing values: imbalance of 5% or
5V
Replace the INV board if there
is a voltage imbalance.
Check the belt heater for prob-
lems if there is no voltage im-
balance.
When the error occurred,
liquid refrigerant may have
been present in the compres-
sor.
[5]
Check the fan
motor ground
fault or the
winding.
Remove the wire for the out-
door fan motor, and check the
fan motor megger and the
winding resistance.
1)
Fan motor megger failure
Failure when the megger is 1Mohm
or less.
Replace the fan motor.
2)
Fan motor disconnection
Standard: The winding resistance
is approximately several ohm.
(It varies depending on the temper-
ature, or while the inner thermo is
operating, it will be
ohm)
[6]
Check the FAN
board failure.
(1)
Check the fan output wir-
ing.
Connector contact failure
Board side (CNINV)
Fan motor side
Connect the connector.
(2)
Check the connector CN-
VDC connection.
Cnnector contact failure
Connect the connector.
(3)
Check the FAN board
failure.
1)
The voltage imbalance among
each motor wiring during operation
(The voltage imbalance is greater
than the larger of the values repre-
sented by 5% or 5 V.)
Replace the FAN board.
2)
The same error occurs even after
the operation is restarted.
[YJMU-A]
Содержание PURY-P120
Страница 1: ...Models PURY P72 P96 P120 P144T Y JMU A PURY P168 P192 P216 P240 P264 P288T Y SJMU A ...
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 36: ... II Restrictions 27 HWE09130 GB ...
Страница 50: ... II Restrictions 41 41 HWE09130 GB ...
Страница 67: ... 58 II Restrictions GB HWE09130 ...
Страница 69: ... 60 ...
Страница 94: ... III Outdoor Unit Components 85 HWE09130 GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 95: ... 86 III Outdoor Unit Components GB HWE09130 ...
Страница 97: ... 88 ...
Страница 105: ... 96 IV Remote Controller GB HWE09130 ...
Страница 107: ... 98 ...
Страница 124: ... 115 HWE09130 GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 117 2 Principal Parts and Functions 126 ...
Страница 125: ... 116 ...
Страница 145: ... 136 ...
Страница 175: ... 166 VII Control GB HWE09130 ...
Страница 177: ... 168 ...
Страница 203: ... 194 ...
Страница 363: ... 354 IX Troubleshooting GB HWE09130 ...
Страница 364: ... 355 HWE09130 GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 357 ...
Страница 365: ... 356 ...